Economizer Control Board (ECB)

Economizer Control Board (ECB)

The ECB controls the economizer actuator. (See Fig. 41 and Table 24.) The control signal from the ECB uses either the MFT (Multi-Function Technology) digital communication protocol or a 4 to 20 mA output signal as defined by the configuration ConfigurationECONE.CTL. The ECB has inputs for Indoor Air Quality (IAQ), Outdoor Air Quality (OAQ), enthalpy and RH sensor. It also controls two power exhaust outputs.

By digitally communicating with the ECB, the economizer actuator is able to provide the damper position and diagnostic information to the ComfortLinkt controller. The damper position is displayed at OutputsECONEC.AP. Diagnostic information is displayed via Alert T414. More information about these alarms is contained in the Alarms and Alerts section.

NOTE: The Economizer Control Board (ECB) has a 4-position DIP switch that is factory set to ‘0’ (ON, towards the center of the board). Do not change this setting.

48/50PG and PM

C07027

Fig. 41 − Economizer Control Board (ECB)