OPERATING MODES

NO. 6

ACTUAL POS = XX MILS; REF = YY MILS – ACTUAL POS is

the distance between the high speed thrust collar and the proximity probe that is used to measure the position. REF is the reference position established at time of com- pressor manufacture.

NO. 7

HIGH SPEED DRAIN TEMP = XXX.X °F Temperature of oil in high speed drain line.

FORM 160.49-O2

To hold any of the above messages, press the DISPLAY DATA key, then press the DISPLAY HOLD key. The message will be displayed and updated every 2 sec- onds until the DISPLAY DATA key is pressed again, whereupon the next message is displayed. To return to the normal foreground messages, press the DISPLAY HOLD key.

HISTORY PRINT – This key is used to initiate a history print to the optional printer. Refer to Form 160.49-N7 for operation of this key.

OPERATING MODES

The MicroComputer Control Center can be operated in four different operating modes as follows:

SERVICE – enables all the Service keys except DIS- PLAY DATA, MANUAL OIL PUMP, and HISTORY PRINT, which are enabled in all modes. See “Service Keys”, page 20.

LOCAL – This is the normal operating mode.The com- pressor can be started and stopped from the Control Center. Also, the Display and Setpoints parameters can be displayed.

PROGRAM – Allows the operator to program the Set- points parameters, and change operating modes.

REMOTE – In this mode, the Control Center will ac- cept control signals from a remote device (i.e., Energy Management System) or cycling input. The control sig- nal inputs are:

1.Remote Start

2.Remote Stop

3.Remote LCWT Setpoint

4.Remove Current Limit Setpoint

NOTE: The compressor can be stopped by the COM- PRESSOR switch, regardless of the operating mode. The switch must be in RUN position to enable REMOTE mode. The operator cannot locally start the compressor using the COM- PRESSOR switch when in the REMOTE mode.

To determine which operating mode the Control Center is presently in, simply press the MODE key.

• If the Control Center is in LOCAL mode,

 

LOCAL OPERATING MODE IN EFFECT

 

is displayed.

• If the Control Center is in REMOTE mode,

 

REMOTE OPERATING MODE IN EFFECT

 

is displayed.

• If the Control Center is in SERVICE mode,

 

SERVICE OPERATING MODE IN EFFECT

 

is displayed.

 

 

 

 

To change operating mode, proceed as follows:

1.Press ACCESS CODE key.

2. ENTER VALID ACCESS CODE _ _ _ _ is displayed.

3.Using Entry keys, enter 9 6 7 5.

4.As each digit is entered, the characters Y O R K are displayed.

NOTE: If digits other than 9 6 7 5 are entered, Y O R K is still displayed.

5.Press ENTER key.

NOTE: If digits other than 9 6 7 5 were entered in

 

step No. 4,

INVALID ACCESS

CODE

is dis-

 

played when the ENTER key is pressed. If

 

this occurs, enter the correct access code

 

(9675) and proceed.

 

 

6.

 

 

is displayed.

ACCESS TO PROGRAM KEY AUTHORIZED

NOTE: Unless terminated by pressing the ACCESS CODE key again, the operator will have ac- cess to the PROGRAM key for 10 minutes. When 10 minutes have elapsed, access to PROGRAM key will be automatically dis- abled and the operator must return to step No. 1 to gain access.

YORK INTERNATIONAL

21

Page 21
Image 21
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Operating Modes, Press ACCESS CODE key

FAQ

What is actual position in the context of a heat pump?

Actual position is the distance between the high speed thrust collar and the proximity probe that is used to measure the position.

How can I change the operating mode of the heat pump?

To change the operating mode, follow the steps outlined in the article, including entering a valid access code and pressing the ENTER key.

What are the control signal inputs in REMOTE mode?

The control signal inputs in REMOTE mode are: Remote Start, Remote Stop, Remote LCWT Setpoint, and Remove Current Limit Setpoint.