48/50PG and PM
Table 23 – MBB Connections
DISPLAY | POINT DESCRIPTION | SENSOR LOCATION | TYPE OF I/O | CONNECTION | |
NAME | PIN NUMBER | ||||
|
|
| |||
|
| INPUTS |
|
| |
| Input power from TRAN1 | control box | 24 VAC | J1, | |
HUM | IGC Fan Request or | gas section / | switch input | J6, 4 | |
Humidistat switch input | space | ||||
|
|
| |||
FDWN | Fire shutdown switch | supply/return/space | switch input | J6, 6 | |
G | Thermostat G (Fan) | space | switch input | J7, 2 | |
W2 | Thermostat W2 (2nd Stage Heat) | space | switch input | J7, 4 | |
W1 | Thermostat W1 (1st Stage Heat) | space | switch input | J7, 6 | |
Y2 | Thermostat Y2 (2nd Stage Cool) | space | switch input | J7, 8 | |
Y1 | Thermostat Y1 (1st Stage Cool) | space | switch input | J7, 10 | |
FIL.S | Filter status switch | indoor fan section | switch input | J9, | |
CS.A1 | Compressor A1 Current Sensor | control box | J9, | ||
CS.B1 or | Compressor B1 or | control box | J9, | ||
CS.A2 | A2 Current Sensor | ||||
|
|
| |||
CS.C1 or | Compressor C1or | control box | J9, | ||
CS.B1 | B1 Current Sensor | ||||
|
|
| |||
SPT | Space temperature (T55/56) | space | 10k thermistor | J8, | |
SPTO or | Space temperature offset (T56) or | space or return | 10k thermistor | J8, | |
RAT | Return air temperature | ||||
|
|
| |||
OAT | Outdoor air temperature | outdoor coil support | 10k thermistor | J8, | |
SAT | Supply air temperature | indoor fan housing, or | 10k thermistor | J8, | |
supply duct | |||||
|
|
|
| ||
SCT.A | Saturated condenser temperature, circuit A | outdoor coil, circuit A | 5k thermistor | J8, | |
SCT.B | Saturated condenser temperature, circuit B | outdoor coil, circuit B | 5k thermistor | J8, | |
SCT.C | Saturated condenser temperature, circuit C | outdoor coil, circuit C | 5k thermistor | J8, | |
FAN.S | Fan status switch | indoor fan section | switch input | J8, | |
SSP.A | Suction pressure, circuit A | compressor A suction | J8, | ||
transducer | |||||
|
|
|
| ||
SSP.B | Suction pressure, circuit B | compressor B suction | J8, | ||
transducer | |||||
|
|
|
| ||
SSP.C | Suction pressure, circuit C | compressor C suction | J8, | ||
transducer | |||||
|
|
|
|
OUTPUTS
CRC | Cooling Reheat Control |
CMP.C or | Compressor C1 relay or |
OFC.2 | Outdoor fan 2 relay |
COMP.B | Compressor B1 relay |
COMP.A | Compressor A1 relay |
CCH or | Crankcase heat relay or |
OFC.3 | Outdoor fan 3 relay or |
OFC.1 | Outdoor fan 1 relay |
OFC.2 or | Outdoor fan 2 relay or |
RH2.B | Reheat 2 valve circuit B & C |
OFC.1 or | Outdoor fan 1 relay or |
RH2.A | Reheat 2 valve circuit A |
IDF | Indoor fan relay |
ALRM | Alarm relay |
HT.1 | Heat Stage 2 relay |
HT.2 | Heat Stage 1 relay |
COMMUNICATION
relay | J10, 3 |
relay | J10, 6 |
relay | J10, 9 |
relay | J10, 11 |
relay | J10, 13 |
relay | J10, 16 |
relay | J10, 19 |
relay | J10, 21 |
relay | J10, 23 |
relay | J10, 25 |
relay | J10, 27 |
Local Equipment Network (LEN) | communication | J5, |
Carrier Comfort Network (CCN) | communication | J5, |
Network device power | 24 VAC | J5, |
Scrolling Marquee Display (LEN) | communication | J4, |
Scrolling Marquee Display power | 24 VAC | J4, |
Optional ECB (LEN) | communication | J3, |
Optional ECB power | 24 VAC | J2, |