CONTROL SET POINT AND CONFIGURATION LOG
Model Number: _____________________________ | Software Versions: ___________________________ |
Serial Number: ______________________________ | MBB: CESR131320−− _ _ |
Date: ______________________________________ | ECB: CESR131249−− _ _ |
Technician: _________________________________ | MARQ: CESR131171−− _ _ |
INDICATE UNIT SETTINGS BELOW
Control Type: | Thermostat/T55 Space Temp./T−56 Space Temp./T−58 Space Temp. | ||
Set Points: | Cooling | Occupied: _______________ | Unoccupied: __________________ |
| Heating | Occupied: _______________ | Unoccupied: __________________ |
MODE — CONFIGURATION
48/50PG and PM
ITEM | EXPANSION | RANGE | UNITS | DEFAULT |
CONFIGURATION |
|
|
|
|
DISP | Display Configuration |
|
|
|
METR | Metric Display | Off/On |
| Off |
LANG | Language Selection | 0=English |
| 0 |
|
| 1=Spanish |
|
|
|
| 2=French |
|
|
|
| 3=Portuguese |
|
|
PROT | Password Enable | Disable/Enable |
| Enable |
PSWD | Service Password | 0000 to 9999 |
| 1111 |
TEST | Test Display LEDs | Off/On |
| Off |
UNIT | Unit Configuration |
|
|
|
S.DLY | Startup Delay | 10 to 600 | sec | 30 |
U.CTL | Unit Control Type | 2=Thermostat |
| 2 |
|
| 3=Space |
|
|
|
| Sensor |
|
|
T.CTL | Thermostat Control Type | 0=Adaptive |
| 0 |
|
| 1=1 Stage Y1 |
|
|
|
| 2=2 Stage Y1 |
|
|
|
| 3=Digital |
|
|
OC.FN | Fan On When Occupied | No/Yes |
| Yes |
IDF.F | Shut Down on IDF Failure | No/Yes |
| Yes |
FN.SW | Fan Status Switch | 0=No Switch |
| 0: no FIOP |
|
| 1=Normal |
| 1: FIOP |
|
| Open |
|
|
|
| 2=Normal |
|
|
|
| Closed |
|
|
FL.SW | Filter Status Switch | 0=No Switch |
| 0: no FIOP |
|
| 1=Normal |
| 1: FIOP |
|
| Open |
|
|
|
| 2=Normal |
|
|
|
| Closed |
|
|
FS.SW | Fire Shutdown Switch | 0=No Switch |
| 0: no FIOP |
|
| 1=Normal |
| 1: FIOP |
|
| Open |
|
|
|
| 2=Normal |
|
|
|
| Closed |
|
|
RM.SW | Remote Occupancy | 0=No Switch |
| 0 |
| Switch | 1=Normal |
|
|
|
| Open |
|
|
|
| 2=Normal |
|
|
|
| Closed |
|
|
SAT.T | SAT Settling Time | 10 to 900 | sec | 240 |
RAT.S | RAT Sensor on SPTO In | No/Yes |
| No |
| put |
|
|
|
RH.S | RH Sensor on OAQ Input | No/Yes |
| No |
RH.SW | Space Humidity Switch | 0=No Switch |
| 0: no HumidiMiZer |
|
| 1=Normal |
| FIOP |
|
| Open |
| 1: HumidiMiZer |
|
| 2=Normal |
| FIOP |
|
| Closed |
|
|
TCS.C | Temp Cmp Strt Cool | 0 to 60 | mins | 0 |
| Factr |
|
|
|
TCS.H | Temp Cmp Strt Heat | 0 to 60 | mins | 0 |
| Factr |
|
|
|
CCN TABLE/
SERVICE CONFIGURATION
DISPLAY
(display only, not in table)
UNIT
CCN POINT | PAGE NO. |
14
14
DISPUNIT 14
LANGUAGE 14
PASS_EBL 14
PASSWORD 14
DISPTEST 14
14
STARTDLY 14
CTL_TYPE 14
STATTYPE 15
OCC_FAN 15
FATALFAN 15
FANSTCFG 15
FILSTCFG 15
SHTDNCFG 15
REMOCCFG 15
SAT_SET 15
RAT_SPTO 15
RH_OAQ 15
HUMSTCFG 15
TCSTCOOL 15
TCSTHEAT 15
180