Fan Performance — 48PGD05 Vertical Units

AIRFLOW

 

0.2

(Cfm)

 

Rpm

Bhp

 

Fan Performance — 48PGD05 Vertical Units

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

0.4

 

0.6

0.8

 

 

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

504

0.16

1300

527

0.19

1400

551

0.22

1500

576

0.26

1600

600

0.30

1700

626

0.35

1800

651

0.40

1900

677

0.46

2000

703

0.52

613

0.23

710

0.31

632

0.27

725

0.35

652

0.31

741

0.40

673

0.35

759

0.44

694

0.40

777

0.50

716

0.45

797

0.55

739

0.51

817

0.62

762

0.57

838

0.69

785

0.64

859

0.76

798

0.40

881

0.49

810

0.44

890

0.54

823

0.49

900

0.59

838

0.54

912

0.65

854

0.60

926

0.71

871

0.66

941

0.78

889

0.73

957

0.85

908

0.80

974

0.93

927

0.88

992

1.01

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

 

1.2

(Cfm)

 

Rpm

Bhp

 

1200

 

0.59

1300

 

0.64

1400

 

0.70

1500

 

0.76

1600

 

0.82

1700

1007

0.89

1800

1021

0.97

1900

1037

1.05

2000

1053

1.14

LEGEND

1.4

Rpm Bhp

1030 0.70

1035 0.75

1042 0.81

1050 0.87

1060 0.94

1071 1.02

1083 1.10

1097 1.18

1111 1.27

 

1.6

 

1.8

 

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1098

0.80

1163

0.91

1225

1.03

1102

0.86

1166

0.98

1227

1.10

1107

0.92

1170

1.04

1231

1.17

1114

0.99

1176

1.12

1235

1.24

1122

1.06

1183

1.19

1241

1.32

1132

1.14

1191

1.27

1248

1.41

1143

1.23

1200

1.36

1256

1.50

1155

1.32

1211

1.45

1266

1.60

1168

1.41

1223

1.55

1276

1.70

NOTES:

48/50PG and PM

Bhp - Brake Horsepower

High Range Motor/Drive Required

1.Motor drive range is 596 to 910 rpm for low range motor/drive and 828 to 1173 rpm for high range motor/drive. All other rpms require a field‐supplied drive.

2.Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase) for high range motor/drive.

3.See General Fan Performance Notes.

AIRFLOW

 

0.2

(Cfm)

 

Rpm

Bhp

 

1200

509

0.16

1300

533

0.19

1400

557

0.23

1500

582

0.27

1600

608

0.31

1700

634

0.36

1800

660

0.41

1900

686

0.47

2000

713

0.54

AIRFLOW

 

1.2

(Cfm)

 

 

 

Fan Performance − 48PGE05 Vertical Units

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

0.4

 

0.6

0.8

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

618

0.24

714

0.32

802

0.41

637

0.27

730

0.36

814

0.45

658

0.31

746

0.40

828

0.50

679

0.36

764

0.45

843

0.55

701

0.40

783

0.50

860

0.61

723

0.46

803

0.56

877

0.67

747

0.52

824

0.63

896

0.74

770

0.58

846

0.70

915

0.82

795

0.66

868

0.78

935

0.90

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

1.4

 

1.6

1.8

 

 

1.0

Rpm

Bhp

884

0.50

894

0.55

905

0.60

917

0.66

931

0.72

947

0.79

963

0.86

981

0.94

999

1.02

2.0

 

Rpm

Bhp

1200

 

0.60

1300

 

0.65

1400

 

0.70

1500

 

0.77

1600

 

0.83

1700

1013

0.90

1800

1027

0.98

1900

1043

1.06

2000

1060

1.16

Rpm Bhp

1033 0.70

1039 0.76

1046 0.82

1054 0.88

1065 0.95

1076 1.03

1089 1.11

1103 1.20

1118 1.29

Rpm

Bhp

Rpm

Bhp

1101

0.81

1166

0.92

1106

0.87

1169

0.98

1111

0.93

1174

1.05

1118

1.00

1180

1.12

1127

1.07

1187

1.20

1137

1.15

1196

1.28

1148

1.24

1206

1.37

1161

1.33

1217

1.47

1175

1.43

1229

1.57

Rpm

Bhp

1228

1.03

1230

1.10

1234

1.17

1239

1.25

1245

1.33

1253

1.42

1261

1.51

1271

1.61

1282

1.72

LEGEND

Bhp - Brake Horsepower

High Range Motor/Drive Required

NOTES:

1.Motor drive range is 596 to 910 rpm for low range motor/drive and 828 to 1173 rpm for high range motor/drive. All other rpms require a field‐supplied drive.

2.Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.

3.See General Fan Performance Notes.