Carrier 48/50PM C16-28 Third Party Control, Heating Test, Cooling/Heating Control, Fire Shutdown

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 13
Image 13
Heating Test

Heating Test

The heating (HEAT) submenu is used to change output status for the individual heat stages, gas or electric. The fans (FANS) and cooling (COOL) service test outputs are reset to OFF for the heating service test. Indoor and outdoor fans are controlled normally to maintain proper unit operation. If adaptive fan is configured, then the indoor fan speed will default to the heating configuration point (ConfigurationA.FANFS.HT) when a stage of heat is turned on. The Reduced Heat Fan Speed (F.SPD) can only be changed while one stage is running. If more then one stage is on the actual fan speed will be 100%. F.SPD shows the reduced speed not actual speed. On single stage units actual fan speed will be 100% when that stage is turned on. All normal heating alarms and alerts are functional.

NOTE: Field terminal strip terminal R must be connected to W1 for the heat to operate in service test. Alert number T410 will occur as a reminder if not done. If the normal unit control mode is thermostat mode, then remove the R−W1 jumper after completing service test.

THIRD PARTY CONTROL

Third party controls may interface with the unit ComfortLinkt controls through the connections described below. See other sections of these instructions for more information on the related unit control and configurations.

Cooling/Heating Control

The thermostat inputs are provided on the field connection terminal

board. The Unit Control Type configuration, ConfigurationUNITU.CTL, must be 2 to recognize the below inputs. Terminal R is the 24vac source for the following:

SY1 = First stage cooling

SY2 = Second stage cooling

SW1 = First stage heating

SW2 = Second stage heating

SG = Indoor fan

Dehumidification Control

On Humidi−MiZert units terminals Humidistat 1 and 2 are provided on the field connection terminal board. Humidity Switch configuration, ConfigurationUNITRH.SW, identifies the normally open or normally closed status of this input at LOW humidity. The Humidistat 1 terminal is the input signal and R can be used as the source.

NOTE: Dehumidification is considered a cooling function in the software and is only available on Humidi-MiZer equipped units.

Remote Occupancy

The remote occupancy input is provided on the field connection terminal board (TB1). The Remote Occupancy Switch configuration, ConfigurationUNITRM.SW, identifies the normally open or normally closed status of this input when unoccupied.

S5 = 24 VAC signal input

S6 = 24 VAC source for dry contact

Fire Shutdown

The fire shutdown input is provided for unit shutdown in response

 

to a fire alarm or smoke detector. The Fire Shutdown Switch

 

configuration, ConfigurationUNITFS.SW, identifies the

 

normally open or normally closed status of this input when there is

 

no fire alarm.

 

For 48/50 units without Humidi-MiZer system, input at field

 

connection terminal board (TB1)

 

S Fire Shutdown 1 = 24 VAC source for dry contact

 

S Fire Shutdown 2 = 24 VAC signal input

 

For 50 series units with Humidi-MiZer system, input at wire

 

harness plug 19 (PL 19). (See Fig. 7.)

 

S PL 19-3 = 24 VAC source for dry contact

 

S PL 19-5 = 24 VAC signal input

 

For 48 series units with Humidi-MiZer system, input at wire

 

harness plug 19 (PL 19). (See Fig. 8.)

PM

S PL 19-3 = 24 VAC source for dry contact

S PL 19-5 = 24 VAC signal for Fire Shutdown

and

 

S PL 19-4 = 24 VAC power for indoor fan contactor control

48/50PG

circuit

 

NOTE: If the indoor fan must be shut down without any delay

 

upon Fire Shutdown input, then the factory jumper between

 

PL19-3 and PL19-4 must be replaced with a normally closed

 

contact when there is no alarm (open with alarm).

 

The plug PL19 is located in the return air section on

 

48/50PG03−14 size units and under the control box on and

 

48/50PM16−28 units.

 

Alarm Output

 

The alarm output is provided on the field connection terminal board (TB1) to indicate a current alarm status. The output will be 24VAC if a current alarm exists.

SC = 24 VAC common

SX = 24 VAC signal output

C08580

Fig. 7 − 50PG/PM Humidi−MiZert − Third Party Smoke

Detector Wiring

13

Page 13
Image 13
Carrier 48/50PM C16-28 Third Party Control, Heating Test, Cooling/Heating Control, Dehumidification Control, Fire Shutdown