MODE — CONFIGURATION

48/50PG and PM

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/

CCN POINT

PAGE NO.

SUB-TABLE

 

 

 

 

 

 

 

CONFIGURATION

 

 

 

 

SERVICE

 

14

 

 

 

 

CONFIGURATION

 

 

 

 

 

 

 

 

DISP

Display Configuration

 

 

 

DISPLAY

 

14

METR

Metric Display

Off/On

 

Off

 

DISPUNIT

14

LANG

Language Selection

0=English

 

0

 

LANGUAGE

14

 

 

1=Spanish

 

 

 

 

 

 

 

2=French

 

 

 

 

 

 

 

3=Portuguese

 

 

 

 

 

PROT

Password Enable

Disable/Enable

 

Enable

 

PASS_EBL

14

PSWD

Service Password

0000 to 9999

 

1111

 

PASSWORD

14

TEST

Test Display LEDs

Off/On

 

Off

(display

DISPTEST

14

 

 

 

 

 

only, not in table)

 

 

UNIT

Unit Configuration

 

 

 

UNIT

 

14

S.DLY

Startup Delay

10 to 600

sec

30

 

STARTDLY

14

U.CTL

Unit Control Type

2=Thermostat

 

2

 

CTL_TYPE

14

 

 

3=Space

 

 

 

 

 

 

 

Sensor

 

 

 

 

 

T.CTL

Thermostat Control Type

0=Adaptive

 

0

 

STATTYPE

15

 

 

1=1 Stage Y1

 

 

 

 

 

 

 

2=2 Stage Y1

 

 

 

 

 

 

 

3=Digital

 

 

 

 

 

OC.FN

Fan On When Occupied

No/Yes

 

Yes

 

OCC_FAN

15

IDF.F

Shut Down on IDF Failure

No/Yes

 

Yes

 

FATALFAN

15

FN.SW

Fan Status Switch

0=No Switch

 

0: no FIOP

 

FANSTCFG

15

 

 

1=Normal

 

1: FIOP

 

 

 

 

 

Open

 

 

 

 

 

 

 

2=Normal

 

 

 

 

 

 

 

Closed

 

 

 

 

 

FL.SW

Filter Status Switch

0=No Switch

 

0: no FIOP

 

FILSTCFG

15

 

 

1=Normal

 

1: FIOP

 

 

 

 

 

Open

 

 

 

 

 

 

 

2=Normal

 

 

 

 

 

 

 

Closed

 

 

 

 

 

FS.SW

Fire Shutdown Switch

0=No Switch

 

0: no FIOP

 

SHTDNCFG

15

 

 

1=Normal

 

1: FIOP

 

 

 

 

 

Open

 

 

 

 

 

 

 

2=Normal

 

 

 

 

 

 

 

Closed

 

 

 

 

 

RM.SW

Remote Occupancy

0=No Switch

 

0

 

REMOCCFG

15

 

Switch

1=Normal

 

 

 

 

 

 

 

Open

 

 

 

 

 

 

 

2=Normal

 

 

 

 

 

 

 

Closed

 

 

 

 

 

SAT.T

SAT Settling Time

10 to 900

sec

240

 

SAT_SET

15

RAT.S

RAT Sensor on SPTO In­

No/Yes

 

No

 

RAT_SPTO

15

 

put

 

 

 

 

 

 

RH.S

RH Sensor on OAQ Input

No/Yes

 

No

 

RH_OAQ

15

RH.SW

Space Humidity Switch

0=No Switch

 

0: no Humidi­MiZer

 

HUMSTCFG

15

 

 

1=Normal

 

FIOP

 

 

 

 

 

Open

 

1: Humidi­MiZer

 

 

 

 

 

2=Normal

 

FIOP

 

 

 

 

 

Closed

 

 

 

 

 

TCS.C

Temp Cmp Strt Cool

0 to 60

mins

0

 

TCSTCOOL

15

 

Factr

 

 

 

 

 

 

TCS.H

Temp Cmp Strt Heat

0 to 60

mins

0

 

TCSTHEAT

15

 

Factr

 

 

 

 

 

 

100