APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
48/50PG and PM
MODE — CONFIGURATION (cont)
ITEM | EXPANSION | RANGE | UNITS | DEFAULT |
ECON | Economizer Configuration |
|
|
|
EC.EN | Economizer Installed | No/Yes |
| No: no FIOP |
|
|
|
| Yes: FIOP |
E.CTL | Economizer Control Type | 1=Dig/Posi |
| 1 |
|
| tion |
|
|
|
| 2=Dig/Com |
|
|
|
| mand |
|
|
|
| 3=Analog |
|
|
|
| Ctrl |
|
|
EC.MN | Econo Minimum Position | 0 to 100 | % | 30 |
|
|
|
| 0: ERV FIOP |
EC.MX | Econo Cool Max Position | 0 to 100 | % | 100 |
M.ANG | Min Actuator Ctrl Angle | 75 to 90 |
| 88 |
EH.LO | Econo Cool Hi Temp Limit | 40 to 100 | °F | 65 |
EL.LO | Econo Cool Lo Temp | 30 to 50 | °F | 0 |
| Limit |
|
|
|
DF.DB | Diff Dry Bulb Control | Disable/En |
| Disable |
|
| able |
|
|
UEFC | Unoccupied Free Cooling | 0=Disabled |
| 2 |
|
| 1=Unoc |
|
|
|
| cpied |
|
|
|
| 2=PreOccu |
|
|
|
| pancy |
|
|
FC.TM | Free Cool PreOcc Time | 1 to 9999 | mins | 120 |
FC.LO | Free Cool Low Temp Limit | 30 to 70 | °F | 50 |
PE.EN | Power Exhaust Installed | No/Yes |
| No: no FIOP |
|
|
|
| Yes: FIOP |
PE.1 | PE Stage1 Econo Position | 0 to 100 | % | 40 |
PE.2 | PE Stage2 Econo Position | 0 to 100 | % | 75 |
EN.SW | Enthalpy Switch | 0=No Switch |
| 0: no FIOP |
|
| 1=Normal |
| 1: FIOP |
|
| Open |
|
|
|
| 2=Normal |
|
|
|
| Closed |
|
|
E.TRV | Economizer Travel Time | 5 to 300 | secs | 150 |
E.MXB | Bottom Stage Max Econo | 0 to 100 | % | 50 |
E.MXM | Middle Stage Max Econo | 0 to 100 | % | 35 |
E.MXT | Top Stage Max Econo | 0 to 100 | % | 25 (PG0316) |
|
|
|
| 0 (2028, PM16) |
AIR.Q | Air Quality Config. |
|
|
|
IA.CF | IAQ Analog Input Config | 0=No IAQ |
| 0: no FIOP |
|
| 1=DCV |
| 1: FIOP |
|
| 2=Override |
|
|
|
| IAQ |
|
|
|
| 3=Ctrl Min |
|
|
|
| Pos |
|
|
IA.FN | IAQ Analog Fan Config | 0=Never |
| 0 |
|
| 1=Occupied |
|
|
|
| 2=Always |
|
|
II.CF | IAQ Switch Input Config | 0=No IAQ |
| 0 |
|
| 1=DCV N/O |
|
|
|
| 2=DCV N/C |
|
|
|
| 3=Override |
|
|
|
| N/O |
|
|
|
| 4=Override |
|
|
|
| N/C |
|
|
II.FN | IAQ Switch Fan Config | 0=Never |
| 0 |
|
| 1=Occupied |
|
|
|
| 2=Always |
|
|
AQ.MN | Econo Min IAQ Position | 0 to 100 | % | 10 |
|
|
|
| 0: ERV FIOP |
EC.MN | Econo Minimum Position | 0 to 100 | % | 30 |
|
|
|
| 0: ERV FIOP |
OVR.P | IAQ Override Position | 0 to 100 | % | 100 |
OA.CF | OAQ Analog Input Config | 0=No OAQ |
| 0 |
|
| 1=DCV |
|
|
|
| 2=Lockout |
|
|
|
| OAQ |
|
|
OAQ.L | OAQ Lockout Limit | 0 to 5000 |
| 600 |
AQD.L | AQ Differential Low | 0 to 5000 |
| 100 |
AQD.H | AQ Differential High | 0 to 5000 |
| 700 |
DF.ON | Fan On AQ Differential | 0 to 5000 |
| 600 |
DF.OF | Fan Off AQ Differential | 0 to 5000 |
| 200 |
I.4M | IAQ Sensor Value at 4mA | 0 to 5000 |
| 0 |
I.20M | IAQ Sensor Value at | 0 to 5000 |
| 2000 |
| 20mA |
|
|
|
O.4M | OAQ Sensor Value at | 0 to 5000 |
| 0 |
| 4mA |
|
|
|
O.20M | OAQ Sensor Value at | 0 to 5000 |
| 2000 |
| 20mA |
|
|
|
H.4M | RH Sensor Value at 4mA | 0 to 50 | % | 0 |
H.20M | RH Sensor Value at 20mA | 60 to 100 | % | 100 |
CCN TABLE/
ECON_CFG
IAQ_CFG
CCN POINT | PAGE NO. |
| 23 |
ECONO | 23 |
ECON_CTL | 14 |
ECONOMIN | 23 |
ECONOMAX | 23 |
MINANGLE | 23 |
OATLECLH | 23 |
OATLECLL | 23 |
DIFFBULB | 23 |
UEFC_CFG | 23 |
UEFCTIME | 23 |
OATLUEFC | 23 |
PE_ENABL | 24 |
PE1_POS | 24 |
PE2_POS | 24 |
ENTHLCFG | 10 |
ECONOTRV | 104 |
ECONMAXB | 104 |
ECONMAXM | 104 |
ECONMAXT | 104 |
| 14 |
IAQANCFG | 14 |
IAQANFAN | 30 |
IAQINCFG | 30 |
IAQINFAN | 34 |
IAQMINP | 30 |
ECONOMIN | 23 |
IAQOVPOS | 30 |
OAQANCFG | 30 |
OAQLOCK | 30 |
DAQ_LOW | 30 |
DAQ_HIGH | 30 |
DAQFNON | 34 |
DAQFNOFF | 34 |
IAQ_4MA | 30 |
IAQ_20MA | 30 |
OAQ_4MA | 33 |
OAQ_20MA | 33 |
RH_4MA | 24 |
RH_20MA | 24 |