UNIT START-UP CHECKLIST

UNIT START-UP CHECKLIST

48/50PG and PM

MODEL NO.:

 

 

SERIAL NO: _____________________________________

DATE:

 

 

______________

TECHNICIAN: ___________________________________

I. PRE-START-UP:

jVERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT

jVERIFY INSTALLATION OF OUTDOOR AIR HOOD

jVERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD (48PG and PM ONLY)

jVERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS

jVERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT

jVERIFY GAS PRESSURE TO UNIT GAS VALVE IS WITHIN SPECIFIED RANGE (48PG and PM ONLY)

jCHECK GAS PIPING FOR LEAKS (48PG AND 48PM)

jCHECK THAT INDOOR−AIR FILTERS ARE CLEAN AND IN PLACE

jCHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE

jVERIFY THAT UNIT IS LEVEL

jCHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT

jVERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED

jVERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION

jVERIFY INSTALLATION OF THERMOSTAT/SPACE SENSOR

jVERIFY CONFIGURATION VALUES FOR ELECTRONIC CONTROLS (REFER TO CONTROL SET UP CHECKLIST)

jVERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS

II.START-UP

ELECTRICAL

SUPPLY VOLTAGE

L1‐L2

L2‐L3

L3‐L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR AMPS — COMPRESSOR A1

L1

L2

L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

—COMPRESSOR B1

L1

L2

L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEAT AMPS (IF EQUIPPED)

L1

L2

L3

 

_______

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY FAN AMPS

 

 

 

L1

 

 

L2

 

 

L3

 

 

 

 

 

TEMPERATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR‐AIR TEMPERATURE

 

 

 

 

 

 

F DB (Dry Bulb)

 

 

 

 

 

RETURN‐AIR TEMPERATURE

 

 

 

 

 

 

F DB

F WB (Wet Bulb)

 

 

 

 

 

 

 

 

COOLING SUPPLY AIR

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS HEAT SUPPLY AIR (48PG AND PM )

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEAT SUPPLY AIR (50PG AND PM)

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURES

GAS INLET PRESSURE

 

 

IN. WG

 

 

 

GAS MANIFOLD PRESSURE

STAGE NO. 1

 

IN. WG

STAGE NO. 2

 

IN. WG

 

 

REFRIGERANT SUCTION

CIRCUIT A

 

PSIG

CIRCUIT A Superheat

 

degF

 

 

 

CIRCUIT B

 

PSIG

CIRCUIT B Superheat

 

degF

 

 

 

REFRIGERANT DISCHARGE

CIRCUIT A

 

PSIG

CIRCUIT A Subcooling

 

degF

 

 

 

CIRCUIT B

 

PSIG

CIRCUIT B Subcooling

 

degF

 

 

 

jVERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

GENERAL

jECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS

Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 1/11

Catalog No:48-50PGPM-03T

 

 