Carrier 48/50PG C03-14, 48/50PM C16-28 Fan Performance — 50PG05 Vertical Units, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 142
Image 142
Fan Performance — 50PG05 Vertical Units

Fan Performance — 50PG05 Vertical Units

AIRFLOW

 

0.2

(Cfm)

 

Rpm

Bhp

 

1200

492

0.15

1300

513

0.18

1400

534

0.21

1500

557

0.24

1600

580

0.28

1700

603

0.33

1800

627

0.38

1900

651

0.43

2000

675

0.49

AIRFLOW

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.4

 

0.6

 

 

0.8

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

604

0.22

701

0.31

790

0.39

620

0.26

714

0.34

800

0.43

638

0.29

729

0.38

812

0.48

657

0.33

745

0.43

825

0.53

677

0.38

762

0.48

839

0.58

697

0.43

779

0.53

855

0.64

718

0.48

798

0.59

871

0.70

739

0.54

817

0.65

889

0.77

761

0.61

837

0.72

907

0.85

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.0

Rpm Bhp

873 0.49

880 0.53

889 0.58

900 0.63

912 0.69

926 0.75

940 0.82

9560.89

9720.97

48/50PG and PM

(Cfm)

 

1.2

Rpm

Bhp

 

1200

 

0.58

1300

 

0.63

1400

 

0.68

1500

 

0.74

1600

 

0.80

1700

 

0.87

1800

1005

0.94

1900

1019

1.02

2000

1034

1.10

LEGEND

1.4

Rpm Bhp

1023 0.69

1027 0.74

1032 0.79

1039 0.85

1047 0.92

1057 0.99

1068 1.06

1080 1.14

1094 1.23

1.6

Rpm Bhp

1092 0.79

1094 0.85

1098 0.91

1103 0.97

1110 1.04

1118 1.11

1128 1.19

1139 1.28

1151 1.37

NOTES:

 

1.8

 

2.0

Rpm

Bhp

Rpm

Bhp

1157

0.90

1219

1.02

1158

0.96

1220

1.08

1161

1.03

1222

1.15

1165

1.09

1225

1.22

1171

1.17

1229

1.30

1178

1.24

1235

1.38

1186

1.33

1242

1.46

1196

1.41

1251

1.56

1206

1.51

1260

1.65

Bhp - Brake Horsepower

High Range Motor/Drive Required

1.Motor drive range is 596 to 910 rpm for low range motor/drive and 828 to 1173 rpm for high range motor/drive. All other rpms require a field‐supplied drive.

2.Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.

3.See General Fan Performance Notes.

Fan Performance — 50PG06 Vertical Units

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

0.2

 

 

0.4

0.6

 

0.8

 

1.0

 

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

1500

568

0.25

667

0.34

753

0.44

 

0.54

 

0.64

1600

592

0.29

687

0.39

771

0.49

 

0.59

 

0.70

1700

616

0.34

708

0.44

789

0.54

 

0.65

 

0.76

1800

641

0.39

730

0.50

809

0.61

 

0.72

 

0.83

1900

665

0.45

752

0.56

829

0.67

 

0.79

 

0.91

2000

690

0.51

775

0.63

850

0.75

 

0.87

 

0.99

2100

716

0.57

798

0.70

871

0.82

 

0.95

1001

1.08

2200

742

0.65

821

0.78

892

0.91

 

1.04

1020

1.18

2300

768

0.73

845

0.86

915

1.00

 

1.14

1039

1.28

2400

794

0.81

869

0.96

937

1.10

1000

1.24

1059

1.38

2500

820

0.91

894

1.05

960

1.20

1021

1.35

1079

1.50

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

1.2

 

 

1.4

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

1500

 

0.75

1046

0.87

1110

0.98

1172

1.11

1231

1.23

1600

 

0.81

1055

0.93

1117

1.05

1178

1.18

1236

1.31

1700

1001

0.88

1065

1.00

1126

1.13

1185

1.26

1242

1.39

1800

1015

0.96

1077

1.08

1136

1.21

1194

1.35

1250

1.48

1900

1029

1.04

1090

1.16

1148

1.30

1204

1.44

1259

1.58

2000

1045

1.12

1104

1.26

1161

1.39

1216

1.53

1269

1.68

2100

1061

1.21

1119

1.35

1174

1.49

1228

1.64

1280

1.79

2200

1078

1.31

1135

1.45

1189

1.60

1241

1.75

1293

1.90

2300

1096

1.42

1151

1.57

1204

1.71

1256

1.87

1306

2.02

2400

1115

1.53

1169

1.68

1221

1.84

1271

1.99

1320

2.15

2500

1134

1.65

1187

1.81

1238

1.97

1287

2.13

1335

2.29

LEGEND

 

 

 

 

NOTES:

 

 

 

 

 

Bhp - Brake Horsepower

 

 

 

 

1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm

 

 

 

 

 

for high range motor/drive. All other rpms require a field‐supplied drive.

 

2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive. 3. See General Fan Performance Notes.

142