Carrier 48/50PM C16-28 Mode — Operating Modes, Appendix A — Local Display And Ccn Tables Cont

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 109
Image 109
MODE — OPERATING MODES

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — OPERATING MODES

ITEM

EXPANSION

RANGE

UNITS

OPERATING MODES

 

 

 

MODE

Control Modes

 

 

SYS

Unit operation disabled

 

 

 

Unit operation enabled

 

 

 

Service test enabled

 

 

HVAC

HVAC Operation Disabled

 

 

 

Ventilation (fan­only)

 

 

 

Cooling

 

 

 

Free Cooling

 

 

 

Unoccupied Free Cooling

 

 

 

Reheat1

 

 

 

Reheat2

 

 

 

Reheat1 / Reheat2

 

 

 

Heating

 

 

HV.DN

Remote HVAC Mode Disable

No/Yes

 

EFF.C

Cool Setpoint In Effect

xx.x

°F

EFF.H

Heat Setpoint In Effect

xx.x

°F

OCC

Currently Occupied

No/Yes

 

T.OVR

Timed Override in Effect

No/Yes

 

LINK

Linkage Active

No/Yes

 

D.LMT

Demand Limit In Effect

No/Yes

 

C.LOC

Compressor OAT Lockout

No/Yes

 

H.LOC

Heat OAT Lockout

No/Yes

 

OK.EC

OK to Use Economizer?

No/Yes

 

COOL

Cool Mode Diagnostic

 

 

COOL

In Cooling Mode?

No/Yes

 

OK.CL

OK to Select Cool Mode?

No/Yes

 

MS.TG

Mode Select Timeguard

xxx

secs

OK.EC

OK to Use Economizer?

No/Yes

 

OK.MC

OK to Use Compressors?

No/Yes

 

C.LOC

Compressor OAT Lockout

No/Yes

 

CA.LO

Circuit A Lockout Temp

xxx

°F

CB.LO

Circuit B Lockout Temp

xxx

°F

CC.LO

Circuit C Lockout Temp

xxx

°F

IDF

Indoor Fan State

Off/On

 

F.SPD

Commanded Fan Speed

xxx

%

AVL.C

Available Cooling Stages

x

 

REQ.C

Requested Cooling Stages

x

 

LMT.C

Max Cool Stage In Effect

x

 

ACT.C

Actual Cooling Stages

x

 

CMP.A

Circuit A Compressor(s)

Off/On

 

CMP.B

Circuit B Compressor

Off/On

 

CMP.C

Circuit C Compressor

Off/On

 

ST.A

Circuit A Strikes

x

 

ST.B

Circuit B Strikes

x

 

ST.C

Circuit C Strikes

x

 

F.LEV

Outdoor Fan Level

x

 

SAT

Supply Air Temperature

 

 

SAT

Supply Air Temperature

xxx.x

°F

SA.DM

Supply Air Temp Demand

xxx.x

^F

SA.PD

SAT Cool Demand (+) Level

xx.x

^F

SA.ND

SAT Cool Demand (­) Level

xx.x

^F

SAT.U

Minimum SAT Upper Level

xx.x

°F

SAT.L

Minimum SAT Lower Level

xx.x

°F

SA.TR

Supply Air d/dt (F/min)

xxxx.x

 

SA.DR

SAT Delta Reference Temp

xxx.x

°F

SPT

Space Temperature

 

 

SPT

Space Temperature

xxx.x

°F

DMD.C

Cooling Demand

xxx.x

^F

TRD.C

Cool Demand d/dt (F/min)

xxx.x

 

CL.PD

SPT Cool Demand (+) Level

xx.x

^F

CL.ND

SPT Cool Demand (­) Level

xx.x

^F

C.LAG

Cool Thermal Lag Factor

x.x

 

HMZR

Humidimizer

 

 

REHT

Humidimizer Equipped

No/Yes

 

HUM

Space Humidity Switch

Low/High

 

SP.RH

Space Humidity Sensor

xxx.x

%

R.LO.A

Reheat2 OAT Lockout A

No/Yes

 

RA.LO

Reheat2 OAT Limit A

xx

°F

R.LP.A

Reheat2 SSP Override A

No/Yes

 

R.LO.B

Reheat2 OAT Lockout B,C

No/Yes

 

RB.LO

Reheat2 OAT Limit B,C

xx

°F

R.LP.B

Reheat2 SSP Override B,C

No/Yes

 

AVL.R

Available Reheat2 Stages

x

 

REQ.R

Requested Reheat2 Stages

x

 

ACT.R

Actual Reheat2 Stages

x

 

CRC

Cool­>Reheat1 Control

Off/On

 

RH2.A

Reheat2 Valve A

Off/On

 

RH2.B

Reheat2 Valve B,C

Off/On

 

CCN TABLE/ SUB-TABLE

MAINTENANCE

MODES

COOLDIAG

CCN WRITE

CCN POINT

STATUS

SYS_MODE_TEXT1 SYS_MODE_TEXT2 (table only)

SYS_MODE_TEXT3 (table only) HVACMODE_TEXT_1 HVACMODE_TEXT_2 (table only) HVACMODE_TEXT_3 (table only)

HVACDOWN forcible

CSP_EFF

HSP_EFF

OCCUPIEDforcible

MODETOVR

MODELINK

MODEDMDL

COMPLOCK

HEATLOCK

ECONCOOL

IN_COOL

OKTOCOOL

COOLMSTG

ECONCOOL

MECHCOOL

COMPLOCK

OATLCMPA

OATLCMPB

OATLCMPC

IDFSTATE

FANSPEED

AVLCSTGS

REQCSTGS

CSTGLIMT

ACTCSTGS

COMP_A

COMP_B

COMP_C

ASTRIKES

BSTRIKES

CSTRIKES

FANLEV

SAT_DISP

SAT_DMD

SAT_POS

SAT_NEG

SATMIN_H

SATMIN_L

SATTREND

SAT_REF

SPACE_Tforcible

COOL_DMD

CLDTREND

DEM_POS

DEM_NEG

COOL_LAG

REHEAT

HUM_STATforcible

SPRHforcible

RHALOCK

OATLRH_A

RHALPOV

RHBLOCK

OATLRH_B

RHBLPOV

AVLRSTGS

REQRSTGS

ACTRSTGS CRC RH2_A RH2_B

DISPLAY WRITE STATUS

forcible

forcible

forcible

48/50PG and PM

109

Page 109
Image 109
Carrier 48/50PM C16-28 manual Mode — Operating Modes, Appendix A — Local Display And Ccn Tables Cont, 48/50PG and PM, Cool