MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

OAU

Outside Air Unit Config

 

 

 

OA.TY

Outdoor Air Unit Type

0=No OAU

 

0: no FIOP

 

 

1=ERV Module

 

1: FIOP EXv2

 

 

2=Economizer

 

 

 

 

3=Pwr Exhaust

 

 

 

 

4=OA Monitor

 

 

 

 

5=100% OA

 

 

 

 

Unit

 

 

 

 

6=EXv1 ERV

 

 

OA.FC

Outside Air Fan Curve

0 to 999

 

0: no FIOP

 

 

 

 

1: PG03­07 1ph low

 

 

 

 

CFM ERV

 

 

 

 

2: PG03­07 3ph low

 

 

 

 

CFM ERV

 

 

 

 

3: PG03­07 1ph high

 

 

 

 

CFM ERV

 

 

 

 

4: PG03­07 3ph high

 

 

 

 

CFM ERV

 

 

 

 

5: PG08­14 low CFM

 

 

 

 

ERV

 

 

 

 

6: PG08­14 high CFM

 

 

 

 

ERV

 

 

 

 

7: PM16­24 low CFM

 

 

 

 

ERV

 

 

 

 

8: PM16­24 high CFM

 

 

 

 

ERV

 

 

 

 

9: PM28 low CFM ERV

 

 

 

 

10: PM28 high CFM

 

 

 

 

ERV

PE.FC

Exhaust Air Fan Curve

0 to 999

 

0: no FIOP

 

 

 

 

1: PG03­06 1ph low

 

 

 

 

CFM ERV

 

 

 

 

2: PG03­07 3ph low

 

 

 

 

CFM ERV

 

 

 

 

3: PG03­06 1ph high

 

 

 

 

CFM ERV

 

 

 

 

4: PG03­07 3ph high

 

 

 

 

CFM ERV

 

 

 

 

5: PG08­14 low CFM

 

 

 

 

ERV

 

 

 

 

6: PG08­14 high CFM

 

 

 

 

ERV

 

 

 

 

7: PM16­24 low CFM

 

 

 

 

ERV

 

 

 

 

8: PM16­24 high CFM

 

 

 

 

ERV

 

 

 

 

9: PM28 low CFM

 

 

 

 

ERV

 

 

 

 

10: PM28 high CFM

 

 

 

 

ERV

U.RUN

OAU Unoccupied Operation

No/Yes

 

NO

OAU.F

Shut Down on Fan Failure

No/Yes

 

Yes

M.WHL

Modulating Wheel Install

No/Yes

 

NO

OA.MN

Minimum Outside Air

0 to 32000

CFM

375: PG03­07 low

 

CFM

 

 

CFM ERV

 

 

 

 

800: PG03­07 high

 

 

 

 

CFM ERV

 

 

 

 

1000: PG08­14 low

 

 

 

 

CFM ERV

 

 

 

 

2500: PG08­14 high

 

 

 

 

CFM ERV

 

 

 

 

3000: PM16­28 low

 

 

 

 

CFM ERV

 

 

 

 

4000: PM16­24 high

 

 

 

 

CFM ERV

 

 

 

 

5000: PM28 high

 

 

 

 

CFM ERV

DCV.M

Min DCV Outside Air CFM

0 to 32000

CFM

100: PG03­07 ERV

 

 

 

 

250: PG08­14 low

 

 

 

 

CFM ERV

 

 

 

 

600: PG08­14 high

 

 

 

 

CFM ERV

 

 

 

 

1000: PM16­24 low

 

 

 

 

CFM ERV

 

 

 

 

1500: PM16­24 high

 

 

 

 

CFM ERV, PM28 low

 

 

 

 

CFM ERV

 

 

 

 

2000: PM28 high

 

 

 

 

CFM ERV

PEX.C

Power Exhaust Control

0=Offset CFM

 

0

 

 

1=BP

 

 

PE.OF

Power Exhaust CFM Offset

­17000 to

CFM

­200

 

 

17000

 

 

BP.SP

Building Pressure Setpnt

­0.25 to 0.25

in H2O

0.05

OA.TM

Outside Air Tempering

Disable/Enable

 

Disable

TM.LO

OA Tempring Lockout Temp

0 to 80

°F

60

TM.SP

OA Tempring SAT Setpoint

35 to 80

°F

55

OAC.K

Outside Air CFM k Factor

0.8 to 1.2

 

1.0

EXC.K

Exhaust Air CFM k Factor

0.8 to 1.2

 

1.0

CCN TABLE/ SUB-TABLE

OAU_CFG

CCN POINT

PAGE NO.

12

OAU_TYPE40

OAFANCRV 105

PEFANCRV 105

UNOCCRUN

105

FATALOAU

105

MODWHEEL

105

MINOACFM

95

MINDCVSP95

PEX_CTL105

EXOFFSET95

OAU_BPSP95

OATEMPER 95

OATMPLOC 95

OATMPSPT95

OACFM_K105