Carrier 48/50PM C16-28 manual Fan RPM at Motor Pulley Settings* − 50PM16−28, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 177
Image 177
Fan RPM at Motor Pulley Settings* − 50PM16−28

Fan RPM at Motor Pulley Settings* − 50PM16−28

50PM

DRIVE

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

0

1/

1

11/

2

21/

3

31/

4

41/

5

51/

6

 

 

 

 

 

2

 

2

 

2

 

2

 

2

 

2

 

 

Low Range Vertical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mid‐Low Range Vertical

 

 

 

1013

1035

1056

1078

1099

1120

1142

1163

1185

1206

PM16, 20

Mid‐High Range Vertical

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

and 24

High Range Vertical

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

(230 and

Low Range Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

460 volt)

Mid‐Low Range Horizontal

 

 

 

1013

1035

1056

1078

1099

1120

1142

1163

1185

1206

 

Mid‐High Range Horizontal

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

 

High Range Horizontal

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

 

Low Range Vertical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mid‐Low Range Vertical

 

 

 

1013

1035

1056

1078

1099

1120

1142

1163

1185

1206

PM16, 20

Mid‐High Range Vertical

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

High Range Vertical

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

and 24

Low Range Horizontal

 

 

 

 

 

 

 

869

 

 

 

 

 

(575 Volt)

 

 

 

 

 

 

 

 

 

 

 

 

Mid‐Low Range Horizontal

 

 

 

1013

1035

1056

1078

1099

1120

1142

1163

1185

1206

 

 

 

 

 

Mid‐High Range Horizontal

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

 

High Range Horizontal

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

 

Low Range Vertical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mid‐Low Range Vertical

 

 

 

 

 

 

 

 

 

 

 

 

1007

 

Mid‐High Range Vertical

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

28

High Range Vertical

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

(all voltages)

Low Range Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mid‐Low Range Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

1007

 

Mid‐High Range Horizontal

 

 

 

1000

1019

1039

1059

1078

1098

1117

1137

1156

1176

 

High Range Horizontal

1014

1038

1061

1085

1108

1132

1156

1179

1203

1226

1250

1273

1297

*Approximate fan rpm shown, based on 1725 rpm motor. NOTE: Factory pulley speed setting is at 3 turns open.

48/50PG and PM

177

Page 177
Image 177
Carrier 48/50PM C16-28, 48/50PG C03-14 manual Fan RPM at Motor Pulley Settings* − 50PM16−28, 48/50PG and PM