Carrier 48/50PM C16-28 Appendix A — Local Display And Ccn Tables Cont, MODE — CONFIGURATION cont

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 103
Image 103
Manual background

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

 

DEFAULT

COOL (cont)

Cooling Configuration

 

 

 

 

3.ON

Fan Lev3 On Temperature

0 to 100

°F

no Humidi­MiZer FIOP:

 

 

 

 

65

 

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

88

(20, PM16)

 

 

 

 

68

(24­28)(PG03­16)

3.OFF

Fan Lev3 Off Temperature

0 to 100

°F

no Humidi­MiZer FIOP:

 

 

 

 

55

 

 

 

 

 

Humidi­MiZer FIOP:

 

 

 

 

78

(20, PM16)

 

 

 

 

62

(24­28)(PG03­16)

HMZR

Humidimizer Config

 

 

 

 

REHT

Humidimizer Equipped

No/Yes

 

No: no Humidi­MiZer

 

 

 

 

FIOP

 

 

 

 

Yes: Humidi­MiZer FIOP

R.DEC

Reheat2 Stage Decr.

0 to 999

secs

60

 

 

Time

 

 

 

 

R.INC

Reheat2 Stage Incr. Time

0 to 999

secs

300

RH.FN

Reheat Fan Control

No/Yes

 

No (03­14)

 

 

 

 

Yes (16­28)

RF.LV

Reheat ODF Fan On

0 to 3

 

2 (03­20)

 

Level

 

 

3 (24­28)

RF. ON

Reheat ODF Fan On

0 to 100

°F

75

(PG03­16)

 

Temp

 

 

93

(PG20­24)(PM16­28)

 

 

 

 

85

(PG 28)

RF.OF

Reheat ODF Fan Off

0 to 100

°F

70

(PG03­16)

 

Temp

 

 

83

(20, PM16)

 

 

 

 

88

(24)(PM 28)

 

 

 

 

80

(PG 28)

RA.LO

Reheat2 OAT Limit A

20 to 70

°F

40

 

RA.LP

Reheat2 SSP Lo Limit A

50 to 100

psig

80

 

RA.HP

Reheat2 SSP Hi Limit A

50 to 100

psig

90

 

RB.LO

Reheat2 OAT Limit B,C

20 to 70

°F

50

 

RB.LP

Reheat2 SSP Lo Limit

50 to 100

psig

80

 

 

B,C

 

 

 

 

RB.HP

Reheat2 SSP Hi Limit B,C

50 to 100

psig

90

 

HEAT

Heating Configuration

 

 

 

 

HT.TY

Type of Heat Installed

0=No Heat

 

0 (50 series with no elec­

 

 

1=Gas

 

tric heat)

 

 

2=Electric

 

1 (48 series)

 

 

 

 

2 (50 series with electric

 

 

 

 

heat)

N.HTR

Number of Heat Stages

1 to 2

 

1 (48 series 1­phase, 50

 

 

 

 

series <15kW)

 

 

 

 

2 (48 series 3­phase, 50

 

 

 

 

series >=15kW)

MRT.H

Heat Minimum On Time

60 to 999

sec

120

MOT.H

Heat Minimum Off Time

60 to 999

sec

120

H.DEC

Heat Stage Decrease

120 to 999

sec

300

 

Time

 

 

 

 

H.INC

Heat Stage Increase

120 to 999

sec

450

 

Time

 

 

 

 

FOD.E

Fan­off Delay, Elect Heat

10 to 600

sec

30

 

FOD.G

Fan­off Delay, Gas Heat

45 to 600

sec

45

 

HT.LO

Heating Lockout Temp

40 to 125

°F

75

 

SAT

 

 

 

 

 

SAT.H

SAT Heat Mode Sensing

Disable/En­

 

Disable

 

 

able

 

 

 

SAM.L

Maximum SAT Lower

85 to 200

°F

140

 

Level

 

 

 

 

SAM.U

Maximum SAT Upper

85 to 200

°F

160

 

Level

 

 

 

 

SPT

Space Temperature

 

 

 

 

HT.PD

SPT Heat Demand (+)

0.5 to 5

^F

1

 

 

Level

 

 

 

 

HT.ND

SPT Heat Demand (­)

­5 to ­0.5

^F

­1

 

 

Level

 

 

 

 

H.LAG

Heat Thermal Lag Factor

0 to 5

 

1

 

CCN TABLE/ SUB-TABLE

COOL_CFG

HMZR_CFG

HEAT_CFG

CCN POINT

PAGE NO.

15

LEV3ON

LEV3OFF

 

 

24

REHEAT

24

RSTAGDEC

28

RSTAGINC

28

RHFANCTL

28

RHFANLEV

28

RHFANON

28

RHFANOFF

28

OATLRH_A

28

RHSSPL_A

28

RHSSPH_A

28

OATLRH_B

28

RHSSPL_B

28

RHSSPH_B

28

 

15

HEATTYPE

21

NUM_HEAT

22

HMIN_ON

22

HMIN_OFF

22

HSTAGDEC

21

HSTAGINC

21

ELEC_FOD

17

GAS_FOD

17

OATLHEAT

21

 

15

SAT_HEAT

16

SATMAX_L

SATMAX_H

16

HDEM_POS

HDEM_NEG

HEAT_LAG

48/50PG and PM