Table 10 – Control Modes with Humidi−MiZert System
Output and Valve States versus Circuit Mode .x = Circuit A, B, or C identifier
DEMAND AND MODEOUTPUTS48/50PG03-16 VALVES
VALVES
| Circuit |
|
| Circuit | Cooling- | Reheat2 | CV.x | RH1.x | RH2.x | RH1.x | RH2.x | |
Space | Circuit | Indoor | Reheat | |||||||||
Cooling | Compressor | Valve | Valve | Valve | Valve | Valve | Valve | |||||
Humidity | Mode | Fan (IDF) | Control | |||||||||
Demand | (CMP.x) | (RH2.x) | ||||||||||
|
|
| (CRC)* | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
— | — | No | OFF | Off | Off | Off | Off | Off | Off | Off | Off | |
power | (open) | (open) | (closed) | (closed) | ||||||||
|
|
|
|
|
|
| ||||||
|
|
| Per |
|
|
| Off | On | Off |
| Off | |
Low | No | Off | Ventilation | Off | Off | Off | Off | |||||
(open) | (closed) | (closed) | (closed) | |||||||||
|
|
| Control |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| ||
Low | Yes | Cool | On | On | Off | Off | Off | On | Off | Off | Off | |
(open) | (closed) | (closed) | (closed) | |||||||||
|
|
|
|
|
|
|
| |||||
High | Yes | Reheat1 | On | On | On | Off | On | Off | Off | On | Off | |
(closed) | (open) | (closed) | (closed) | |||||||||
|
|
|
|
|
|
|
| |||||
High | No | Reheat2 | On | On | On | On | On | Off | On | On | On | |
(closed) | (open) | (open) | (open) | |||||||||
|
|
|
|
|
|
|
|
RH2.x |
|
| RH1.x |
COND COIL | |
COMP |
|
| CV.x |
OUTDOOR AIR |
|
48/50PG and PM
| EVAP COIL |
|
|
| |
CLOSED VALVE |
| |
|
| |
|
| |
OPEN VALVE |
|
|
INDOOR ENTERING |
| |
|
| |
| AIR |
|
METERING DEVICE
C07003
Fig. 9 − Normal Cooling Mode — Humidi−MiZert System
48/50PG03−16