![•Phase rotation/loss](/images/new-backgrounds/34957/3495751x1.webp)
has increased to 265 PSIG
MON XX:XX AM – EVAP TRANS OR PROBE ERROR
The chiller is shut down because the leaving chilled water temperature minus the evaporator saturation tem- perature is outside the range of
On Steam Turbine applications (Micro Board program jumper JP4 removed), with EPROM version C.02F
(T).12 or later, this check is bypassed for the first 20 minutes of chiller run time and then performed at the regular 10 minute intervals thereafter. This is to allow for the additional time required to decrease the evapo- rator pressure due to the longer acceleration time of the steam turbine.
MON XX:XX AM – MOTOR CONTROLLER – EXT. RESET
The chiller is shut down because a current module
NOTE: The following motor controller shutdowns do not require an external reset to restart chiller.
Solid State Starter 110°F start inhibit. Anytime the chiller has been shut down for any reason, this mes- sage will be displayed until the SCR heatsink tempera- tures decrease to below 110°F.
MON XX:XX AM – POWER FAULT – AUTOSTART
The chiller is shut down because of a Solid State Starter or current module
Solid State Starter application, the shutdown could have been caused by any of the following reasons. The ap- propriate light on the Solid State Starter Logic Board will be illuminated.
•Phase rotation/loss
•Trigger Board out of lock (OOL)
•Power Fault
•Half Phase
MON XX:XX AM – HIGH DISCHARGE TEMP
The chiller is shut down because the discharge tem- perature has increased to 220°F. The system will be allowed to restart when the temperature has decreased to 219°F. Temperature is sensed by a thermistor RT2. To restart the chiller, press COMPRESSOR switch to STOP/RESET position and then to the START posi- tion.
MON XX:XX AM – HIGH OIL TEMP
The chiller is shut down because the oil temperature has increased to 180°F. The system will be allowed to restart when the temperature decreases to 179°F. The temperature is sensed by thermistor RT3. To restart the chiller, press COMPRESSOR switch to STOP/RE- SET position and then to the START position.
MON XX:XX AM – OIL PRESSURE TRANSDUCER
The chiller is shut down because the oil pressure has increased to 125 PSID (during the first 7 minutes of compressor operation) 60 PSID (after the first minutes of compressor operation). The chiller will be allowed to restart when the oil pressure decreases to 59 PSID. To restart the chiller, press COMPRESSOR switch to STOP/RESET position and then to the START posi- tion.
MON XX:XX AM – FAULTY COND PRESSURE XDCR
The chiller is shut down because the condenser trans- ducer is indicating a pressure of less than 24.2 PSIG
MON XX:XX AM – FAULTY OIL PRESSURE XDCR
The chiller is shut down because either the high side or low side oil pressure transducer was
26 | YORK INTERNATIONAL |