Fan Performance — 50PG14 Horizontal Units
AIRFLOW |
| 0.2 | |
(Cfm) |
| ||
Rpm | Bhp | ||
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
| |||
| 0.4 |
| 0.6 | 0.8 |
|
Rpm | Bhp | Rpm | Bhp | Rpm | Bhp |
| 1.0 |
Rpm | Bhp |
3750 | 542 | 0.93 |
3950 | 564 | 1.07 |
4150 | 586 | 1.22 |
4350 | 608 | 1.38 |
4550 | 630 | 1.55 |
4750 | 652 | 1.75 |
4950 | 674 | 1.95 |
5150 | 697 | 2.18 |
5350 | 719 | 2.42 |
5550 | 742 | 2.67 |
5750 | 765 | 2.95 |
5950 | 788 | 3.24 |
6150 | 811 | 3.56 |
6250 | 822 | 3.72 |
607 | 1.10 |
626 | 1.25 |
645 | 1.41 |
665 | 1.58 |
685 | 1.77 |
705 | 1.97 |
726 | 2.19 |
747 | 2.42 |
767 | 2.67 |
789 | 2.94 |
810 | 3.22 |
831 | 3.53 |
8533.85
8644.02
665 | 1.27 |
683 | 1.43 |
701 | 1.60 |
719 | 1.78 |
737 | 1.98 |
756 | 2.19 |
775 | 2.42 |
794 | 2.66 |
814 | 2.92 |
834 | 3.20 |
854 | 3.49 |
874 | 3.81 |
8944.14
9054.32
719 | 1.44 |
735 | 1.61 |
752 | 1.78 |
769 | 1.98 |
786 | 2.18 |
804 | 2.40 |
822 | 2.64 |
840 | 2.89 |
858 | 3.16 |
877 | 3.45 |
896 | 3.76 |
915 | 4.08 |
9354.43
9444.61
770 | 1.62 |
785 | 1.79 |
800 | 1.97 |
816 | 2.17 |
832 | 2.39 |
849 | 2.62 |
866 | 2.86 |
883 | 3.13 |
901 | 3.41 |
918 | 3.70 |
936 | 4.02 |
955 | 4.36 |
973 | 4.71 |
983 | 4.89 |
PM
AIRFLOW |
| 1.2 | |
(Cfm) |
| ||
Rpm | Bhp | ||
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
| |||
| 1.4 |
| 1.6 | 1.8 |
|
Rpm | Bhp | Rpm | Bhp | Rpm | Bhp |
| 2.0 |
Rpm | Bhp |
48/50PG and
3750 |
| 1.79 |
3950 |
| 1.97 |
4150 |
| 2.16 |
4350 |
| 2.37 |
4550 |
| 2.59 |
4750 |
| 2.83 |
4950 |
| 3.09 |
5150 |
| 3.36 |
5350 |
| 3.65 |
5550 |
| 3.96 |
5750 |
| 4.28 |
5950 |
| 4.63 |
6150 | 1011 | 4.99 |
6250 | 1020 | 5.18 |
1.97
2.16
2.36
2.57
2.80
3.05
3.31
3.59
3.89
4.21
1013 4.54
1030 4.89
— —
— —
2.16
2.35
2.56
2.78
3.02
3.27
3.54
1002 3.83
1017 4.13
1033 4.46
1049 4.80
1065 5.16
— —
— —
2.35
2.55
2.76
2.99
3.23
1011 3.49
1025 3.77
1039 4.06
1054 4.38
1069 4.71
1084 5.06
— —
— —
— —
| 2.54 |
1003 | 2.75 |
1014 | 2.97 |
1024 | 3.20 |
1036 | 3.45 |
1049 | 3.72 |
1061 | 4.00 |
1075 | 4.30 |
1089 | 4.62 |
1103 | 4.96 |
— | — |
— | — |
— | — |
— | — |
LEGEND
Bhp - Brake Horsepower
High Range Motor/Drive Required
NOTES:
1.Motor drive range is 690 to 893 for low range motor/drive and 852 to 1055 rpm for high range motor/drive. All other rpms require a field‐supplied drive.
2.Maximum continuous bhp is 3.70 for low range motor/drive and 5.25 for high range motor/drive.
3.See General Fan Performance Notes.
| GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES | ||
1. | Static pressure losses from accessories and options | 4. | Extensive motor and drive testing on these units ensures |
|
| that the full horsepower range of the motor can be utilized | |
| to external static pressure before entering Fan Performance |
| with confidence. Using the fan motors up to the bhp rating |
| table. Refer to Accessory/FIOP Static Pressure information. |
| shown will not result in nuisance tripping or premature |
2. | Interpolation is permissible. Do not extrapolate. |
| motor failure. Unit warranty will not be affected. |
3. | Fan performance tables are based on wet coils, clean filters, | 5. | Use of a |
| and casing losses. Gas heat losses are included for 48 series |
| Recalculate the unit power supply MCA and MOCP if |
| units. |
| required. Contact your Carrier representative for details. |
|
| 6. | Use the following formula to calculate input watts: |
|
|
| Input Watts = Bhp x (746/Motor Eff) |