APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — RUN STATUS (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/

CCN POINT

CCN

MENU

 

 

 

 

SUB­TABLE

 

WRITE

WRITE

 

 

 

 

 

 

STATUS

STATUS

HEAT

Heating Status

 

 

HEATDISP

 

 

 

DMD.H

Heating Demand

xxx.x

^F

 

HEAT_DMD

 

 

AVL.H

Available Heating Stages

x

 

 

AVLHSTGS

 

 

REQ.H

Requested Heating Stages

x

 

 

REQHSTGS

 

 

MAX.H

Max Allowed Heat Stages

x

 

 

MAXHSTGS

forcible

 

LMT.H

Max Heat Stage In Effect

x

 

 

HSTGLIMT

 

 

IDF

Indoor Fan State

Off/On

 

 

IDFSTATE

 

 

F.SPD

Commanded Fan Speed

xxx

%

 

FANSPEED

 

 

HT.1

Heat Stage 1 Relay

Off/On

 

 

HEAT_1

 

 

TG.H1

Heat Stage 1 Timeguard

xxx

sec

 

TIMGD_H1

 

 

HT.2

Heat Stage 2 Relay

Off/On

 

 

HEAT_2

 

 

TG.H2

Heat Stage 2 Timeguard

xxx

sec

 

TIMGD_H2

 

 

ECON

Economizer Status

 

 

ECONDISP

 

 

 

EC.CP

Econo Commanded Position

xxx

%

 

ECONOCMD

 

 

EC.AP

Econo Actual Position

xxx

%

 

ECONOPOS

 

 

EC.MP

Min Position in Effect

xxx

%

 

MIN_POS

forcible

 

IAQ.S

IAQ Level (switch)

Low/High

 

 

IAQIN

 

 

IAQ

IAQ Level (sensor)

xxxx

 

 

IAQ

 

 

OAT

Outdoor Air Temperature

xxx.x

°F

 

OA_TEMP

 

 

ENTH

Outdoor Enthalpy Switch

Low/High

 

 

ENTHALPY

 

 

OAQ

OAQ Level (sensor)

xxxx

 

 

OAQ

 

 

PE.1

Power Exhaust 1 Relay

Off/On

 

 

PE_1

 

 

PE.2

Power Exhaust 2 Relay

Off/On

 

 

PE_2

 

 

OAU

Outside Air Unit Status

 

 

OAUDISP

 

 

 

OA.RN

OAU System Run State

1=AUTO

 

 

OAU_RUN

 

 

 

 

2=OFF

 

 

 

 

 

 

 

3=TEST

 

 

 

 

 

OA.OP

OAU Operating Mode

0=Off

 

 

OAU_MODE

 

 

 

 

1=ERV (DCV)

 

 

 

 

 

 

 

2=Free Cooling

 

 

 

 

 

 

 

3=OA Tempering

 

 

 

 

 

 

 

4=Defrost

 

 

 

 

 

 

 

5=Test

 

 

 

 

 

 

 

6=Ext. Mode 1

 

 

 

 

 

 

 

7=Ext. Mode 2

 

 

 

 

 

 

 

8=Ext. Mode 3

 

 

 

 

 

UPC

UPC Software Version

xxxx

 

 

UPC_VER

 

 

OAU

OA Unit Software Version

xxxx

 

 

OAU_VER

 

 

2P.DM

OAU 2­position Damper

Close/Open

 

 

OAUDMPR

 

 

WHL

OAU Wheel Speed

xxx

%

 

OAUWHEEL

 

 

LAT

OAU Leaving Air Temp

xxx.x

°F

 

OAU_LAT

 

 

EXAT

OAU Exhaust Air Temp

xxx.x

°F

 

OAU_EXAT

 

 

OA.MN

Minimum Outside Air CFM

xxxxx

CFM

 

MINOACFM

 

 

DCV.M

Min DCV Outside Air CFM

xxxxx

CFM

 

MINDCVSP

 

 

OA.FS

OAU OA Fan Speed

xxx

%

 

OAFANSPD

 

 

A.OA

Actual Outside Air CFM

xxxxx

CFM

 

ACTOACFM

 

 

C.OA

Command Outside Air CFM

xxxxx

CFM

 

CMDOACFM

 

 

PE.OF

Power Exhaust CFM Offset

xxxxx

CFM

 

EXOFFSET

 

 

EX.FS

OAU Exhaust Fan Speed

xxx

%

 

OAUPESPD

 

 

A.EX

Actual Exhaust Air CFM

xxxxx

CFM

 

ACTEXCFM

 

 

C.EX

Command Exhaust Air CFM

xxxxx

CFM

 

CMDEXCFM

 

 

BP.SP

Building Pressure Setpnt

x.xx

in H2O

 

OAU_BPSP

 

 

BP

Building Pressure

x.xx

in H2O

 

OAU_BP

 

 

TM.LO

OA Tempring Lockout Temp

xx

°F

 

OATMPLOC

 

 

TM.SP

OA Tempring SAT Setpoint

xx

°F

 

OATMPSPT

 

 

OA.HT

OAU Tempering Heater

xxx

%

 

OAHEATER

 

 

HRS

Component Run Hours

 

 

STRTHOUR

 

 

 

A1

Compressor A1 Run Hours

xxxxx.xx

hours

 

HR_A1

forcible

 

A2

Compressor A2 Run Hours

xxxxx.xx

hours

 

HR_A2

forcible

 

B1

Compressor B1 Run Hours

xxxxx.xx

hours

 

HR_B1

forcible

 

C1

Compressor C1 Run Hours

xxxxx.xx

hours

 

HR_C1

forcible

 

CCH

Crankcase Heat Run Hours

xxxxx.xx

hours

 

HR_CCH

forcible

 

IDF

Indoor Fan Run Hours

xxxxx.xx

hours

 

HR_IDF

forcible

 

OFC.1

Outdoor Fan 1 Run Hours

xxxxx.xx

hours

 

HR_OFC_1

forcible

 

OFC.2

Outdoor Fan 2 Run Hours

xxxxx.xx

hours

 

HR_OFC_2

forcible

 

OFC.3

Outdoor Fan 3 Run Hours

xxxxx.xx

hours

 

HR_OFC_3

forcible

 

HT.1

Heat Stage 1 Run Hours

xxxxx.xx

hours

 

HR_HTR_1

forcible

 

HT.2

Heat Stage 2 Run Hours

xxxxx.xx

hours

 

HR_HTR_2

forcible

 

PE.1

Power Exhaust1 Run Hours

xxxxx.xx

hours

 

HR_PE_1

forcible

 

PE.2

Power Exhaust2 Run Hours

xxxxx.xx

hours

 

HR_PE_2

forcible

 

ALRM

Alarm Relay Run Hours

xxxxx.xx

hours

 

HR_ALM

forcible

 

CRC

Reheat1 Valve Run Hours

xxxxx.xx

hours

 

HR_CRC

forcible

 

RH2.A

Reheat2 Valve A Run Hrs

xxxxx.xx

hours

 

HR_RH2_A

forcible

 

RH2.B

Reheat2 Valve BC Run Hrs

xxxxx.xx

hours

 

HR_RH2_B

forcible

 