48/50PG and PM
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — SET POINTS
ITEM | EXPANSION | RANGE | UNITS |
| DEFAULT | CCN TABLE/ | CCN POINT |
| |||||||
|
|
|
|
|
|
| |
|
|
|
|
|
| SETPOINT CONFIGURATION |
|
SETPOINTS |
|
|
|
|
| SET_PNT |
|
OCSP | Occupied Cool Setpoint | 55 to 80 | °F | 78 |
|
| OCSP |
UCSP | Unoccupied Cool Setpoint | 65 to 95 | °F | 85 |
|
| UCSP |
OHSP | Occupied Heat Setpoint | 55 to 80 | °F | 68 |
|
| OHSP |
UHSP | Unoccupied Heat Setpoint | 40 to 80 | °F | 60 |
|
| UHSP |
GAP | HeatCool Setpoint Gap | 2 to 10 | ^F | 5 |
|
| HCSP_GAP |
STO.R | SPT Offset Range (+/) | 0 to 5 | ^F | 5 |
|
| SPTO_RNG |
RH.SP | Space RH Occupied SP | 30 to 100 | % | 50 |
|
| SPRH_SP |
RH.UN | Space RH Unoccupied SP | 30 to 100 | % | 50 |
|
| SPRH_USP |
RH.DB | Space RH Deadband | 2 to 20 | % | 8 |
|
| SPRH_DB |
RH.HB | Reheat Heat SP Deadband | 5 to 5 | ^F | 2 |
|
| RH_HSPDB |
CA.LO | Circuit A Lockout Temp | 0 to 100 | °F | 0 |
|
| OATLCMPA |
CB.LO | Circuit B Lockout Temp | 0 to 100 | °F | 0: no HumidiMiZer FIOP |
| OATLCMPB | |
|
|
|
| HumidiMiZer FIOP: |
|
| |
|
|
|
| 40 | (PG0816) |
|
|
|
|
|
| 0 (2028, PM16)(0307) |
|
| |
CC.LO | Circuit C Lockout Temp | 0 to 100 | °F | 0 |
|
| OATLCMPC |
HT.LO | Heating Lockout Temp | 40 to 125 | °F | 75 |
|
| OATLHEAT |
EH.LO | Econo Cool Hi Temp Limit | 40 to 100 | °F | 65 |
|
| OATLECLH |
EL.LO | Econo Cool Lo Temp Limit | 30 to 50 | °F | 0 |
|
| OATLECLL |
FC.LO | Free Cool Low Temp Limit | 30 to 70 | °F | 50 |
|
| OATLUEFC |
LCSP | Low Cool SAT Setpoint | 55 to 75 | °F | 55 | (0307) |
| LCSASP |
|
|
|
| 65 | (0828) |
|
|
HCSP | High Cool SAT Setpoint | 50 to 70 | °F | 55 |
|
| HCSASP |
|
| MODE — INPUTS |
| ||
ITEM | EXPANSION | RANGE | UNITS | CCN TABLE/ | |
|
|
|
| ||
|
|
|
| STATUS DISPLAY | |
INPUTS |
|
|
| UINPUT | |
STAT | Thermostat Inputs |
|
|
| |
Y1 | Thermostat Y1 Input | On/Off |
|
| |
Y2 | Thermostat Y2 Input | On/Off |
|
| |
W1 | Thermostat W1 Input | On/Off |
|
| |
W2 | Thermostat W2 Input | On/Off |
|
| |
G | Thermostat G Input | On/Off |
|
| |
GEN.I | General Inputs |
|
|
| |
FIL.S | Filter Status Switch | Dirty/Clean |
|
| |
FAN.S | Fan Status Switch | On/Off |
|
| |
FDWN | Fire Shutdown Switch | On/Off |
|
| |
ENTH | Outdoor Enthalpy Switch | High/Low |
|
| |
RM.OC | Remote Occupancy Switch | On/Off |
|
| |
HUM | Space Humidity Switch | High/Low |
|
| |
CS.IN | Current Sensor Inputs |
|
|
| |
CS.A1 | Compressor A1 Feedback | On/Off |
|
| |
CS.A2 | Compressor A2 Feedback | On/Off |
|
| |
CS.B1 | Compressor B1 Feedback | On/Off |
|
| |
CS.C1 | Compressor C1 Feedback | On/Off |
|
| |
AIR.Q | Air Quality Inputs |
|
|
| |
IAQ.S | IAQ Level (switch) | High/Low |
|
| |
IAQ | IAQ Level (sensor) | xxxx | ppm |
| |
OAQ | OAQ Level (sensor) | xxxx | ppm |
| |
SP.RH | Space Humidity Sensor | xxx.x | % |
|
| CCN | DISPLAY |
CCN POINT | WRITE | WRITE |
| STATUS | STATUS |
Y1 | forcible |
|
Y2 | forcible |
|
W1 | forcible |
|
W2 | forcible |
|
Gforcible
FILTSTAT | forcible |
|
FAN_STAT | forcible |
|
FIREDOWN | forcible |
|
ENTHALPY | forcible |
|
REM_OCC | forcible |
|
HUM_STAT | forcible |
|
CS_A1 |
|
|
CS_A2 |
|
|
CS_B1 |
|
|
CS_C1 |
|
|
IAQIN | forcible | forcible |
IAQ | forcible | forcible |
OAQ | forcible | forcible |
SPRH | forcible | forcible |
98