Carrier 48/50PG C03-14, 48/50PM C16-28 Fan Performance — 48PGD14 Horizontal Units, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 138
Image 138
Fan Performance — 48PGD14 Horizontal Units

48/50PG and PM

Fan Performance — 48PGD14 Horizontal Units

AIRFLOW

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

 

1.0

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

3750

591

1.06

651

1.23

706

1.40

 

1.57

 

1.75

3950

615

1.22

672

1.40

726

1.57

 

1.75

 

1.94

4150

639

1.39

695

1.58

746

1.76

 

1.95

 

2.14

4350

663

1.58

717

1.77

767

1.97

 

2.17

 

2.36

4550

688

1.78

740

1.99

788

2.19

 

2.40

 

2.60

4750

712

2.00

763

2.22

810

2.43

 

2.65

 

2.86

4950

737

2.24

786

2.47

832

2.69

 

2.91

 

3.14

5150

762

2.50

809

2.73

853

2.97

 

3.20

 

3.43

5350

787

2.77

832

3.02

876

3.26

 

3.50

 

3.75

5550

811

3.07

856

3.33

898

3.58

 

3.83

 

4.08

5750

836

3.39

879

3.65

920

3.92

 

4.18

 

4.44

5950

861

3.72

903

4.00

943

4.28

 

4.55

1019

4.81

6150

886

4.09

927

4.37

966

4.66

1004

4.94

1040

5.21

6250

899

4.28

939

4.57

977

4.85

1015

5.14

AIRFLOW

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

1.2

 

1.4

 

1.6

 

1.8

 

 

2.0

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

3750

 

1.93

 

2.11

 

2.30

 

2.49

1025

2.69

3950

 

2.12

 

2.31

 

2.51

 

2.71

1036

2.91

4150

 

2.34

 

2.53

 

2.74

1009

2.94

1048

3.15

4350

 

2.57

 

2.77

 

2.98

1023

3.19

1061

3.41

4550

 

2.81

 

3.03

1000

3.24

1038

3.46

1075

3.68

4750

 

3.08

 

3.30

1016

3.52

1053

3.75

1090

3.98

4950

 

3.36

 

3.59

1033

3.82

1069

4.05

1105

4.29

5150

 

3.67

1014

3.90

1050

4.14

1086

4.38

1121

4.62

5350

 

3.99

1032

4.23

1068

4.48

1103

4.72

1137

4.97

5550

1015

4.33

1051

4.58

1086

4.84

1120

5.09

5750

1035

4.70

1070

4.96

1105

5.22

5950

1055

5.08

6150

6250

LEGEND

NOTES:

Bhp - Brake Horsepower

1.

Motor drive range is 690 to 893 rpm for low range motor/drive, 852 to 1055 rpm for

 

High Range Motor/Drive Required

high range motor/drive. All other rpms require a field‐supplied drive.

 

 

2.

Maximum continuous bhp is 3.70 for low range motor/drive and 5.25 for high range

 

 

motor/drive.

 

 

3.

See General Fan Performance Notes.