Carrier 48/50PG C03-14, 48/50PM C16-28 manual ECB Connections, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 74
Image 74
Table 24 – ECB Connections

48/50PG and PM

Table 24 – ECB Connections

DISPLAY

POINT DESCRIPTION

SENSOR

TYPE OF I/O

CONNECTION

NAME

 

LOCATION

 

PIN NUMBER

 

 

INPUTS

 

 

 

Input power from MBB

control box

24 VAC

J1, 1-2

RM.OC

Remote occupancy switch

field installed

switch input

J4, 2

ENTH or

Outdoor enthalpy switch, or

economizer, or

switch input

J4, 4

IAQ.S

Indoor air quality switch

return/space

 

 

IAQ

Indoor air quality sensor

return/space

0-20 mA

J5, 2

OAQ or

Outdoor air quality sensor, or

field installed

0-20 mA

J5, 5

SP.RH

Relative humidity sensor

 

 

 

 

Sensor Common

 

Ground

J5, 3

 

Actuator Common

 

Ground

J7, 3

 

 

OUTPUTS

 

 

 

Output power to enthalpy switch

 

24 VAC

J4, 3

 

Output power for loop power sensors

 

24 VDC

J5, 1

 

Output power to economizer actuator

 

24 VAC

J7, 2

PE.1

Power exhaust 1 relay

 

relay

J8, 3

PE.2

Power exhaust 2 relay

 

relay

J8, 6

EC.CP or

Commanded Economizer position or

 

0-20 mA

J9, 1

F.SPD

Commanded Fan Speed

 

 

 

 

 

COMMUNICATION

 

 

 

Local Equipment Network (LEN)

 

communication

J2, 1-3

 

Carrier Comfort Network (CCN)

 

communication

J3

EC.CP &

Economizer actuator position

 

MFT

J7, 1

EC.AP

(digital control)

 

communication

 

74

Page 74
Image 74