Carrier 48/50PM C16-28, 48/50PG C03-14 manual 48/50PG and PM, UNIT 48PM, Orientation

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 173
Image 173
UNIT

Evaporator Fan Motor Specifications − 48PM16−28 (cont)

UNIT

48PM

24

28

NOTES:

DRIVE

ORIENTATION

Low

Vertical

Mid-Low

Vertical

Mid-High

Vertical

High

Vertical

Low

Horizontal

Mid-Low

Horizontal

Mid-High

Horizontal

High

Horizontal

Low

Vertical

Mid-Low

Vertical

Mid-High

Vertical

High

Vertical

Low

Horizontal

Mid-Low

Horizontal

Mid-High

Horizontal

High

Horizontal

VOLTAGE

EFFICIENCY %

MAX BHP

MAX AMPS

208

85.8

4.26

10.6

230

85.8

4.26

9.6

460

85.8

4.26

4.8

575

87.5

5.75

6.0

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

208

N/A

N/A

N/A

230

N/A

N/A

N/A

460

N/A

N/A

N/A

575

N/A

N/A

N/A

208

85.8

4.26

10.6

230

85.8

4.26

9.6

460

85.8

4.26

4.8

575

87.5

5.75

6.0

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

48/50PG and PM

1.Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

2.All Indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.

173

Page 173
Image 173