Carrier 48/50PG C03-14 Appendix A — Local Display And Ccn Tables Cont, MODE - CONFIGURATION cont

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 102
Image 102
COOL (cont)

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

48/50PG and PM

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

 

DEFAULT

COOL (cont)

Cooling Configuration

 

 

 

 

B2.FN

Level 2 Fans B

0 to 7

 

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

0

(03­07)

 

 

 

 

3

(PG08­16)

 

 

 

 

6

(20, PM16)

 

 

 

 

2

(24­28)

 

 

 

 

Humidi­Mizer FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

1

(PG16)

 

 

 

 

3

(20, PM16)

 

 

 

 

2

(24­28)

B3.FN

Level 3 Fans B

0 to 7

 

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

0

(03­07)

 

 

 

 

3

(PG08­16)

 

 

 

 

6

(20­28, PM16)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

1

(PG16)

 

 

 

 

3

(20­28, PM16)

CIR.C

Circuit C

 

 

 

 

CC.LO

Circuit C Lockout Temp

0 to 100F

°F

0

 

CS.C1

Current Sensing C1

Disable/En­

 

Disable (03­14,

 

 

able

 

20­28)

 

 

 

 

Enable (PG16)

C1.FN

Level 1 Fans C

0­7

 

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

1

(PG16)

 

 

 

 

0

(20­28, PM16)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

0

(PG03­16)

 

 

 

 

1

(20­28, PM16)

C2.FN

Level 2 Fans C

0 to 7

 

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

3

(PG16)

 

 

 

 

0

(20­28, PM16)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

1

(PG16)

 

 

 

 

2

(20­28, PM16)

C3.FN

Level 3 Fans C

0 to 7

 

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

3

(PG16)

 

 

 

 

0

(20­28, PM16)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

0

(03­14)

 

 

 

 

1

(PG16)

 

 

 

 

3

(20­28, PM16)

SST

Low Suction Control

 

 

 

 

SST.O

Suction OK Temperature

10 to 50

°F

18

SST.1

Low Suction ­ Level 1

10 to 50

°F

20

SST.2

Low Suction ­ Level 2

5 to 50

°F

15

SST.3

Low Suction ­ Level 3

0 to 50

°F

10

CK.DL

Delay On Low SST Check

0 to 300

sec

0

 

OFC

Outdoor Fan Control

 

 

 

 

OFC.3

OFC3 Enable. CCH Dis­

No/Yes

 

No (PG03­16)

 

able

 

 

Yes (20­28, PM16)

0.MXP

Fan Lev0 Max Pressure

100 to 500

psig

200

1.MXP

Fan Lev1 Max Pressure

100 to 500

psig

400 (PG03­16)

 

 

 

 

450 (20­28, PM16)

2.MNP

Fan Lev2 Min Pressure

100 to 500

psig

150 (PG03­16)

 

 

 

 

200 (20­28, PM16)

2.ON

Fan Lev2 On Temperature

0 to 100

°F

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

55 (03­20)

 

 

 

 

45 (24­28)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

68 (20, PM16)

 

 

 

 

61 (24­28)(PG03­16)

2.OFF

Fan Lev2 Off Temperature

0 to 100

°F

no Humidi­MiZer

 

 

 

 

FIOP:

 

 

 

 

45 (PG03­16)

 

 

 

 

50 (20, PM16)

 

 

 

 

40 (24­28)

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

57 (20­28,

 

 

 

 

PM16)(PG03­16)

2.MXP

Fan Lev2 Max Pressure

100 to 500

psig

400

3.MNP

Fan Lev3 Min Pressure

100 to 500

psig

250

CCN TABLE/ SUB-TABLE

COOL_CFG

CCN POINT

PAGE NO.

15

CIR_B_2

CIR_B_3

19

OATLCMPC

C1_SENSE

CIR_C_1

CIR_C_2

CIR_C_3

39

SSTOK

SSTLEV1

SSTLEV2

SSTLEV3

SSTCKDLY

19

OFC3_CTL

LEV0MAXP

LEV1MAXP

LEV2MINP

LEV2ON

LEV2OFF

LEV2MAXP

LEV3MINP

102

Page 102
Image 102
Carrier 48/50PG C03-14 Appendix A — Local Display And Ccn Tables Cont, MODE - CONFIGURATION cont, 48/50PG and PM, Item