SYSTEM STARTING & SHUTDOWN SEQUENCE
OPERATOR INITIATED
(NOTE 2)
LD00952
NOTES: 1. REF. MICROBOARD PROGRAM JUMPER JP6
2. REF. MICROBOARD PROGRAM JUMPER JP4
FIG. 15 – CHILLER STARTING SEQUENCE & SHUTDOWN SEQUENCE
However, the current draw (amperes) by the compres- sor motor cannot exceed the setting of the % CUR- RENT LIMIT at any time during the unit operation, since the MicroComputer Control Center 40 to 100% three- phase peak current limit software function, plus the 3- phase 100% solid state overload current limiter (CM-
2)on
If the load continues to decrease, after the Prerotation Vanes are entirely closed, the chiller will be shut down by the Low Water Temperature control (LWT) function which is displayed on the Control Center as:
MON 10:30 AM – LOW WATER TEMPERATURE – AUTOSTART
This occurs when the leaving water temperature falls to 4°F below setpoint or 36°F, whichever is higher. The LWT is part of the Micro Board.
NOTE: If the temperature setpoint has been repro- grammed within the last 10 minutes, the LWT cutout is 36°F for 10 minutes.
Condenser Water Temperature Control
The YORK Millennium chiller is designed to use less power by taking advantage of lower than design tem- peratures that are naturally produced by cooling tow- ers throughout the operating year. Exact control of con- denser water such as a cooling tower bypass, is not necessary for most installations. The chiller requires only that the minimum condenser water temperature
32 | YORK INTERNATIONAL |