SYSTEM RUN – PRESSURE STATUS
Displayed when the chiller is running. It instructs the operator to press the STATUS key, whereupon one of the following messages will be displayed:
•WARNING: COND OR EVAP TRANSDUCER ERROR
Indicates a probable condenser or evaporator trans- ducer problem, because the output is unreasonable. The microprocessor arrives at this conclusion by subtracting the evaporator transducer output from the condenser transducer output. The result must be zero or some positive number. If the result is a nega- tive number, it concludes that there is a probable condenser or evaporator transducer problem. This function is inhibited for the first 10 minutes of chiller
NOTE: If the STATUS key is arbitrarily pressed, with- out the operator being prompted by the PRESS STATUS message, the following message shall be displayed.
NO MALFUNCTION DETECTED
WARNING – REFRIGERANT LEVEL OUT OF RANGE
Displayed when the refrigerant level sensor output goes to > 4.4VDC. While this is displayed, the variable ori- fice is driven open until the level is within range. This message is automatically cleared when output is within range.
SYSTEM RUN – LEAVING TEMP CONTROL
Displayed while the chiller is running. Indicates that the
SYSTEM READY TO START
Indicates that the system is not running, but will start upon application of a start signal.
SYSTEM SHUTDOWN – PRESS STATUS
Displayed when chiller is shut down on a cycling shut- down, safety shutdown (operator must move the COM- PRESSOR switch to STOP/RESET in order to restart) or
initial
SYSTEM SHUTDOWN – PRESS STATUS
Display can be held indefinitely by depressing DIS- PLAY key. For examples of System Shutdown Mes- sages, see below.
SYSTEM SHUTDOWN MESSAGES
Day of Week | Cause of Shutdown |
Time of Day | Type of Restart |
|
|
MON 10:00 AM – LOW | WATER TEMP – AUTOSTART |
|
|
Chiller was shut down on Monday at 10:00 AM be- cause the LCWT has decreased to a value that is 4°F below the
MON XX:XX AM – FLOW SWITCH – AUTOSTART
Chiller is shut down because a
MON XX:XX AM – SYSTEM CYCLING – AUTOSTART
A remote command (computer relay contact or manual switch) connected to the Remote/Local cycling input of the digital input board has shut down the chiller.
MON XX:XX AM – MULTI UNIT CYCLING – AUTOSTART
Lead/Lag sequence control accessory has shut down the chiller.
MON XX:XX AM – POWER FAILURE – AUTOSTART
The chiller is shut down because there has been a power interruption or failure. The chiller will automati- cally restart when power is restored. This message