48/50PG and PM

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

ECON

Economizer Configuration

 

 

 

EC.EN

Economizer Installed

No/Yes

 

No: no FIOP

 

 

 

 

Yes: FIOP

E.CTL

Economizer Control Type

1=Dig/Posi­

 

1

 

 

tion

 

 

 

 

2=Dig/Com­

 

 

 

 

mand

 

 

 

 

3=Analog

 

 

 

 

Ctrl

 

 

EC.MN

Econo Minimum Position

0 to 100

%

30

 

 

 

 

0: ERV FIOP

EC.MX

Econo Cool Max Position

0 to 100

%

100

M.ANG

Min Actuator Ctrl Angle

75 to 90

 

88

EH.LO

Econo Cool Hi Temp Limit

40 to 100

°F

65

EL.LO

Econo Cool Lo Temp

­30 to 50

°F

0

 

Limit

 

 

 

DF.DB

Diff Dry Bulb Control

Disable/En­

 

Disable

 

 

able

 

 

UEFC

Unoccupied Free Cooling

0=Disabled

 

2

 

 

1=Unoc­

 

 

 

 

cpied

 

 

 

 

2=PreOccu­

 

 

 

 

pancy

 

 

FC.TM

Free Cool PreOcc Time

1 to 9999

mins

120

FC.LO

Free Cool Low Temp Limit

­30 to 70

°F

50

PE.EN

Power Exhaust Installed

No/Yes

 

No: no FIOP

 

 

 

 

Yes: FIOP

PE.1

PE Stage1 Econo Position

0 to 100

%

40

PE.2

PE Stage2 Econo Position

0 to 100

%

75

EN.SW

Enthalpy Switch

0=No Switch

 

0: no FIOP

 

 

1=Normal

 

1: FIOP

 

 

Open

 

 

 

 

2=Normal

 

 

 

 

Closed

 

 

E.TRV

Economizer Travel Time

5 to 300

secs

150

E.MXB

Bottom Stage Max Econo

0 to 100

%

50

E.MXM

Middle Stage Max Econo

0 to 100

%

35

E.MXT

Top Stage Max Econo

0 to 100

%

25 (PG03­16)

 

 

 

 

0 (20­28, PM16)

AIR.Q

Air Quality Config.

 

 

 

IA.CF

IAQ Analog Input Config

0=No IAQ

 

0: no FIOP

 

 

1=DCV

 

1: FIOP

 

 

2=Override

 

 

 

 

IAQ

 

 

 

 

3=Ctrl Min

 

 

 

 

Pos

 

 

IA.FN

IAQ Analog Fan Config

0=Never

 

0

 

 

1=Occupied

 

 

 

 

2=Always

 

 

II.CF

IAQ Switch Input Config

0=No IAQ

 

0

 

 

1=DCV N/O

 

 

 

 

2=DCV N/C

 

 

 

 

3=Override

 

 

 

 

N/O

 

 

 

 

4=Override

 

 

 

 

N/C

 

 

II.FN

IAQ Switch Fan Config

0=Never

 

0

 

 

1=Occupied

 

 

 

 

2=Always

 

 

AQ.MN

Econo Min IAQ Position

0 to 100

%

10

 

 

 

 

0: ERV FIOP

EC.MN

Econo Minimum Position

0 to 100

%

30

 

 

 

 

0: ERV FIOP

OVR.P

IAQ Override Position

0 to 100

%

100

OA.CF

OAQ Analog Input Config

0=No OAQ

 

0

 

 

1=DCV

 

 

 

 

2=Lockout

 

 

 

 

OAQ

 

 

OAQ.L

OAQ Lockout Limit

0 to 5000

 

600

AQD.L

AQ Differential Low

0 to 5000

 

100

AQD.H

AQ Differential High

0 to 5000

 

700

DF.ON

Fan On AQ Differential

0 to 5000

 

600

DF.OF

Fan Off AQ Differential

0 to 5000

 

200

I.4M

IAQ Sensor Value at 4mA

0 to 5000

 

0

I.20M

IAQ Sensor Value at

0 to 5000

 

2000

 

20mA

 

 

 

O.4M

OAQ Sensor Value at

0 to 5000

 

0

 

4mA

 

 

 

O.20M

OAQ Sensor Value at

0 to 5000

 

2000

 

20mA

 

 

 

H.4M

RH Sensor Value at 4mA

0 to 50

%

0

H.20M

RH Sensor Value at 20mA

60 to 100

%

100

CCN TABLE/ SUB-TABLE

ECON_CFG

IAQ_CFG

CCN POINT

PAGE NO.

23

ECONO23

ECON_CTL14

ECONOMIN 23

ECONOMAX 23

MINANGLE23

OATLECLH23

OATLECLL23

DIFFBULB23

UEFC_CFG23

UEFCTIME23

OATLUEFC23

PE_ENABL24

PE1_POS24

PE2_POS24

ENTHLCFG 10

ECONOTRV 104

ECONMAXB 104

ECONMAXM 104

ECONMAXT 104

14

IAQANCFG14

IAQANFAN30

IAQINCFG30

IAQINFAN34

IAQMINP30

ECONOMIN 23

IAQOVPOS30

OAQANCFG 30

OAQLOCK30

DAQ_LOW30

DAQ_HIGH30

DAQFNON34

DAQFNOFF 34

IAQ_4MA30

IAQ_20MA30

OAQ_4MA33

OAQ_20MA33

RH_4MA24

RH_20MA24