Accessory/FIOP Static Pressure Drops (in. wg)* − 48/50PM16−28
CFM | Economizer | ||
4000 | 0.02 | 0.17 | - |
4500 | 0.03 | 0.19 | - |
5000 | 0.04 | 0.21 | - |
5500 | 0.05 | 0.24 | - |
6000 | 0.06 | 0.27 | - |
6500 | 0.07 | 0.31 | 0.19 |
7000 | 0.08 | 0.35 | 0.21 |
7500 | 0.09 | 0.39 | 0.23 |
8000 | 0.1 | 0.43 | 0.26 |
8500 | 0.11 | 0.48 | 0.29 |
9000 | 0.12 | 0.52 | 0.31 |
9500 | 0.13 | 0.57 | 0.34 |
10000 | 0.15 | 0.62 | 0.37 |
10500 | 0.16 | - | 0.4 |
11000 | 0.17 | - | 0.43 |
11500 | 0.19 | - | 0.46 |
12000 | 0.2 | - | 0.5 |
LEGEND
FIOP -
*The static pressure must be added to the external static pressure. The sum and the evaporator
Accessory/FIOP Electric Heat Static Pressure Drop (in. wg) − 50PM16−28
CFM | Nominal Heater | Pressure Drop (in. | Nominal Heater | Pressure Drop (in. | Nominal Heater | Pressure Drop (in. | |
Size (kw) | wg) | Size (kw) | wg) | Size (kw) | wg) | ||
| |||||||
4800 |
| 0.01 |
| 0.02 |
| 0.03 | |
5000 |
| 0.01 |
| 0.02 |
| 0.04 | |
6000 |
| 0.02 |
| 0.04 |
| 0.06 | |
7000 | 25 | 0.03 | 50 | 0.06 | 75 | 0.08 | |
8000 | 0.04 | 0.08 | 0.12 | ||||
|
|
| |||||
9000 |
| 0.05 |
| 0.1 |
| 0.15 | |
10000 |
| 0.06 |
| 0.13 |
| 0.2 | |
11500 |
| 0.09 |
| 0.18 |
| 0.27 |
LEGEND | NOTES: |
FIOP - | 1. Heaters are rated at 240v, 480v, and 600v. |
| 2. The static pressure must be added to the external static pressure. The |
| sum and the evaporator |
| conjunction with the Fan Performance tables to determine blower rpm, bhp, |
| and watts. |