DISPLAYING SYSTEM SETPOINTS

DISPLAYING SYSTEM SETPOINTS

The currently programmed Setpoint values can be viewed at any time (see page 22) in SERVICE, LOCAL or REMOTE operating mode as follows:

Press and release the appropriate Setpoint key – the message will be displayed for 2 seconds.

or –

Press and hold the appropriate Setpoint key – the message will be displayed as long as the key is pressed.

or –

Press and release the appropriate Setpoint key, then press and release the DISPLAY HOLD key. The mes- sage will be displayed until the DISPLAY HOLD key is again pressed and released, or 10 minutes have elapsed, whichever comes first.

To Display CHILLED LIQUID TEMP Setpoint:

Use CHILLED LIQUID TEMP setpoint key as de- scribed on page 10 to produce the following mes- sage:

LEAVING SETPOINT = XX.X °F

NOTE: The value displayed is the actual LCWT setpoint. For example, the value displayed in LOCAL or PROGRAM modes is that which is operator pro- grammed. The value displayed in the REMOTE mode is that base setpoint with added tempera- ture reset by an Energy Management System, via remote LCWT setpoint (PWM signal) if a re- mote reset signal was received within 30 min- utes.

To Display % CURRENT LIMIT Setpoint:

Use % CURRENT LIMIT setpoint key as described above to produce the following message:

CURRENT LIMIT = XXX % FLA

NOTE: The value displayed is the actual % current limit setpoint. For example, the value displayed in LOCAL or PROGRAM mode is that which is operator programmed. The value displayed in the REMOTE mode is that which has been pro- grammed by the Energy Management System via the remote current limit setpoint input.

If chiller is equipped with a YORK Solid State Starter, the message is:

CURRENT LIMIT = XXX % FLA; *MTR CUR = 000 FLA

NOTE: On Solid State Starter applications, this value is programmed at the YORK factory. A special ac- cess code is required.

To Display PULL DOWN DEMAND Setpoint:

Use PULL DOWN DEMAND setpoint key as de- scribed on page 10 to produce the following mes- sage:

SETPOINT = XXX MIN @ XX % FLA XXX MIN LEFT

To Display CLOCK Setpoint (Time of Day):

Use CLOCK setpoint key as described above to produce the following message:

TODAY IS DAY XX:XX AM/PM 1/1/92

To Display DAILY SCHEDULE Setpoints:

Press and hold the DAILY SCHEDULE setpoint key.

The chiller start and stop times for each day of the week are sequentially displayed, beginning with Sun- day and ending with Holiday. The display will continu- ously scroll until the DAILY SCHEDULE key is re- leased.

or –

Press and release the DAILY SCHEDULE setpoint key. Then press and release the DISPLAY HOLD key. The chiller start and stop times for each day of the week are sequentially displayed beginning with Sunday and ending with Holiday.The display will continuously scroll until the DISPLAY HOLD key is again pressed and released, or 10 minutes have elapsed, whichever comes first.

The display message for DAILY SCHEDULE will scroll in the following sequence:

SUN START = 08:30 AM

STOP = 06:00 PM

 

 

MON START = 05:00 AM

STOP = 07:00 PM

 

 

12

YORK INTERNATIONAL

Page 12
Image 12
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Displaying System Setpoints

FAQ

How can I view the currently programmed setpoint values?

You can view the currently programmed setpoint values by following the instructions on page 22 of the official manual for the York heat pump models YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4.

What is the actual value displayed for CHILLED LIQUID TEMP setpoint?

The actual value displayed for CHILLED LIQUID TEMP setpoint is the operator programmed value in LOCAL or PROGRAM mode and the base setpoint with added temperature reset in REMOTE mode.

How do I view the DAILY SCHEDULE setpoints?

You can view the DAILY SCHEDULE setpoints by pressing and holding the DAILY SCHEDULE setpoint key, or by following the instructions on page 22 of the official manual for the York heat pump models YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4.