Table 12 — ComfortLinkt Alarm Codes (cont)
48/50PG and PM
ALARM |
| ||
OR |
| DESCRIPTION | |
ALERT | |||
| |||
NUMBER |
| ||
A154 |
| Serial EEPROM Hardware Failure | |
T155 |
| Serial EEPROM Storage Failure Error | |
A156 |
| Critical Serial EEPROM Storage Fail Error | |
A157 |
| A/D Hardware Failure | |
A163 |
| Circuit A Down Due to Failure | |
| Service Test - Circuit A Down Due to Failure | ||
|
| ||
A164 |
| Circuit B Down Due to Failure | |
| Service Test - Circuit B Down Due to Failure | ||
|
| ||
A165 |
| Circuit C Down Due to Failure | |
| Service Test - Circuit C Down Due to Failure | ||
|
| ||
T173 |
| Loss of communication with the Energy | |
| Management Module | ||
|
| ||
T179 |
| Loss of communication with the Economizer | |
| Control Board | ||
|
| ||
T180 |
| Loss of communication with the Economizer | |
| Actuator | ||
|
| ||
T181 |
| Loss of communication with Outside Air Unit | |
A200 |
| Linkage Timeout Error - Comm Failure | |
A404 |
| Fire Shutdown | |
T408 |
| Dirty Air Filter | |
|
| Fan Status Switch ON, fan commanded off | |
T409 |
|
| |
|
| Fan Status Switch OFF, fan commanded on | |
|
| ||
T410 |
| ||
|
| Service Test | |
T411 |
| Thermostat Y2 Input Activated without Y1 Activated | |
T412 |
| Thermostat W2 Input Activated without W1 | |
| Activated | ||
|
| ||
T413 |
| Thermostat Y and W Inputs Activated | |
| Simultaneously | ||
|
| ||
|
| Economizer Damper Actuator Out of Calibration | |
|
| Economizer Damper Actuator Torque Above Load | |
|
| Limit | |
T414 |
| Economizer Damper Actuator Hunting Excessively | |
|
| ||
|
| Economizer Damper Stuck or Jammed | |
|
| Economizer Damper Actuator Mechanical Failure | |
|
| Economizer Damper Actuator Direction Switch | |
|
| Wrong | |
T415 |
| IAQ Input Out of Range | |
T416 |
| OAQ Input Out of Range | |
|
| OAU Motor Failure | |
T418 |
| OAU Dirty Filter | |
| OAU Low CFM | ||
|
| ||
|
| OAU General Alarm | |
LEGEND |
| ||
ECB | - | Economizer Control Board | |
IGC | - | Integrated Gas Controller | |
MBB | - | Main Base Board | |
OAT | - |
ACTION TAKEN BY | RESET | PROBABLE CAUSE | |
CONTROL | METHOD | ||
| |||
Unit Shutdown | Automatic | Software failure or MBB failure | |
Unit operation errors | Automatic | Software failure or MBB failure | |
Unit Shutdown | Automatic | Software failure or MBB failure | |
Unit Shutdown | Automatic | Software failure or MBB failure | |
Lockout Circuit A | Manual | Circuit has 3 strikes or has been locked out by another alarm | |
Lockout Circuit B | Manual | Circuit has 3 strikes or has been locked out by another alarm | |
Lockout Circuit C | Manual | Circuit has 3 strikes or has been locked out by another alarm | |
No action | Automatic | MBB Software failure, reload software or replace board | |
No economizer operation | Automatic | Communication wiring problem with ECB or faulty MBB or ECB | |
No economizer operation | Automatic | Communication wiring problem with actuator. | |
Reset OAU data | Automatic | Wiring Problem or OAU communication failure | |
No Linkage Operation fall | Automatic | Received a table write from Linkage before, now not receiving | |
back to local SPT | any linkage commands | ||
| |||
Unit Shutdown | Automatic | Smoke detected by smoke detector | |
Alert Generated | Automatic | Dirty Filter | |
| If IDF.F = |
| |
If IDF.F = Yes, then Unit | YES, then |
| |
Manual, | Bad Fan Status Switch. Configuration incorrect. | ||
Shutdown | |||
otherwise |
| ||
|
| ||
| automatic |
| |
| If IDF.F = |
| |
If IDF.F = Yes, then Unit | YES, then | Tripped Circuit Breaker. Broken belt. Bad indoor fan motor. | |
Manual, | |||
Shutdown | Configuration incorrect. Bad fan status switch. | ||
otherwise | |||
|
| ||
| automatic |
| |
Unable to run heat | Automatic | Missing jumper wire | |
Unable to Test Heat Outputs | Automatic | Missing jumper wire | |
Run unit as if Y2 and Y1 are | Automatic | Bad Thermostat or Thermostat Wiring | |
On | |||
|
| ||
Run unit as if W2 and W1 are | Automatic | Bad Thermostat or Thermostat Wiring | |
On | |||
|
| ||
Run unit in mode activated | Automatic | Bad Thermostat or Thermostat Wiring | |
first | |||
|
| ||
Alert Generated | Automatic | Calibrate economizer (E.CAL). If problem still exist then | |
determine what is limiting economizer rotation. | |||
|
| ||
Alert Generated | Automatic | Actuator load too high. Check damper load. | |
Alert Generated | Automatic | Damper position changing too quickly. | |
Alert Generated | Automatic | No economizer motion. Check damper blades, gears, and | |
actuator. | |||
|
| ||
Alert Generated | Automatic | Check actuator and replace if necessary. | |
Alert Generated | Automatic | Actuator direction control switch (CCW, CW) wrong. | |
No IAQ Operations | Automatic | Bad sensor, bad wiring, or sensor configured incorrectly. | |
No OAQ Operations | Automatic | Bad sensor, bad wiring, or sensor configured incorrectly. | |
Alert generated | Automatic | Check OAU motors for failure | |
Alert generated | Automatic | Check/change OAU filters | |
Alert generated | Automatic | Check OAU air flow | |
Alert generated | Automatic | Check OAU |