48/50PG and PM
Fan Performance — 48PGD14 Vertical Units
AIRFLOW |
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
| ||||||
0.2 |
|
| 0.4 |
| 0.6 | 0.8 |
| 1.0 |
|
| ||||
(Cfm) |
|
|
|
|
|
| ||||||||
Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | |||||
|
|
| ||||||||||||
3750 |
|
| 1.28 |
| 1.45 |
| 1.62 |
| 1.80 |
| 1.98 |
| ||
3950 |
|
| 1.47 |
| 1.65 |
| 1.83 |
| 2.01 |
| 2.20 |
| ||
4150 |
|
| 1.68 |
| 1.86 |
| 2.05 |
| 2.25 |
| 2.44 |
| ||
4350 |
|
| 1.90 |
| 2.10 |
| 2.30 |
| 2.50 |
| 2.70 |
| ||
4550 |
|
| 2.15 |
| 2.35 |
| 2.56 |
| 2.77 |
| 2.98 |
| ||
4750 |
|
| 2.42 |
| 2.63 |
| 2.85 |
| 3.06 |
| 3.28 |
| ||
4950 |
|
| 2.71 |
| 2.93 |
| 3.15 |
| 3.38 |
| 3.61 |
| ||
5150 |
|
| 3.02 |
| 3.25 |
| 3.48 |
| 3.72 | 1022 | 3.95 |
| ||
5350 |
|
| 3.36 |
| 3.60 |
| 3.84 | 1009 | 4.08 | 1046 | 4.32 |
| ||
5550 |
|
| 3.72 |
| 3.97 |
| 4.22 | 1035 | 4.47 | 1070 | 4.72 |
| ||
5750 |
|
| 4.10 |
| 4.36 | 1024 | 4.62 | 1060 | 4.88 | 1095 | 5.14 |
| ||
5950 |
|
| 4.52 | 1015 | 4.78 | 1051 | 5.05 | — | — | — | — | |||
6150 |
| 1006 | 4.96 | 1043 | 5.23 | — | — | — | — | — | — | |||
6250 |
| 1021 | 5.19 | — | — | — | — | — | — | — | — | |||
AIRFLOW |
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
| ||||||
1.2 |
|
| 1.4 |
| 1.6 | 1.8 |
| 2.0 |
|
| ||||
(Cfm) |
|
|
|
|
|
| ||||||||
Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | Rpm | Bhp | |||||
|
|
| ||||||||||||
3750 |
|
| 2.17 |
| 2.36 |
| 2.55 | 1037 | 2.75 | 1076 | 2.95 |
| ||
3950 |
|
| 2.39 |
| 2.59 | 1012 | 2.79 | 1052 | 3.00 | 1091 | 3.21 |
| ||
4150 |
|
| 2.64 |
| 2.85 | 1030 | 3.05 | 1069 | 3.27 | 1106 | 3.48 |
| ||
4350 |
|
| 2.91 | 1010 | 3.12 | 1048 | 3.34 | 1086 | 3.55 | 1123 | 3.78 |
| ||
4550 |
|
| 3.20 | 1030 | 3.41 | 1068 | 3.64 | 1104 | 3.86 | 1140 | 4.09 |
| ||
4750 |
| 1013 | 3.50 | 1051 | 3.73 | 1087 | 3.96 | 1123 | 4.19 | 1158 | 4.43 |
| ||
4950 |
| 1036 | 3.84 | 1072 | 4.07 | 1108 | 4.31 | 1142 | 4.55 | 1176 | 4.79 |
| ||
5150 |
| 1058 | 4.19 | 1094 | 4.43 | 1129 | 4.68 | 1162 | 4.93 | 1196 | 5.18 |
| ||
5350 |
| 1082 | 4.57 | 1116 | 4.82 | 1150 | 5.07 | — | — | — | — | |||
5550 |
| 1105 | 4.98 | 1139 | 5.23 | — | — | — | — | — | — | |||
5750 |
| — | — | — | — | — | — | — | — | — | — | |||
5950 |
| — | — | — | — | — | — | — | — | — | — | |||
6150 |
| — | — | — | — | — | — | — | — | — | — | |||
6250 |
| — | — | — | — | — | — | — | — | — | — | |||
LEGEND |
|
|
|
| NOTES: |
|
|
|
|
| ||||
Bhp - Brake Horsepower |
|
|
|
| 1. | Motor drive range is 690 to 893 rpm for low range motor/drive and 852 to 1055 rpm | ||||||||
| High Range Motor/Drive Required |
|
|
| for high range motor/drive. All other rpms require a field‐supplied drive. |
|
|
2. Maximum continuous bhp is 3.70 for low range motor/drive and 5.25 for high range motor/drive.
3. See General Fan Performance Notes.
124