will be displayed if the Micro Board is configured for
MON XX:XX AM – POWER FAILURE
The chiller is shut down because there has been a power interruption or failure. When power is restored, the chiller can be restarted by pressing the COMPRES- SOR switch to STOP/RESET position and then to START position. This message will be displayed if the Micro Board is configured for MANUAL RESTART AF- TER POWER FAILURE. The Micro Board is factory set for manual restart after power failure. This has been accomplished by removing the
AC UNDERVOLTAGE – AUTOSTART
The chiller is shut down because the MicroComputer Control Center was in RUN mode, displaying
SYSTEM RUN – LEAVING TEMP CONTROL , but the motor current was less than 10% FLA for 25 continuous sec- onds. This is indicative of an AC undervoltage condi- tion that has caused the start relay (1R) in the Micro- Computer Control Center to
SYSTEM RUN – LEAVING TEMP CONTROL .
This check is not performed when program jumper JP4 is removed (Steam Turbine applications).
MON XX:XX AM – INTERNAL CLOCK – AUTOSTART
The
REMOTE STOP
This message will be displayed when a remote device (typically an Energy Management System) has com- manded the chiller to shut down. The chiller will restart upon application of a separate start signal from the remote device. This message will only be displayed
FORM
when Control Center is in REMOTE mode.
The chiller may not restart more frequently than every 30 minutes. Displayed when chiller is shut down and there is time remaining on the
This feature eliminated when program jumper JP4 is removed (Steam Turbine applications).
WARNING: Remove this jumper after servicing. Failure to do this voids the Warranty.
MON XX:XX AM – LOW EVAP PRESSURE
The chiller is shut down because the evaporator pres- sure has decreased to 54.3 PSIG
MON XX:XX AM – LOW EVAP PRESSURE – BRINE
The chiller is shut down because the brine Low Evapo- rator Pressure (LEP, not included with standard Con- trol Center) safety contacts have opened. The brine LEP safety is located external to the Control Center. Safety
MON XX:XX AM – LOW OIL PRESSURE
The chiller is shut down because the oil pressure has decreased to 15 PSID while running, or never achieved 25 PSID prior to compressor start during the oil pump
MON XX:XX AM – HIGH PRESSURE
The chiller is shut down because condenser pressure