Carrier 48/50PM C16-28, 48/50PG C03-14 manual Available External Static Pressure in. wg

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 151
Image 151
Available External Static Pressure (in. wg)

Fan Performance — 48PMD16 Vertical Supply / Return Units

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

0.4

 

 

 

 

0.6

 

 

 

 

0.8

 

 

1.0

 

CFM

 

 

RPM

BHP

Drive

RPM

BHP

Drive

 

RPM

BHP

 

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

 

 

513

0.79

 

A

 

585

0.99

A

 

656

1.23

 

A

730

1.53

A

807

1.91

A

4800

 

 

535

0.92

 

A

 

604

1.14

A

 

670

1.37

 

A

738

1.66

A

809

2.02

A

5100

 

 

558

1.07

 

A

 

624

1.30

A

 

687

1.54

 

A

749

1.82

A

814

2.15

A

5400

 

 

582

1.23

 

A

 

645

1.47

A

 

704

1.72

 

A

763

2.00

A

823

2.32

A

5700

 

 

605

1.42

 

A

 

666

1.67

A

 

723

1.93

 

A

779

2.21

A

835

2.52

A

6000

 

 

629

1.62

 

A

 

688

1.88

A

743

2.15

 

A

796

2.44

A

848

2.75

A

6300

 

 

653

1.83

 

A

 

710

2.12

A

763

2.40

 

A

814

2.69

A

864

3.00

A

6600

 

 

677

2.07

 

A

 

732

2.37

A

784

2.66

 

A

833

2.96

A

880

3.28

A

6900

 

 

701

2.33

 

A

755

2.64

A

805

2.95

 

A

852

3.26

A

898

3.58

A

7200

 

 

726

2.61

 

A

777

2.94

A

826

3.26

 

A

872

3.58

A

917

3.91

A

7500

 

 

750

2.92

 

A

800

3.25

A

848

3.59

 

A

893

3.92

A

936

4.26

B

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

1.2

 

 

 

 

 

1.4

 

 

 

 

1.6

 

 

 

 

1.8

 

 

2.0

 

CFM

RPM

BHP

Drive

 

RPM

 

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

880

2.33

A

 

942

 

2.75

A

993

3.12

 

A

1035

3.46

A

1072

3.77

A

4800

881

2.44

A

 

948

 

2.90

A

1005

3.34

 

A

1054

3.74

A

1095

4.11

A

5100

882

2.56

A

 

950

 

3.03

A

 

1012

3.51

 

A

1065

3.98

A

1112

4.41

B

5400

886

2.71

A

 

950

 

3.16

A

 

1013

3.66

 

A

1071

4.17

A

1123

4.67

B

5700

893

2.89

A

 

953

 

3.32

A

 

1014

3.81

 

A

 

1073

4.34

B

1128

4.88

B

6000

902

3.10

A

 

958

 

3.51

A

 

1016

3.98

 

A

 

1074

4.50

B

1130

5.06

B

6300

914

3.35

A

 

966

 

3.74

A

 

1020

4.18

 

A

 

1075

4.69

B

1130

5.24

B

6600

928

3.62

A

 

977

 

4.00

A

 

1027

4.43

 

B

1079

4.91

B

1132

5.44

B

6900

944

3.92

A

 

990

 

4.30

B

1037

4.71

 

B

1085

5.17

B

1135

5.68

B

7200

960

4.25

A

 

1004

 

4.63

B

1049

5.03

 

B

1094

5.47

B

1141

5.96

C

7500

978

4.61

B

1020

 

4.98

B

1062

5.38

 

B

1105

5.82

C

1149

6.29

C

Fan Performance — 48PME16 and 48PMF16 Vertical Supply / Return Units

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.2

 

 

 

0.4

 

 

 

0.6

 

 

 

0.8

 

 

1.0

 

CFM

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

527

0.82

A

599

1.03

A

670

1.28

A

745

1.60

A

822

1.99

A

4800

551

0.97

A

619

1.18

A

685

1.43

A

753

1.73

A

825

2.10

A

5100

575

1.12

A

639

1.35

A

701

1.60

A

764

1.89

A

830

2.25

A

5400

599

1.30

A

661

1.54

A

720

1.79

A

779

2.08

A

839

2.42

A

5700

623

1.49

A

683

1.74

A

739

2.00

A

795

2.29

A

851

2.62

A

6000

648

1.70

A

706

1.97

A

760

2.24

A

812

2.53

A

865

2.85

A

6300

673

1.93

A

729

2.21

A

781

2.49

A

831

2.79

A

881

3.11

A

6600

698

2.18

A

752

2.48

A

802

2.77

A

851

3.08

A

898

3.40

A

6900

723

2.46

A

775

2.77

A

824

3.07

A

871

3.39

A

917

3.72

A

7200

749

2.75

A

799

3.08

A

846

3.40

A

892

3.72

A

936

4.06

A

7500

774

3.08

A

823

3.41

A

869

3.74

A

913

4.08

A

956

4.42

B

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

1.2

 

 

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

2.0

 

CFM

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

RPM

BHP

Drive

4500

893

2.42

A

 

953

2.82

A

1002

3.19

A

1043

3.52

A

1078

3.83

A

4800

896

2.54

A

 

961

3.00

A

1016

3.43

A

1063

3.82

A

1103

4.19

A

5100

899

2.67

A

 

965

3.14

A

 

1025

3.63

A

1077

4.09

A

1122

4.51

B

5400

903

2.82

A

 

967

3.29

A

 

1029

3.80

A

 

1086

4.31

B

1135

4.79

B

5700

910

3.01

A

 

971

3.45

A

 

1031

3.96

A

 

1090

4.50

B

1143

5.03

B

6000

920

3.22

A

 

976

3.65

A

 

1034

4.14

A

 

1092

4.68

B

1147

5.24

B

6300

932

3.47

A

 

985

3.88

A

 

1039

4.35

B

1094

4.87

B

1149

5.44

B

6600

946

3.76

A

 

996

4.15

A

 

1046

4.60

B

1099

5.10

B

1151

5.66

B

6900

962

4.07

A

 

1009

4.46

B

1056

4.89

B

1105

5.37

B

1155

5.90

C

7200

980

4.41

B

1024

4.80

B

1069

5.22

B

1114

5.68

B

1162

6.19

C

7500

998

4.78

B

1040

5.17

B

1082

5.58

B

1126

6.03

C

1170

6.53

C

LEGEND

 

 

NOTES:

BHP

- Brake Horsepower (motor input to fan)

Grey Cells indicate field-supplied pulley change required.

RPM

-

Revolutions Per Minute (fan speed)

Do not exceed listed motor maximum BHP value.

Drive

-

Motor & Pulley Drive Option Based on 460V motor maximum BHP. See

Motor Drive Ranges

notes on this page.

(A) Low Range: 208/230 and 460V, RPM Range - 685 to 939, Maximum BHP - 4.26

 

 

(B) Mid-Low Range: All voltages, RPM Range - 949 to 1206, Maximum BHP - 5.75

See General Notes for Fan Performance Data Tables.

(C) Mid-High Range: All voltages, RPM Range - 941 to 1176, Maximum BHP - 8.63

 

 

(D) High Range: Not used

48/50PG and PM

151

Page 151
Image 151
Carrier 48/50PM C16-28, 48/50PG C03-14 manual Available External Static Pressure in. wg