2.18

48/50PG and PM

Fan Performance — 48PMD16 Horizontal Supply / Return Units

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

CFM

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

787

2.11

F

847

2.38

F

904

2.65

F

957

2.92

F

1008

2.88

F

4800

832

2.42

F

889

2.70

F

943

2.98

F

994

3.26

F

1042

3.25

F

5100

877

2.76

F

931

3.05

F

982

3.33

F

1031

3.30

F

1078

3.66

F

5400

922

3.13

F

974

3.43

F

1023

3.38

F

1070

3.74

F

1115

4.12

F

5700

967

3.53

F

1017

3.47

F

1064

3.84

F

1109

4.22

F

1153

4.61

G

6000

1013

3.58

F

1060

3.96

F

1105

4.35

G

1149

4.75

G

1191

5.16

G

6300

1059

4.10

F

1104

4.50

G

1147

4.91

G

1189

5.32

G

1230

5.75

G

6600

1105

4.67

G

1148

5.09

G

1190

5.52

G

1230

5.95

H

1269

6.39

H

6900

1151

5.30

G

1192

5.73

G

1232

6.17

H

1272

6.62

H

1310

7.08

H

7200

1197

5.98

H

1237

6.43

H

1275

6.89

H

1313

7.36

H

1350

7.83

H

7500

1243

6.71

H

1281

7.18

H

1319

7.66

H

1355

8.14

H

1391

8.63

H

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

CFM

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

1056

3.21

F

1103

3.56

F

1147

3.91

F

1191

4.28

G

1233

4.65

G

4800

1089

3.60

F

1134

3.96

F

1178

4.33

G

1220

4.71

G

1261

5.10

G

5100

1124

4.03

F

1167

4.41

G

1209

4.79

G

1250

5.18

G

1290

5.58

G

5400

1159

4.50

G

1201

4.89

G

1242

5.29

G

1282

5.70

G

1320

6.12

H

5700

1195

5.01

G

1236

5.42

G

1275

5.84

H

1314

6.26

H

1352

6.69

H

6000

1232

5.57

G

1271

6.00

H

1310

6.43

H

1348

6.87

H

1384

7.31

H

6300

1269

6.18

H

1308

6.62

H

1345

7.07

H

1382

7.52

H

----

---

---

6600

1308

6.84

H

1345

7.29

H

1381

7.76

H

----

---

---

----

---

---

6900

1347

7.55

H

1383

8.02

H

----

---

---

----

---

---

----

---

---

7200

1386

8.31

H

----

---

---

----

---

---

----

---

---

----

---

---

7500

----

---

---

----

---

---

----

---

---

----

---

---

----

---

---

Fan Performance — 48PME16 Horizontal Supply / Return Units

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

 

0.4

 

 

0.6

 

 

 

0.8

 

 

1.0

 

CFM

RPM

BHP

Drive

 

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

 

 

 

 

 

 

F

918

2.75

F

972

3.04

F

1024

3.01

F

800

2.18

F

861

2.47

4800

845

2.51

F

 

903

2.80

F

958

3.10

F

1009

3.05

F

1059

3.41

F

5100

891

2.86

F

946

3.17

F

998

3.47

F

1048

3.47

F

1095

3.84

F

5400

937

3.24

F

989

3.56

F

1039

3.54

F

1087

3.93

F

1133

4.32

G

5700

983

3.66

F

1033

3.63

F

1081

4.03

F

1127

4.43

G

1171

4.84

G

6000

1029

3.74

F

1077

4.15

F

1123

4.56

G

1167

4.98

G

1210

5.41

G

6300

1075

4.28

G

1121

4.71

G

1165

5.14

G

1208

5.58

G

1249

6.03

H

6600

1122

4.88

G

1166

5.32

G

1208

5.78

H

1250

6.24

H

1290

6.70

H

6900

1169

5.52

G

1211

5.99

H

1252

6.46

H

1292

6.94

H

1330

7.43

H

7200

1215

6.23

H

1256

6.72

H

1296

7.21

H

1334

7.71

H

1371

8.21

H

7500

1262

7.00

H

1302

7.50

H

1340

8.01

H

1377

8.53

H

----

----

---

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

1.2

 

 

 

1.4

 

 

1.6

 

 

 

1.8

 

 

2.0

 

CFM

RPM

BHP

Drive

 

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

1073

3.36

F

1120

3.71

F

1165

4.07

F

1209

4.43

G

1252

4.80

G

4800

1106

3.77

F

1152

4.14

F

1196

4.52

G

1239

4.90

G

1280

5.29

G

5100

1141

4.22

F

1186

4.61

G

1228

5.01

G

1270

5.41

G

1310

5.81

H

5400

1177

4.72

G

1220

5.13

G

1261

5.54

G

1302

5.95

H

1341

6.38

H

5700

1214

5.26

G

1255

5.68

G

1296

6.11

H

1335

6.55

H

1373

6.99

H

6000

1251

5.85

H

1292

6.29

H

1331

6.74

H

 

1369

7.19

H

----

----

---

6300

1290

6.49

H

1329

6.95

H

1367

7.41

H

 

----

----

---

----

----

---

6600

1328

7.18

H

 

1366

7.65

H

----

----

---

 

----

----

---

----

----

---

6900

1368

7.92

H

 

----

----

---

----

----

---

 

----

----

---

----

----

---

7200

----

----

---

----

----

---

----

----

---

 

----

----

---

----

----

---

7500

----

----

---

----

----

---

----

----

---

 

----

----

---

----

----

---

LEGEND

 

 

NOTES:

BHP

- Brake Horsepower (motor input to fan)

Grey Cells - Indicates field-supplied pulley change required.

RPM

-

Revolutions Per Minute (fan speed)

Do not exceed listed motor maximum BHP value.

Drive

-

Motor & Pulley Drive Option Based on 460V motor maximum

Motor Drive Ranges

BHP. See notes on this page.

(E) Low Range: Not Used

 

 

(F) Mid-Low Range: 208/230 and 460V - RPM Range - 896 to 1227,

 

Maximum BHP - 4.26

 

(G) Mid-High Range: All voltages, RPM Range - 1113 to 1414,

 

Maximum BHP - 5.75

 

(H) High Range: All voltages, RPM Range - 1096 to 1339,

 

Maximum BHP - 8.63

 

See General Notes for Fan Performance Data Tables.

158

Page 158
Image 158
Carrier 48/50PG C03-14, 48/50PM C16-28 manual 2.18