York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 To Display REFRIGERANT PRESSURE

Models: YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 YK M3 M3 G4

1 60
Download 60 pages 33.73 Kb
Page 9
Image 9
To Display CHILLED LIQUID TEMPERATURES:

 

 

 

DISPLAY

 

 

 

READS

CONDENSER PRESS. = < 6.8 PSIG,

or > 300 PSIG

XX.X PSIG

EVAPORATOR PRESS. = < 50 PSIG,

or > 125 PSIG

XX.X PSIG

EVAP. PRESS. (BRINE)

= < 25 PSIG,

or > 100 PSIG

XX.X PSIG

HOP TRANSDUCER

= < 59.1 PSIG, or > 314.9 PSIG

XX.X PSIG

LOP TRANSDUCER

= < 23.2 PSIG, or > 271.8 PSIG

XX.X PSIG

DISCHARGE TEMP.

= < 20.3°F;

> 226.4°F

XXX.X°F

OIL TEMP.

= < 20.3°F;

> 226.4°F

XXX.X°F

LEAVING CONDENSER

=

< 8.4°F;

> 134.1°F

XXX.X°F

WATER TEMP.

 

 

 

 

ENTERING CONDENSER

=

< 8.4°F;

> 134.1°F

XXX.X°F

WATER TEMP.

 

 

 

 

 

 

 

 

LEAVING EVAPORATOR

= < 0°F

 

XX.X°F

WATER TEMP.

= > 81.1°F

 

XX.X°F

 

 

 

 

ENTERING EVAPORATOR

= < .1°F

 

XX.X°F

WATER TEMP.

= > 93°F

 

XX.X°F

 

 

 

 

 

FIG. 4 – SYSTEM PARAMETERS – OUT OF RANGE READINGS

To Display CHILLED LIQUID TEMPERATURES:

Press CHILLED LIQUID TEMPS display key as de- scribed on page 7 to produce the following alphanu- meric display message:

CHILLED LEAVING = XXX.X°F, RETURN = XXX.X°F

To Display REFRIGERANT PRESSURE:

Use REFRIGERANT PRESSURE display key as described on page 7 to produce the following alpha- numeric display message:

EVAP = XXX.X PSIG; COND = XXX.X PSIG

To Display OIL PRESSURE:

Use OIL PRESSURE display key as described on page 7 to produce the following alphanumeric dis- play message:

OIL PRESSURE = XXXX.X PSID

The differential pressure displayed is the pressure dif- ference between the high side oil pressure transducer (output of oil filter) and the low side oil pressure trans- ducer (compressor housing). Displayed value includes offset pressure derived from auto-zeroing during “START SEQUENCE INITIATED”. If either transducer is out-of-range, XX.X is displayed. Oil pressure is calculated as follows:

FORM 160.49-O2

______ PSID = (HOP – LP) – OFFSET PRESSURE

OFFSET PRESSURE: Pressure differential between the HOP transducer and LOP transducer outputs dur- ing a 3 second period beginning 10 seconds after the start of “START SEQUENCE INITIATED”. During this time, the transducers will be sensing the same pres- sure and their outputs should indicate the same pres- sure. However, due to accuracy tolerances in trans- ducer design, differences can exist. Therefore, to com- pensate for differences between transducers and as- sure differential pressure sensing accuracy, the OFF- SET PRESSURE is subtracted algebraically from the differential pressure. The offset pressure calculation will not be performed if either transducer is out-of-range. The offset value will be taken as 0 PSI in this instance.

To Display OPTIONS:

This key is not used.

NO OPTIONS INSTALLED

is displayed when this key is pressed.

To Display SSS MOTOR CURRENT / VOLTS:

(Solid State Starter Applications Only)

If chiller is equipped with a YORK Solid State Starter, use SSS MOTOR CURRENT / VOLTS key to dis- play 3-phase compressor motor current and 3-phase Solid State Starter input line voltage.

Continuously pressing this key will display the mo- tor current and line voltage alternately. When used with the DISPLAY HOLD key, motor current and line voltage will alternately be displayed each time this key is pressed. The messages are as follows:

A AMPS = XXXX; B AMPS = XXXX; C AMPS = XXXX

V A-B = XXXX; V B-C = XXXX; V C-A = XXXX

If chiller is not equipped with a Solid State Starter, this key produces the following message:

SOLID STATE STARTER NOT INSTALLED

In PROGRAM mode, this key is used to display the applicable line voltage range (200-208VAC, 220- 240VAC, 380VAC, 400VAC, 415VAC, 440-480VAC, 500-600VAC, Supply Voltage Range Disabled).The correct line voltage range is programmed at the YORK factory and is checked by the service tech- nician at start-up. For security reasons, a special access code is required to program the line volt- age range. The line voltage range is used to deter- mine a low line voltage threshold for cycling shut- down. Refer to “System Setpoints” for Trip/Reset values.

YORK INTERNATIONAL

9

Page 9
Image 9
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual To Display CHILLED LIQUID TEMPERATURES

FAQ

How do I display chilled liquid temperatures?

Press the CHILLED LIQUID TEMPS display key as described on page 7 to view alphanumerical display messages for CHILLED LEAVING and CHILLED RETURN temperatures.

How can I access refrigerant pressure readings?

Use the REFRIGERANT PRESSURE display key as described on page 7 to access alpha-numeric messages displaying EVAP and COND refrigerant pressures.

What does the OIL PRESSURE display show?

The OIL PRESSURE display key provides alphanumeric messages indicating the oil pressure, including offset pressure derived from auto-zeroing during START SEQUENCE INITIATED.