Sensor Trim

48/50PG and PM

SCT.A

SCT.A

MOTORMASTER

SENSOR

(3rd return bend down from top)

MOTORMASTER

SENSOR

(bottom stub

of outside header)

48/50PG03,04

48/50PG03-07

C09347

Fig. 23 − Saturated Condensing Temperature Thermistor Location — 48/50PG03−07

 

THERMISTOR

THERMISTOR

 

LOCATION

 

LOCATION

 

(SCT.B)

 

(SCT.A)

THERMISTOR

 

 

 

LOCATION

THERMISTOR

 

(SCT.B)

 

 

LOCATION

MOTORMASTER

 

(SCT.A)

 

SENSOR

 

 

 

 

(4th stub from bottom

 

MOTORMASTER

of outside header)

 

SENSOR

 

 

(2nd stub from bottom

 

 

of outside header)

 

48/50PG08-12

 

48/50PG14

C09348

Fig. 24 − Saturated Condensing Temperature Thermistor Location — 48/50PG08−14

Sensor Trim

Corrective offsets can be applied to the space temperature and the supply air temperature sensor readings. These corrections are set in the ConfigurationTRIM menu for the display, or in the MaintenanceTRIM table for CCN. See the Indoor Air Quality section for available adjustments to IAQ and OAQ sensor readings. The space temperature may be corrected by entering either a calibration temperature value in SPT.C, or an offset temperature value in SPT.T. The supply-air temperature may be corrected by entering either a calibration temperature value in SAT.C, or an offset temperature value in SAT.T. Temperature corrections should only be made if sensor readings are compared to an accurate reference temperature measurement device.

Transducer Troubleshooting

The electronic control uses suction pressure transducers to measure the suction pressure of the refrigerant circuits. The pressure/voltage characteristics of these transducers are in shown in Table 22, the 5vdc power is applied to legs A and B of the transducer and legs B to C represent the signal voltage. To use the voltage drop table for troubleshooting, read the voltage across A and B, then subtract the voltage reading from B to C. This is the voltage drop which can be

looked up in table 22. The accuracy of these transducers can be verified by connecting an accurate pressure gauge to the second refrigerant port in the suction line.

Forcing Inputs and Outputs

Many variables may have their value forced through CCN or directly at the local display. This can be useful during diagnostic testing and also during operation, typically as part of an advanced third party control scheme. Input and output points that may be forced are indicated as ‘forcible’ in the write status column of the display and CCN tables.

If the user needs to force a variable, follow the same process as when editing a configuration parameter. A forced variable will be displayed on the Scrolling Marquee with a blinking period “.” following its value. A forced value on Navigatoraccessory is indicated with a blinking “f”. A forced value on CCN devices is indicated with “Control” if forced at the unit display, or “Supervisor” if forced via CCN. To remove a local force with the Scrolling Marquee, select the point with the ENTER key and then press the up-arrow and down-arrow keys simultaneously.

NOTE: In the case of a control power reset, any force in effect at the time of power reset will be cleared.

52

Page 52
Image 52
Carrier 48/50PG C03-14, 48/50PM C16-28 manual Transducer Troubleshooting, Forcing Inputs and Outputs, Sensor Trim