ROLLOUT | INDUCED |
SWITCH | DRAFT |
| MOTOR |
| COMBUSTION |
| FAN HOUSING |
| MAIN GAS |
| VALVE |
HEAT EXCHANGER | MAIN BURNER SECTION |
SECTION | |
| C07037 |
Fig. 50 − 48PG03−14 Typical Gas Heating Section
(48PG03−07 Shown)
COMBUSTION
FAN HOUSING
HEAT | INDUCED | |
EXCHANGER | ||
DRAFT | ||
SECTION | ||
MOTOR | ||
|
MAIN GAS
IGC BOARD VALVE (HIDDEN)
MAIN BURNER
SECTION
C07259
Fig. 51 − 48PM16−28
Typical Gas Heating Section
Condenser and Evaporator−Fan Motor Bearings
The
Economizer or Manual Outside Air Damper
If blade adjustment is required, refer to unit or accessory installation instructions.
Evaporator Fan Service and Replacement
The units feature a
1.Turn off unit power.
2.Open the fan section access door.
3.Remove two no. 10 screws at front of
4.For 48/50PG03−14 units, disconnect the electrical wires connected to the slide−out fan deck (supply air thermistor and fan status switch if installed). Wires may be damaged if not disconnected. For 48/50PM16−28 units, disconnect the limit switch wires located on the right side of the fan deck (48 series only). Other wires do not need to be disconnected.
5.Fan deck can now be slid out to access serviceable components.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit.
DO NOT SLIDE FAN DECK OUT PAST THE FAN DECK STOP. If further access is required, the fan deck must be supported. Make sure plugs and wiring are not pinched between fan housing and unit sheet metal post.
6.To replace fan deck to operating position, slide fan deck back into the unit. Secure with the two no. 10 screws removed in Step 3.
7.
8.Close fan section access door.
9.Restore power to unit.
FAN DECK STOP
MOTOR
MOUNTING
BASE
SCREW (HIDDEN)
FAN
MOTOR PULLEY
PULLEY
SCREW
FAN DECK
C06177
Fig. 52 − 48/50PG03−14
Evaporator−Fan Motor Adjustment
| MOTOR | |
FAN | PULLEY | |
(HIDDEN) | ||
PULLEY | ||
| ||
| MOTOR | |
LIMIT | MOUNTING | |
BASE | ||
SWITCH | ||
| ||
QUICK | ||
CONNECT | ||
(48PM ONLY) | FAN DECK | |
|
C08008
Fig. 53 − 48/50PM16−28
Evaporator−Fan Motor Adjustment
48/50PG and PM
85