APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION (cont)
ITEM | EXPANSION | RANGE | UNITS | DEFAULT |
OAU | Outside Air Unit Config |
|
|
|
OA.TY | Outdoor Air Unit Type | 0=No OAU |
| 0: no FIOP |
|
| 1=ERV Module |
| 1: FIOP EXv2 |
|
| 2=Economizer |
|
|
|
| 3=Pwr Exhaust |
|
|
|
| 4=OA Monitor |
|
|
|
| 5=100% OA |
|
|
|
| Unit |
|
|
|
| 6=EXv1 ERV |
|
|
OA.FC | Outside Air Fan Curve | 0 to 999 |
| 0: no FIOP |
|
|
|
| 1: PG0307 1ph low |
|
|
|
| CFM ERV |
|
|
|
| 2: PG0307 3ph low |
|
|
|
| CFM ERV |
|
|
|
| 3: PG0307 1ph high |
|
|
|
| CFM ERV |
|
|
|
| 4: PG0307 3ph high |
|
|
|
| CFM ERV |
|
|
|
| 5: PG0814 low CFM |
|
|
|
| ERV |
|
|
|
| 6: PG0814 high CFM |
|
|
|
| ERV |
|
|
|
| 7: PM1624 low CFM |
|
|
|
| ERV |
|
|
|
| 8: PM1624 high CFM |
|
|
|
| ERV |
|
|
|
| 9: PM28 low CFM ERV |
|
|
|
| 10: PM28 high CFM |
|
|
|
| ERV |
PE.FC | Exhaust Air Fan Curve | 0 to 999 |
| 0: no FIOP |
|
|
|
| 1: PG0306 1ph low |
|
|
|
| CFM ERV |
|
|
|
| 2: PG0307 3ph low |
|
|
|
| CFM ERV |
|
|
|
| 3: PG0306 1ph high |
|
|
|
| CFM ERV |
|
|
|
| 4: PG0307 3ph high |
|
|
|
| CFM ERV |
|
|
|
| 5: PG0814 low CFM |
|
|
|
| ERV |
|
|
|
| 6: PG0814 high CFM |
|
|
|
| ERV |
|
|
|
| 7: PM1624 low CFM |
|
|
|
| ERV |
|
|
|
| 8: PM1624 high CFM |
|
|
|
| ERV |
|
|
|
| 9: PM28 low CFM |
|
|
|
| ERV |
|
|
|
| 10: PM28 high CFM |
|
|
|
| ERV |
U.RUN | OAU Unoccupied Operation | No/Yes |
| NO |
OAU.F | Shut Down on Fan Failure | No/Yes |
| Yes |
M.WHL | Modulating Wheel Install | No/Yes |
| NO |
OA.MN | Minimum Outside Air | 0 to 32000 | CFM | 375: PG0307 low |
| CFM |
|
| CFM ERV |
|
|
|
| 800: PG0307 high |
|
|
|
| CFM ERV |
|
|
|
| 1000: PG0814 low |
|
|
|
| CFM ERV |
|
|
|
| 2500: PG0814 high |
|
|
|
| CFM ERV |
|
|
|
| 3000: PM1628 low |
|
|
|
| CFM ERV |
|
|
|
| 4000: PM1624 high |
|
|
|
| CFM ERV |
|
|
|
| 5000: PM28 high |
|
|
|
| CFM ERV |
DCV.M | Min DCV Outside Air CFM | 0 to 32000 | CFM | 100: PG0307 ERV |
|
|
|
| 250: PG0814 low |
|
|
|
| CFM ERV |
|
|
|
| 600: PG0814 high |
|
|
|
| CFM ERV |
|
|
|
| 1000: PM1624 low |
|
|
|
| CFM ERV |
|
|
|
| 1500: PM1624 high |
|
|
|
| CFM ERV, PM28 low |
|
|
|
| CFM ERV |
|
|
|
| 2000: PM28 high |
|
|
|
| CFM ERV |
PEX.C | Power Exhaust Control | 0=Offset CFM |
| 0 |
|
| 1=BP |
|
|
PE.OF | Power Exhaust CFM Offset | 17000 to | CFM | 200 |
|
| 17000 |
|
|
BP.SP | Building Pressure Setpnt | 0.25 to 0.25 | in H2O | 0.05 |
OA.TM | Outside Air Tempering | Disable/Enable |
| Disable |
TM.LO | OA Tempring Lockout Temp | 0 to 80 | °F | 60 |
TM.SP | OA Tempring SAT Setpoint | 35 to 80 | °F | 55 |
OAC.K | Outside Air CFM k Factor | 0.8 to 1.2 |
| 1.0 |
EXC.K | Exhaust Air CFM k Factor | 0.8 to 1.2 |
| 1.0 |
CCN TABLE/
OAU_CFG
CCN POINT | PAGE NO. |
12
OAU_TYPE40
OAFANCRV 105
PEFANCRV 105
UNOCCRUN | 105 |
FATALOAU | 105 |
MODWHEEL | 105 |
MINOACFM | 95 |
MINDCVSP95
PEX_CTL105
EXOFFSET95
OAU_BPSP95
OATEMPER 95
OATMPLOC 95
OATMPSPT95
OACFM_K105
EXCFM_K105
48/50PG and PM
105