APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — RUN STATUS (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/

CCN POINT

CCN

MENU

 

 

 

 

SUB­TABLE

 

WRITE

WRITE

 

 

 

 

 

 

STATUS

STATUS

STRT

Component Starts

 

 

 

 

 

 

A1

Compressor A1 Starts

xxxxxx

 

 

ST_A1

forcible

 

A2

Compressor A2 Starts

xxxxxx

 

 

ST_A2

forcible

 

B1

Compressor B1 Starts

xxxxxx

 

 

ST_B1

forcible

 

C1

Compressor C1 Starts

xxxxxx

 

 

ST_C1

forcible

 

CCH

Crankcase Heat Starts

xxxxxx

 

 

ST_CCH

forcible

 

IDF

Indoor Fan Starts

xxxxxx

 

 

ST_IDF

forcible

 

OFC.1

Outdoor Fan 1 Starts

xxxxxx

 

 

ST_OFC_1

forcible

 

OFC.2

Outdoor Fan 2 Starts

xxxxxx

 

 

ST_OFC_2

forcible

 

OFC.3

Outdoor Fan 3 Starts

xxxxxx

 

 

ST_OFC_3

forcible

 

HT.1

Heat Stage 1 Starts

xxxxxx

 

 

ST_HTR_1

forcible

 

HT.2

Heat Stage 2 Starts

xxxxxx

 

 

ST_HTR_2

forcible

 

PE.1

Power Exhaust 1 Starts

xxxxxx

 

 

ST_PE_1

forcible

 

PE.2

Power Exhaust 2 Starts

xxxxxx

 

 

ST_PE_2

forcible

 

ALRM

Alarm Relay Starts

xxxxxx

 

 

ST_ALM

forcible

 

CRC

Reheat1 Valve Starts

xxxxxx

 

 

ST_CRC

forcible

 

RH2.A

Reheat2 Valve A Starts

xxxxxx

 

 

ST_RH2_A

forcible

 

RH2.B

Reheat2 Valve BC Starts

xxxxxx

 

 

ST_RH2_B

forcible

 

(ALRMDISP) =

 

 

 

ALRMDISP

 

 

 

CCN only)

 

 

 

 

 

 

 

 

Active Alarm 1 Code

xxx

 

 

ALMCODE1

 

 

 

Active Alarm 2 Code

xxx

 

 

ALMCODE2

 

 

 

Active Alarm 3 Code

xxx

 

 

ALMCODE3

 

 

 

Active Alarm 4 Code

xxx

 

 

ALMCODE4

 

 

 

Active Alarm 5 Code

xxx

 

 

ALMCODE5

 

 

 

Reset All Current Alarms

No/Yes

 

 

ALRESET

forcible

 

 

Reset Alarm History

No/Yes

 

 

ALHISCLR

forcible

 

(GENERIC =

 

 

 

GENERIC

 

 

 

CCN only)

 

 

 

 

 

 

 

 

 

 

 

 

up to 20 points

 

 

(LON_DATA =

 

 

 

LON_DATA

 

 

 

CCN only)

 

 

 

 

 

 

 

 

nviSpaceTemp

xxx.x

°F

 

NVI_SPT

Forcible

 

 

nviSetPoint

xxx.x

°F

 

NVI_SP

forcible

 

 

nvoSpaceTemp

xxx.x

°F

 

NVO_SPT

 

 

 

nvoUnitStatus.mode

xxxx

 

 

NVO_MODE

 

 

 

nvoUnitStatus.heat_out_p

xxx.x

%

 

NVO_HPRI

 

 

 

nvoUnitStatus.heat_out_s

xxx.x

%

 

NVO_HSEC

 

 

 

nvoUnitStatus.cool_out

xxx.x

%

 

NVO_COOL

 

 

 

nvoUnitStatus.econ_out

xxx.x

%

 

NVO_ECON

 

 

 

nvoUnitStatus.fan_out

xxx

%

 

NVO_FAN

 

 

 

nvoUnitStatus.in_alarm

xxx

 

 

NVO_ALRM

 

 

 

nviSetPtOffset

xxx.x

^F

 

NVI_SPTO

forcible

 

 

nviOutsideTemp

xxx.x

°F

 

NVI_OAT

forcible

 

 

nviOutsideRH

xxxx.x

%

 

NVI_OARH

forcible

 

 

nvoEffectSetPt

xxx.x

°F

 

NVO_EFSP

 

 

 

nvoOutsideTemp

xxxx.x

°F

 

NVO_OAT

 

 

 

nvoOutsideRH

xxx.x

%

 

NVO_OARH

 

 

 

nviSpaceRH

xxx.x

%

 

NVI_SPRH

forcible

 

 

nviCO2

xxxxx

 

 

NVI_CO2

forcible

 

 

nvoCO2

xxxxx

 

 

NVO_CO2

 

 

 

nvoTEMP1

xxx.x

°F

 

NVO_SAT

 

 

 

nvoTEMP2

xxx.x

°F

 

NVO_RAT

 

 

 

nviPCT1

xxx.x

%

 

NVI_RHSP

forcible

 

 

nvoPCT1

xxx.x

%

 

NVO_SPRH

 

 

 

nviDISCRETE1

Off/On

 

 

NVI_FSD

forcible

 

 

nviDISCRETE2

No/Yes

 

 

NVI_OCC

forcible

 

 

nviDISCRETE3

Off/On

 

 

NVI_IAQD

forcible

 

 

nvoDISCRETE1

Off/On

 

 

NVO_FSD

 

 

 

nvoDISCRETE2

No/Yes

 

 

NVO_OCC

 

 

 

nvoDISCRETE3

Off/On

 

 

NVO_IAQD

 

 

 

nciCO2Limit

xxxxx

 

 

NCI_CO2

forcible

 

 

nciSetPnts.occupied_cool

xxx.x

°F

 

NCI_OCSP

forcible

 

 

nciSetPnts.standby_cool

xxx.x

°F

 

NCI_SCSP

forcible

 

 

nciSetPnts.unoccupd_cool

xxx.x

°F

 

NCI_UCSP

forcible

 

 

nciSetPnts.occupied_heat

xxx.x

°F

 

NCI_OHSP

forcible

 

 

nciSetPnts.standby_heat

xxx.x

°F

 

NCI_SHSP

forcible

 

 

nciSetPnts.unoccupd_heat

xxx.x

°F

 

NCI_UHSP

forcible

 