York YK M3 M3 G4 operation manual Section, Troubleshooting

Models: YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 YK M3 M3 G4

1 60
Download 60 pages 33.73 Kb
Page 44
Image 44

44

YORK INTERNATIONAL

TABLE 1 – CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL, CENTER DISPLAY

 

SHUTDOWN CAUSE

 

GOVERNING CONTROL FUNCTION

 

 

 

 

CONTROL CENTER DISPLAY

 

 

 

 

 

 

 

 

 

PROGRAMMED

START-UP OF

PROBABLE CAUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING

 

 

 

 

 

 

SETPOINTS

SYSTEM AFTER

AND SERVICE

DAY OF

TIME OF

CAUSE OF

 

METHOD OF

 

POINT

 

DESCRIPTION

BY OPERATOR

SHUTDOWN

REQUIRED

WEEK

DAY

SHUTDOWN

 

RESTART

ON

ON

 

 

 

 

 

 

 

 

 

 

 

RISE

FALL

 

 

 

MON.

10:00 AM

Low Water

 

Autostart

Low Water

Chilled

4°F below

4°F below chilled

Automatic Restart

System load is less

 

 

Temp.

 

 

(LWT)

water

chiller

water setpoint

when water reaches

than minimum

 

 

 

 

 

 

setpoint

water

(If set to 40°F

setpoint; if system

capacity

 

 

 

 

 

 

 

setpoint

would be 36°F)

is running and set-

 

 

 

 

 

 

 

 

 

(36°F minimum

point is increased

 

 

 

 

 

 

 

 

 

 

4°F, system will

 

 

 

 

 

 

 

 

 

 

continue to run, as

 

 

 

 

 

 

 

 

 

 

LWT cutout shifts

 

 

 

 

 

 

 

 

 

 

to a fixed 36°F for

 

 

 

 

 

 

 

 

 

 

10 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

MON.

10:00 AM

Flow Switch

 

Autostart

Flow Switch

 

 

 

Automatic Restart

Lack of water flow.

 

 

 

 

 

 

 

 

 

when water flow is

Check operation of

 

 

 

 

 

 

 

 

 

Restored to close

chilled water pump

 

 

 

 

 

 

 

 

 

flow switch.

 

 

 

 

 

 

 

 

 

 

 

 

MON.

10:00 AM

System

 

Autostart

A remote com-

 

 

 

Automatic Restart

Contact-connected to

 

 

Cycling

 

 

mand (computer

 

 

 

upon remote

the Remote/Local

 

 

 

 

 

relay contact or

 

 

 

command.

cycling input of the

 

 

 

 

 

manual switch)

 

 

 

 

Digital input board

 

 

 

 

 

 

 

 

 

 

 

MON.

10:00 AM

Multi-Unit

 

Autostart

(Optional) Lead-

 

 

 

Automatic Restart

Contact-connected to

 

 

 

 

 

Lag Sequence

 

 

 

upon remote

the Multi-Unit cycling

 

 

 

 

 

Control

 

 

 

command.

input of the Digital

 

 

 

 

 

 

 

 

 

 

input board

 

 

 

 

 

 

 

 

 

 

 

MON.

10:00 AM

Internal

 

Autostart

Internal Clock

 

 

Daily Schedule

Will automatically

Pressing Compressor

 

 

Clock

 

 

 

 

 

Programmed to

restart when pro-

Start Switch over-

 

 

 

 

 

 

 

 

Shutdown Unit

grammed schedule

rides the program

 

 

 

 

 

 

 

 

 

permits

 

 

 

 

 

 

 

 

 

 

 

 

MON.

10:00 AM

AC under-

 

Autostart

<15% FLA for

 

 

 

 

Cycling shutdown oc-

 

 

voltage

 

 

25 continuous

 

 

 

 

curs when motor cur-

 

 

 

 

 

seconds

 

 

 

 

rent is >15% FLA for

 

 

 

 

 

 

 

 

 

 

25 seconds during

 

 

 

 

 

 

 

 

 

 

chiller operation

MON.

10:00 AM

Power Fault

 

Autostart

CM-2 Current

 

 

 

Will start automatic-

Motor Controller con-

 

 

 

 

 

Module or

 

 

 

tically following

tacts opening and

 

 

 

 

 

Solid State

 

 

 

coastdown

closing in less than 3

 

 

 

 

 

Starter

 

 

 

 

seconds due to a power

 

 

 

 

 

 

 

 

 

 

fault condition

 

 

Remote Stop

 

 

Energy manage-

 

 

 

Start up by start

Remote Stop Contact

 

 

 

 

 

ment System

 

 

 

signal from remote

Closure

 

 

 

 

 

 

 

 

 

start switch

 

 

 

 

 

 

 

 

 

 

 

 

MON.

 

Anti-Recycle,

 

 

Anti-Recycle

 

 

Will not start

Will restart when

Min.Time between

 

 

20 Min. Left

 

 

timer

 

 

until 30 Min.

time left = 00 Min.

successive compres-

 

 

 

 

 

 

 

 

timer is timed

 

sor starts is 30 min.

 

 

 

 

 

 

 

 

 

 

 

TROUBLESHOOTING

SECTION 6

Page 44
Image 44
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Section, Troubleshooting

FAQ

What are the causes of normal and safety system shutdowns for York heat pump models YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4?

This article provides detailed information on the causes of normal and safety system shutdowns for the specified York heat pump models.

How can I identify the shutdown cause from the control center display?

The control center display provides information on the shutdown cause, governing control function, and probable cause, helping you identify the reason for the shutdown.

What is the programmed start-up of the system after shutdown and service?

The programmed start-up ensures that the system automatically restarts after a shutdown, providing seamless operation.