Table 12 — ComfortLinkt Alarm Codes (cont)

Table 12 — ComfortLinkt Alarm Codes (cont)

48/50PG and PM

ALARM

 

OR

 

DESCRIPTION

ALERT

 

NUMBER

 

A154

 

Serial EEPROM Hardware Failure

T155

 

Serial EEPROM Storage Failure Error

A156

 

Critical Serial EEPROM Storage Fail Error

A157

 

A/D Hardware Failure

A163

 

Circuit A Down Due to Failure

 

Service Test - Circuit A Down Due to Failure

 

 

A164

 

Circuit B Down Due to Failure

 

Service Test - Circuit B Down Due to Failure

 

 

A165

 

Circuit C Down Due to Failure

 

Service Test - Circuit C Down Due to Failure

 

 

T173

 

Loss of communication with the Energy

 

Management Module

 

 

T179

 

Loss of communication with the Economizer

 

Control Board

 

 

T180

 

Loss of communication with the Economizer

 

Actuator

 

 

T181

 

Loss of communication with Outside Air Unit

A200

 

Linkage Timeout Error - Comm Failure

A404

 

Fire Shutdown

T408

 

Dirty Air Filter

 

 

Fan Status Switch ON, fan commanded off

T409

 

 

 

 

Fan Status Switch OFF, fan commanded on

 

 

R-W1 Jumper Not Installed in Space Temp Mode

T410

 

R-W1 Jumper Must Be Installed to Run Heat In

 

 

Service Test

T411

 

Thermostat Y2 Input Activated without Y1 Activated

T412

 

Thermostat W2 Input Activated without W1

 

Activated

 

 

T413

 

Thermostat Y and W Inputs Activated

 

Simultaneously

 

 

 

 

Economizer Damper Actuator Out of Calibration

 

 

Economizer Damper Actuator Torque Above Load

 

 

Limit

T414

 

Economizer Damper Actuator Hunting Excessively

 

 

 

 

Economizer Damper Stuck or Jammed

 

 

Economizer Damper Actuator Mechanical Failure

 

 

Economizer Damper Actuator Direction Switch

 

 

Wrong

T415

 

IAQ Input Out of Range

T416

 

OAQ Input Out of Range

 

 

OAU Motor Failure

T418

 

OAU Dirty Filter

 

OAU Low CFM

 

 

 

 

OAU General Alarm

LEGEND

 

ECB

-

Economizer Control Board

IGC

-

Integrated Gas Controller

MBB

-

Main Base Board

OAT

-

Outdoor-Air Thermistor

ACTION TAKEN BY

RESET

PROBABLE CAUSE

CONTROL

METHOD

 

Unit Shutdown

Automatic

Software failure or MBB failure

Unit operation errors

Automatic

Software failure or MBB failure

Unit Shutdown

Automatic

Software failure or MBB failure

Unit Shutdown

Automatic

Software failure or MBB failure

Lockout Circuit A

Manual

Circuit has 3 strikes or has been locked out by another alarm

Lockout Circuit B

Manual

Circuit has 3 strikes or has been locked out by another alarm

Lockout Circuit C

Manual

Circuit has 3 strikes or has been locked out by another alarm

No action

Automatic

MBB Software failure, reload software or replace board

No economizer operation

Automatic

Communication wiring problem with ECB or faulty MBB or ECB

No economizer operation

Automatic

Communication wiring problem with actuator.

Reset OAU data

Automatic

Wiring Problem or OAU communication failure

No Linkage Operation fall

Automatic

Received a table write from Linkage before, now not receiving

back to local SPT

any linkage commands

 

Unit Shutdown

Automatic

Smoke detected by smoke detector

Alert Generated

Automatic

Dirty Filter

 

If IDF.F =

 

If IDF.F = Yes, then Unit

YES, then

 

Manual,

Bad Fan Status Switch. Configuration incorrect.

Shutdown

otherwise

 

 

 

 

automatic

 

 

If IDF.F =

 

If IDF.F = Yes, then Unit

YES, then

Tripped Circuit Breaker. Broken belt. Bad indoor fan motor.

Manual,

Shutdown

Configuration incorrect. Bad fan status switch.

otherwise

 

 

 

automatic

 

Unable to run heat

Automatic

Missing jumper wire

Unable to Test Heat Outputs

Automatic

Missing jumper wire

Run unit as if Y2 and Y1 are

Automatic

Bad Thermostat or Thermostat Wiring

On

 

 

Run unit as if W2 and W1 are

Automatic

Bad Thermostat or Thermostat Wiring

On

 

 

Run unit in mode activated

Automatic

Bad Thermostat or Thermostat Wiring

first

 

 

Alert Generated

Automatic

Calibrate economizer (E.CAL). If problem still exist then

determine what is limiting economizer rotation.

 

 

Alert Generated

Automatic

Actuator load too high. Check damper load.

Alert Generated

Automatic

Damper position changing too quickly.

Alert Generated

Automatic

No economizer motion. Check damper blades, gears, and

actuator.

 

 

Alert Generated

Automatic

Check actuator and replace if necessary.

Alert Generated

Automatic

Actuator direction control switch (CCW, CW) wrong.

No IAQ Operations

Automatic

Bad sensor, bad wiring, or sensor configured incorrectly.

No OAQ Operations

Automatic

Bad sensor, bad wiring, or sensor configured incorrectly.

Alert generated

Automatic

Check OAU motors for failure

Alert generated

Automatic

Check/change OAU filters

Alert generated

Automatic

Check OAU air flow

Alert generated

Automatic

Check OAU