York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 Checking Operation

Models: YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 YK M3 M3 G4

1 60
Download 60 pages 33.73 Kb
Page 33
Image 33
CHECKING OPERATION

be no lower than the value determined by referring to the formula below:

 

15 x % LOAD

)

Min. ECWT = LCHWT—C RANGE + 5 + (

100

where:

 

 

 

ECWT

= entering condensing water temperature

LCHWT

= leaving chilled water temperature

 

C RANGE = condensing water temperature range

 

At start-up, the entering condenser water temperature may be as much as 25°F colder than the standby re- turn chilled water temperature. Cooling tower fan cycling will normally provide adequate control of the entering condenser water temperature on most instal- lations.

CHECKING OPERATION

During operation, the following conditions should be periodically checked:

1.On starting, the prerotation vanes should remain closed until the compressor motor is up to speed on the run winding; then the vane motor should cause the vanes to modulate with load requirements.

FORM 160.49-O2

2.Be sure the oil pump is operating while unit is run- ning.

3.Check Oil Pressure display. A gradual decrease in bearing oil pressure of 5 to 10 psi (with constant suction and discharge pressures) may be an indi- cation of a dirty filter. The filter should be replaced when pressure loss is 30% or more of the original pressure. The actual bearing oil pressure will vary with compressor suction and discharge pressures. When a new system is first operated under normal full load conditions, the bearing oil pressure should be recorded as a reference point with which to com- pare subsequent readings.

OPERATING LOG SHEET

A permanent daily record of system operating condi- tions (temperatures and pressures) recorded at regu- lar intervals throughout each 24 hour operating period should be kept.

An optional status printer is available for this purpose or Fig. 16 shows a log sheet used by YORK Personnel for recording test data on chiller systems. It is avail- able from the factory in pads of 50 sheets each under Form 160.44-F6 and may be obtained through the nearest

23889A

LD00467

*NOTE: These items can be printed by an electronic printer connected to TB8 of the Micro Board and pressing the PRINT key on the Micro Board or automatically using the Data Logger feature.

FIG. 16 – LIQUID CHILLER LOG SHEETS

YORK INTERNATIONAL

33

Page 33
Image 33
York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 operation manual Checking Operation, Operating Log Sheet

FAQ

What should be periodically checked during operation?

The prerotation vanes, oil pump, and oil pressure display should be periodically checked.

What is the range for condensing water temperature?

The condensing water temperature range should be a minimum of 15 x % load, plus the leaving chilled water temperature range + 5, plus 100.

Where can I obtain a log sheet for recording test data on chiller systems?

A log sheet is available from YORK Personnel under Form 160.44-F6.