Manual background

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

48/50PG and PM

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

ECON

Economizer Configuration

 

 

 

EC.EN

Economizer Installed

No/Yes

 

No: no FIOP

 

 

 

 

Yes: FIOP

E.CTL

Economizer Control Type

1=Dig/Posi­

 

1

 

 

tion

 

 

 

 

2=Dig/Com­

 

 

 

 

mand

 

 

 

 

3=Analog

 

 

 

 

Ctrl

 

 

EC.MN

Econo Minimum Position

0 to 100

%

30

 

 

 

 

0: ERV FIOP

EC.MX

Econo Cool Max Position

0 to 100

%

100

M.ANG

Min Actuator Ctrl Angle

75 to 90

 

88

EH.LO

Econo Cool Hi Temp Limit

40 to 100

°F

65

EL.LO

Econo Cool Lo Temp

­30 to 50

°F

0

 

Limit

 

 

 

DF.DB

Diff Dry Bulb Control

Disable/En­

 

Disable

 

 

able

 

 

UEFC

Unoccupied Free Cooling

0=Disabled

 

2

 

 

1=Unoc­

 

 

 

 

cpied

 

 

 

 

2=PreOccu­

 

 

 

 

pancy

 

 

FC.TM

Free Cool PreOcc Time

1 to 9999

mins

120

FC.LO

Free Cool Low Temp Limit

­30 to 70

°F

50

PE.EN

Power Exhaust Installed

No/Yes

 

No: no FIOP

 

 

 

 

Yes: FIOP

PE.1

PE Stage1 Econo Position

0 to 100

%

40

PE.2

PE Stage2 Econo Position

0 to 100

%

75

EN.SW

Enthalpy Switch

0=No Switch

 

0: no FIOP

 

 

1=Normal

 

1: FIOP

 

 

Open

 

 

 

 

2=Normal

 

 

 

 

Closed

 

 

E.TRV

Economizer Travel Time

5 to 300

secs

150

E.MXB

Bottom Stage Max Econo

0 to 100

%

50

E.MXM

Middle Stage Max Econo

0 to 100

%

35

E.MXT

Top Stage Max Econo

0 to 100

%

25 (PG03­16)

 

 

 

 

0 (20­28, PM16)

AIR.Q

Air Quality Config.

 

 

 

IA.CF

IAQ Analog Input Config

0=No IAQ

 

0: no FIOP

 

 

1=DCV

 

1: FIOP

 

 

2=Override

 

 

 

 

IAQ

 

 

 

 

3=Ctrl Min

 

 

 

 

Pos

 

 

IA.FN

IAQ Analog Fan Config

0=Never

 

0

 

 

1=Occupied

 

 

 

 

2=Always

 

 

II.CF

IAQ Switch Input Config

0=No IAQ

 

0

 

 

1=DCV N/O

 

 

 

 

2=DCV N/C

 

 

 

 

3=Override

 

 

 

 

N/O

 

 

 

 

4=Override

 

 

 

 

N/C

 

 

II.FN

IAQ Switch Fan Config

0=Never

 

0

 

 

1=Occupied

 

 

 

 

2=Always

 

 

AQ.MN

Econo Min IAQ Position

0 to 100

%

10

 

 

 

 

0: ERV FIOP

EC.MN

Econo Minimum Position

0 to 100

%

30

 

 

 

 

0: ERV FIOP

OVR.P

IAQ Override Position

0 to 100

%

100

OA.CF

OAQ Analog Input Config

0=No OAQ

 

0

 

 

1=DCV

 

 

 

 

2=Lockout

 

 

 

 

OAQ

 

 

OAQ.L

OAQ Lockout Limit

0 to 5000

 

600

AQD.L

AQ Differential Low

0 to 5000

 

100

AQD.H

AQ Differential High

0 to 5000

 

700

DF.ON

Fan On AQ Differential

0 to 5000

 

600

DF.OF

Fan Off AQ Differential

0 to 5000

 

200

I.4M

IAQ Sensor Value at 4mA

0 to 5000

 

0

I.20M

IAQ Sensor Value at

0 to 5000

 

2000

 

20mA

 

 

 

O.4M

OAQ Sensor Value at

0 to 5000

 

0

 

4mA

 

 

 

O.20M

OAQ Sensor Value at

0 to 5000

 

2000

 

20mA

 

 

 

H.4M

RH Sensor Value at 4mA

0 to 50

%

0

H.20M

RH Sensor Value at 20mA

60 to 100

%

100

CCN TABLE/ SUB-TABLE

ECON_CFG

IAQ_CFG

CCN POINT

PAGE NO.

 

23

ECONO

23

ECON_CTL

14

ECONOMIN

23

ECONOMAX

23

MINANGLE

23

OATLECLH

23

OATLECLL

23

DIFFBULB

23

UEFC_CFG

23

UEFCTIME

23

OATLUEFC

23

PE_ENABL

24

PE1_POS

24

PE2_POS

24

ENTHLCFG

10

ECONOTRV

104

ECONMAXB

104

ECONMAXM

104

ECONMAXT

104

 

14

IAQANCFG

14

IAQANFAN

30

IAQINCFG

30

IAQINFAN

34

IAQMINP

30

ECONOMIN

23

IAQOVPOS

30

OAQANCFG

30

OAQLOCK

30

DAQ_LOW

30

DAQ_HIGH

30

DAQFNON

34

DAQFNOFF

34

IAQ_4MA

30

IAQ_20MA

30

OAQ_4MA

33

OAQ_20MA

33

RH_4MA

24

RH_20MA

24

104

Page 104
Image 104
Carrier 48/50PG C03-14 Appendix A — Local Display And Ccn Tables Cont, MODE — CONFIGURATION cont, 48/50PG and PM, Item