MODE — SET POINTS

48/50PG and PM

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — SET POINTS

ITEM

EXPANSION

RANGE

UNITS

 

DEFAULT

CCN TABLE/

CCN POINT

 

SUB-TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

SETPOINT CONFIGURATION

 

SETPOINTS

 

 

 

 

 

SET_PNT

 

OCSP

Occupied Cool Setpoint

55 to 80

°F

78

 

 

OCSP

UCSP

Unoccupied Cool Setpoint

65 to 95

°F

85

 

 

UCSP

OHSP

Occupied Heat Setpoint

55 to 80

°F

68

 

 

OHSP

UHSP

Unoccupied Heat Setpoint

40 to 80

°F

60

 

 

UHSP

GAP

Heat­Cool Setpoint Gap

2 to 10

^F

5

 

 

HCSP_GAP

STO.R

SPT Offset Range (+/­)

0 to 5

^F

5

 

 

SPTO_RNG

RH.SP

Space RH Occupied SP

30 to 100

%

50

 

 

SPRH_SP

RH.UN

Space RH Unoccupied SP

30 to 100

%

50

 

 

SPRH_USP

RH.DB

Space RH Deadband

2 to 20

%

8

 

 

SPRH_DB

RH.HB

Reheat Heat SP Deadband

­5 to 5

^F

2

 

 

RH_HSPDB

CA.LO

Circuit A Lockout Temp

0 to 100

°F

0

 

 

OATLCMPA

CB.LO

Circuit B Lockout Temp

0 to 100

°F

0: no Humidi­MiZer FIOP

 

OATLCMPB

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

 

 

40

(PG08­16)

 

 

 

 

 

 

0 (20­28, PM16)(03­07)

 

 

CC.LO

Circuit C Lockout Temp

0 to 100

°F

0

 

 

OATLCMPC

HT.LO

Heating Lockout Temp

40 to 125

°F

75

 

 

OATLHEAT

EH.LO

Econo Cool Hi Temp Limit

40 to 100

°F

65

 

 

OATLECLH

EL.LO

Econo Cool Lo Temp Limit

­ 30 to 50

°F

0

 

 

OATLECLL

FC.LO

Free Cool Low Temp Limit

­ 30 to 70

°F

50

 

 

OATLUEFC

LCSP

Low Cool SAT Setpoint

55 to 75

°F

55

(03­07)

 

LCSASP

 

 

 

 

65

(08­28)

 

 

HCSP

High Cool SAT Setpoint

50 to 70

°F

55

 

 

HCSASP

 

 

MODE — INPUTS

 

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/

SUB-TABLE

 

 

 

 

 

 

 

 

STATUS DISPLAY

INPUTS

 

 

 

UINPUT

STAT

Thermostat Inputs

 

 

 

Y1

Thermostat Y1 Input

On/Off

 

 

Y2

Thermostat Y2 Input

On/Off

 

 

W1

Thermostat W1 Input

On/Off

 

 

W2

Thermostat W2 Input

On/Off

 

 

G

Thermostat G Input

On/Off

 

 

GEN.I

General Inputs

 

 

 

FIL.S

Filter Status Switch

Dirty/Clean

 

 

FAN.S

Fan Status Switch

On/Off

 

 

FDWN

Fire Shutdown Switch

On/Off

 

 

ENTH

Outdoor Enthalpy Switch

High/Low

 

 

RM.OC

Remote Occupancy Switch

On/Off

 

 

HUM

Space Humidity Switch

High/Low

 

 

CS.IN

Current Sensor Inputs

 

 

 

CS.A1

Compressor A1 Feedback

On/Off

 

 

CS.A2

Compressor A2 Feedback

On/Off

 

 

CS.B1

Compressor B1 Feedback

On/Off

 

 

CS.C1

Compressor C1 Feedback

On/Off

 

 

AIR.Q

Air Quality Inputs

 

 

 

IAQ.S

IAQ Level (switch)

High/Low

 

 

IAQ

IAQ Level (sensor)

xxxx

ppm

 

OAQ

OAQ Level (sensor)

xxxx

ppm

 

SP.RH

Space Humidity Sensor

xxx.x

%

 

 

CCN

DISPLAY

CCN POINT

WRITE

WRITE

 

STATUS

STATUS

Y1

forcible

 

Y2

forcible

 

W1

forcible

 

W2

forcible

 

Gforcible

FILTSTAT

forcible

 

FAN_STAT

forcible

 

FIREDOWN

forcible

 

ENTHALPY

forcible

 

REM_OCC

forcible

 

HUM_STAT

forcible

 

CS_A1

 

 

CS_A2

 

 

CS_B1

 

 

CS_C1

 

 

IAQIN

forcible

forcible

IAQ

forcible

forcible

OAQ

forcible

forcible

SPRH

forcible

forcible