Accessory/FIOP Pressure Drop (in. wg) —
AIRFLOW | ELECTRIC | ECONOMIZER | ECONOMIZER | |||
HEAT | (Vertical) | (Horizontal) | SYSTEM | SYSTEM | ||
(CFM) | ||||||
(Sizes 03‐07) | (Sizes 03‐07) | (Sizes 03‐07) | (Sizes 03‐04) | (Sizes 05‐07) | ||
| ||||||
| 0.01 | 0.01 | 0.03 | 0.01 | — | |
| 0.01 | 0.01 | 0.05 | 0.02 | — | |
1000 | 0.02 | 0.02 | 0.07 | 0.03 | — | |
1200 | 0.02 | 0.03 | 0.10 | 0.04 | 0.02 | |
1400 | 0.03 | 0.04 | 0.14 | 0.04 | 0.03 | |
1600 | 0.04 | 0.06 | 0.17 | 0.05 | 0.03 | |
1800 | 0.05 | 0.07 | 0.22 | — | 0.04 | |
2000 | 0.07 | 0.09 | 0.26 | — | 0.04 | |
2200 | 0.08 | 0.11 | 0.31 | — | 0.05 | |
2400 | 0.10 | 0.13 | 0.37 | — | 0.06 | |
2600 | 0.11 | 0.15 | 0.43 | — | 0.06 | |
2800 | 0.13 | 0.18 | 0.49 | — | 0.07 | |
3000 | 0.15 | 0.21 | 0.56 | — | 0.08 |
Accessory/FIOP Pressure Drop (in. wg) —
AIRFLOW | ELECTRIC | ECONOMIZER | ECONOMIZER | |
(CFM) | HEAT | (Vertical) | (Horizontal) | SYSTEM |
2250 | 0.03 | 0.05 | 0.10 | 0.03 |
2650 | 0.05 | 0.06 | 0.13 | 0.03 |
3050 | 0.06 | 0.08 | 0.17 | 0.04 |
3450 | 0.08 | 0.09 | 0.21 | 0.05 |
3850 | 0.10 | 0.10 | 0.26 | 0.06 |
4250 | 0.12 | 0.12 | 0.31 | 0.07 |
4650 | 0.14 | 0.13 | 0.37 | 0.08 |
5050 | 0.17 | 0.15 | 0.44 | 0.09 |
5450 | 0.20 | 0.17 | 0.50 | 0.10 |
5850 | 0.23 | 0.18 | 0.58 | 0.11 |
6250 | 0.26 | 0.20 | 0.66 | 0.12 |
LEGEND
FIOP -
*The static pressure must be added to the external static pressure. The sum and the evaporator