chiller, press COMPRESSOR switch to STOP/RESET position and then to START position.
VANE MOTOR SWITCH OPEN
The chiller is shut down because a
MON XX:XX AM – STARTER MALFUNCTION DETECTED
The chiller is shut down because the Control Center has detected a
MON XX:XX AM – PROGRAM INITIATED RESET
The chiller is shut down because Micro Board did not receive a
SYSTEM READY TO START – PRESS STATUS
The chiller was shut down on a safety shutdown and will start upon application of a local or remote start signal. Since the message states that the chiller is “Ready to Start”, it means that the shutdown no longer exists and the Control Center has been manually re- set. When the STATUS key is pressed, a message is displayed that describes the reason for shutdown. The message will be displayed for 2 seconds and then re- turn to SYSTEM READY TO START – PRESS STATUS .
Those messages that could be displayed are any of the previously described
START SEQUENCE INITIATED
Indicates that the Micro Board has received a local or remote start signal and has initiated the chiller start- up routine.
This is the compressor
FORM
jumper on the Micro Board as follows:
FUNCTION | JUMPER POSITION |
50 Sec. Oil Pump Prerun | Installed |
180 Sec. Oil Pump Prerun | Cut |
SYSTEM COASTDOWN
Displayed while motor is decelerating after a chiller shutdown. The oil pump is running during this period. The duration of this period is 150 seconds.
If unit is configured for a Steam Turbine application (program jumper JP4 removed), this period is extended to allow for a longer coastdown time. EPROM version C.02F(T).11 provides a 6 minute coastdown period. EPROM version C.02F(T).12 or later provides a 10 minute coastdown period.
MON XX:XX AM – MTR PHASE CURRENT UNBALANCE
(Solid State Starter applications only)
The chiller is shut down because the
any phase deviates from the average (a + b + c ) current
3
by greater than 30% for a minimum of 45 consecutive seconds, a shutdown is initiated. To restart the sys- tem, press the COMPRESSOR switch to STOP/RE- SET position and then to the START position. An ex- ample of the conditions for shutdown is as follows:
IF:
I∅A = 200A
I∅B = 200A
I∅C = 118A
THEN:
IAV = 200 + 200 + 118 3
IAV = 173A
IACCEPTABLE = 173 ± 30% = 121A or 225A
THEREFORE:
Since I∅C = 118A which is less than the accept- able 121A, the chiller would shut down if this unbalance exists for 45 consecutive seconds.
MON XX:XX AM – LOW LINE VOLTAGE
(Solid State Starter applications only)
Chiller is shut down because the voltage in any phase of line voltage has decreased below the