Carrier 48/50PM C16-28 Mode — Alarms, Appendix A — Local Display And Ccn Tables Cont, OAU cont

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 111
Image 111
OAU (cont)

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — OPERATING MODES (cont)

CCN TABLE/

CCN WRITE

DISPLAY

SUB-TABLE

OAU_DIAG

DMDL

TRIM

CCN POINT

OAUPESPD ACTEXCFM CMDEXCFM OAU_BPSP

OAU_BP

OATMPLOC

OATMPSPT

OAHEATER

OAUALRM1

OAUALRM2

OAUALRM3

OAUALRM4

MODEDMDL CSTGLIMT HSTGLIMT MODEREDL MODESHED MAXCSTGS MAXHSTGS

STATUS

WRITE

STATUS

48/50PG and PM

ITEM

EXPANSION

RANGE

UNITS

OAU (cont)

Outside Air Unit Diagnostic

 

 

EX.FS

OAU Exhaust Fan Speed

xxx

%

A.EX

Actual Exhaust Air CFM

xxxxx

CFM

C.EX

Command Exhaust Air CFM

xxxxx

CFM

BP.SP

Building Pressure Setpnt

x.xx

in

 

 

 

H2O

BP

Building Pressure

x.xx

in

 

 

 

H2O

TM.LO

OA Tempring Lockout Temp

xx

°F

TM.SP

OA Tempring SAT Setpoint

xx

°F

OA.HT

OAU Tempering Heater

xxx

%

ALM.1

OAU Motor Failure Alarm

Off/On

 

ALM.2

OAU Dirty Filter Alarm

Off/On

 

ALM.3

OA Low CFM Alarm

Off/On

 

ALM.4

OAU Alarm

Off/On

 

DMD.L

DEMAND LIMITING

 

 

D.LMT

Demand Limit In Effect

No/Yes

 

LMT.C

Max Cool Stage In Effect

x

 

LMT.H

Max Heat Stage In Effect

x

 

REDL

Redline Activated

No/Yes

 

SHED

Loadshed Activated

No/Yes

 

MAX.C

Max Allowed Cool Stages

x

 

MAX.H

Max Allowed Heat Stages

x

 

(Display TRIM ­ see

Sensor Calibration

 

 

Configuration)

 

 

 

 

Space Temp Calibration

­30 to 130

°F

 

Space Temp Trim

­30 to 30

^F

 

Supply Air Temp Calib.

­30 to 130

°F

 

Supply Air Temp Trim

­30 to 30

^F

 

Return Air Temp Calib.

­30 to 130

°F

 

Return Air Temp Trim

­30 to 30

^F

(LINKDATA = CCN

CCN ­ Linkage

 

 

only)

 

 

 

 

Supervisory Element #

xxx

 

 

Supervisory Bus

xxx

 

 

Supervisory Block Number

xxx

 

 

Average Occup. Heat Stp.

xxxx.x

°F

 

Average Occup. Cool Stp.

xxxx.x

°F

 

Average Unocc. Heat Stp.

xxxx.x

°F

 

Average Unocc. Cool Stp.

xxxx.x

°F

 

Average Zone Temperature

xxxx.x

°F

 

Average Occup. Zone Temp

xxxx.x

°F

 

Linkage System Occupied?

No/Yes

 

 

Next Occupied Day

"Mon",

3­char

 

 

"Tue", ... ,

text

 

 

"Sun"

 

 

Next Occupied Time

xx:xx

hh:mm

 

Next Unoccupied Day

"Mon",

3­char

 

 

"Tue", ... ,

text

 

 

"Sun"

 

 

Next Unoccupied Time

xx:xx

hh:mm

 

Last Unoccupied Day

"Mon",

3­char text

 

 

"Tue", ... ,

 

 

 

"Sun"

 

 

Last Unoccupied Time

xx:xx

hh:mm

(OCCDEFM = CCN

Occupancy Supervisory

 

 

only)

 

 

 

 

Current Mode (1=Occup)

0,1

 

 

Current Occup Period #

0 to 8

 

 

Time­Override in Effect

No/Yes

 

 

Time­Override Duration

0 to 4

hours

 

Current Occupied Tiime

xx.xx

hh:m

 

 

 

m

 

Current Unoccupied Time

xx.xx

hh:mm

 

Next Occupied Day

 

 

 

Next Occupied Time

xx.xx

hh:mm

 

Next Unoccupied Day

 

 

 

Next Unoccupied Time

xx.xx

hh:mm

 

Previous Unoccupied Day

 

 

 

Previous Unoccupied Time

xx.xx

hh.mm

LINKDATA

OCCDEFM

SPT_CALforcible

SPT_OFFforcible

SAT_CALforcible

SAT_OFFforcible

RAT_CALforcible

RAT_OFFforcible

SUPE­ADR

SUPE­BUS

BLOCKNUM

AOHS

AOCS

AUHS

AUCS

AZT

AOZT

LOCC

LNEXTOCD

LNEXTOCCforcible

LNEXTUOD

LNEXTUNCforcible

LLASTUOD

LLASTUNCforcible

MODE

PER_NO

OVERLAST

OVR_HRS

STRTTIME

ENDTIME

NXTOCDAY

NXTOCTIM

NXTUNDAY

NXTUNTIM

PRVUNDAY

PRVUNTIM

MODE — ALARMS

 

 

 

 

CCN TABLE/

CCN

CCN

ITEM

EXPANSION

RANGE

DEFAULT

WRITE

SUB-TABLE

POINT

 

 

 

 

STATUS

 

 

 

 

 

 

 

 

 

 

MAINTENANCE DISPLAY

 

 

ALARMS

 

 

 

ALARMS

 

 

R.CUR

Reset All Current Alarms

Yes/No

No

 

ALRESET

forcible

R.HIS

Reset Alarm History

Yes/No

No

 

ALHISCLR

forcible

CURR

Currently Active Alarms

 

 

 

 

 

alarm#

text string

 

 

 

ALARM01C -

 

 

 

 

ALARM25C

 

 

 

 

 

 

 

(repeat up to 25 alarms)

 

 

 

 

 

 

HIST

Alarm History

 

 

ALARM HISTORY

 

 

alarm#

alarm#-mm/dd/yy-

 

 

 

 

 

hh.mm-text string

 

 

 

 

 

 

 

 

 

 

 

(repeat up to 20 alarms)

 

 

 

 

 

 

DISPLAY WRITE STATUS

forcible forcible

111

Page 111
Image 111
Carrier 48/50PM C16-28 manual Mode — Alarms, Appendix A — Local Display And Ccn Tables Cont, MODE — OPERATING MODES cont