Evaporator Fan Motor Specifications − 50PM16−28 (cont)
UNIT | DRIVE | ORIENTATION | VOLTAGE | EFFICIENCY | MAX BHP | MAX AMPS | |
50PM | (%) | ||||||
|
|
|
|
| |||
|
|
| 208 | 85.8 |
| 10.6 | |
| Low | Vertical | 230 | 85.8 |
|
| |
| 460 | 85.8 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 87.5 |
| 15.8 | |
| Mid‐Low | Vertical | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 88.5 |
| 22.0 | |
| Mid‐High | Vertical | 230 | 88.5 |
| 22.0 | |
| 460 | 88.5 |
| 11.6 | |||
|
|
|
| ||||
|
|
| 575 | 88.5 |
|
| |
|
|
| 208 | 89.5 |
| 28.0 | |
| High | Vertical | 230 | 89.5 | 10.45 | 28.0 | |
| 460 | 89.5 | 11.19 | 15.0 | |||
|
|
| |||||
24 |
|
| 575 | 89.5 | 11.50 | 12.0 | |
|
| 208 | 85.8 |
| 10.6 | ||
|
|
|
| ||||
| Low | Horizontal | 230 | 85.8 |
|
| |
| 460 | 85.8 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 87.5 |
| 15.8 | |
| Mid‐Low | Horizontal | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 88.5 |
| 22.0 | |
| Mid‐High | Horizontal | 230 | 88.5 |
| 22.0 | |
| 460 | 88.5 |
| 11.6 | |||
|
|
|
| ||||
|
|
| 575 | 88.5 |
|
| |
|
|
| 208 | 89.5 |
| 28.0 | |
| High | Horizontal | 230 | 89.5 | 10.45 | 28.0 | |
| 460 | 89.5 | 11.19 | 15.0 | |||
|
|
| |||||
|
|
| 575 | 89.5 | 11.50 | 12.0 | |
|
|
| 208 | 87.5 |
| 15.8 | |
| Low | Vertical | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 87.5 |
| 15.8 | |
| Mid‐Low | Vertical | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 88.5 |
| 22.0 | |
| Mid‐High | Vertical | 230 | 88.5 |
| 22.0 | |
| 460 | 88.5 |
| 11.6 | |||
|
|
|
| ||||
|
|
| 575 | 88.5 |
|
| |
|
|
| 208 | 89.5 |
| 28.0 | |
| High | Vertical | 230 | 89.5 | 10.45 | 28.0 | |
| 460 | 89.5 | 11.19 | 15.0 | |||
|
|
| |||||
28 |
|
| 575 | 89.5 | 11.50 | 12.0 | |
|
| 208 | 87.5 |
| 15.8 | ||
|
|
|
| ||||
| Low | Horizontal | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 87.5 |
| 15.8 | |
| Mid‐Low | Horizontal | 230 | 87.5 |
| 15.4 | |
| 460 | 87.5 |
|
| |||
|
|
|
|
| |||
|
|
| 575 | 87.5 |
|
| |
|
|
| 208 | 88.5 |
| 22.0 | |
| Mid‐High | Horizontal | 230 | 88.5 |
| 22.0 | |
| 460 | 88.5 |
| 11.6 | |||
|
|
|
| ||||
|
|
| 575 | 88.5 |
|
| |
|
|
| 208 | 89.5 |
| 28.0 | |
| High | Horizontal | 230 | 89.5 | 10.45 | 28.0 | |
| 460 | 89.5 | 11.19 | 15.0 | |||
|
|
| |||||
|
|
| 575 | 89.5 | 11.50 | 12.0 |
NOTES:
1.Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2.Convert bhp to watts using the following formula:
watts = | bhp (746) | |
motor efficiency | ||
|
48/50PG and PM