Carrier 48/50PM C16-28 manual IAQ Switch Input, Outdoor Air Quality Analog Input, IAQ Control

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 33
Image 33
VENTILATION FOR PEOPLE

ECONOMIZER MINIMUM DAMPER POSITION

(EC. MN)

MINIMUM

IAQ

DAMPER

POSITION

(AQ. MN)

VENTILATIONINCREASING

VENTILATION FOR PEOPLE

 

VENTILATION FOR SOURCES

and PM

100

700

INSIDE/OUTSIDE CO2 DIFFERENTIAL

AQ

AQ

 

DIFFERENTIAL

 

DIFFERENTIAL

 

LOW (AQD.L)

 

HIGH (AQD.H)

 

 

 

C07010

Fig. 20 − IAQ Control

48/50PG

IA.CF = 3 (Control Minimum Position)

When IA.CF = 3, an external 4 to 20 mA source is used to set the minimum position. The 4 mA signal corresponds to 0% and the 20 mA signal corresponds to 100%. In this mode, configurations such as ConfigurationAIR.QEC.MN and ConfigurationAIR.QAQ.MN are not used.

If the indoor fan is not operating, the economizer position will be zero. The damper position may exceed the economizer minimum position to provide economizer cooling.

IAQ (Switch Input)

Indoor air quality can also be measured using a switch input. For the purpose of specifying the type of switch input, low CO2 levels are considered normal. The IAQ switch input is defined by the configuration by ConfigurationAIR.QII.CF IAQ Level (Switch Input). Enthalpy and IAQ are controlled by the same switch input and therefore they cannot be used simultaneously.

II.CF = 0 (No IAQ)

The II.CF = 0 configuration signifies that there is no IAQ switch input. The damper will operate at the EC.MN position when the space is occupied and the indoor fan is on.

II.CF = 1 (DCV NO) or II.CF = 2 (DCV NC)

The Demand Control Ventilation (DCV) allows the economizer minimum position to be decreased when there is no IAQ problem. If IAQ is low, the economizer minimum position is Minimum IAQ Damper Position (ConfigurationAIR.QAQ.MN). If IAQ is high, the economizer minimum position is the Economizer Minimum Position (ConfigurationAIR.QEC.MN).

II.CF = 3 (Override NO) or II.CF = 4 (Override NC)

The damper override function permits absolute positioning of the economizer damper for ventilation purposes. The override is active when IAQ is high and inactive when IAQ is low. The override position is configurable by the configuration by Configuration AIR.QOVR.P (Economizer Override Position).

Outdoor Air Quality (Analog Input)

The ComfortLinkt control is configured for outdoor air quality sensors which provide 4 to 20 mA for 0 to 2000 ppm. If a sensor has a different range, the ppm display range must be reconfigured by entering new values for ConfigurationAIR.Q O.4M and ConfigurationAIR.QO.20M.

OA.CF = 0 (No OAQ)

This signifies there is no outdoor air sensor installed. The default value of OAQ is 400 ppm.

OA.CF = 1 (DCV)

The outdoor air quality sensor analog input is for the value of OAQ during demand control ventilation operation.

OA.CF = 2 (OAQ Lockout)

The outdoor air quality sensor analog input is only used to lock out the outdoor ventilation. The economizer commanded position is set to 0% when the ppm exceeds the OAQ lockout value configured for ConfigurationAIR.QOAQ.L. The default value of OAQ.L is 600 ppm.

33

Page 33
Image 33
Carrier 48/50PM C16-28 IAQ Switch Input, Outdoor Air Quality Analog Input, IAQ Control, IA.CF = 3 Control Minimum Position