MODE — CONFIGURATION (cont)
ITEM | EXPANSION | RANGE | UNITS |
| DEFAULT |
COOL (cont) | Cooling Configuration |
|
|
|
|
3.ON | Fan Lev3 On Temperature | 0 to 100 | °F | no HumidiMiZer FIOP: | |
|
|
|
| 65 |
|
|
|
|
| HumidiMiZer FIOP: | |
|
|
|
| 88 | (20, PM16) |
|
|
|
| 68 | (2428)(PG0316) |
3.OFF | Fan Lev3 Off Temperature | 0 to 100 | °F | no HumidiMiZer FIOP: | |
|
|
|
| 55 |
|
|
|
|
| HumidiMiZer FIOP: | |
|
|
|
| 78 | (20, PM16) |
|
|
|
| 62 | (2428)(PG0316) |
HMZR | Humidimizer Config |
|
|
|
|
REHT | Humidimizer Equipped | No/Yes |
| No: no HumidiMiZer | |
|
|
|
| FIOP | |
|
|
|
| Yes: HumidiMiZer FIOP | |
R.DEC | Reheat2 Stage Decr. | 0 to 999 | secs | 60 |
|
| Time |
|
|
|
|
R.INC | Reheat2 Stage Incr. Time | 0 to 999 | secs | 300 | |
RH.FN | Reheat Fan Control | No/Yes |
| No (0314) | |
|
|
|
| Yes (1628) | |
RF.LV | Reheat ODF Fan On | 0 to 3 |
| 2 (0320) | |
| Level |
|
| 3 (2428) | |
RF. ON | Reheat ODF Fan On | 0 to 100 | °F | 75 | (PG0316) |
| Temp |
|
| 93 | (PG2024)(PM1628) |
|
|
|
| 85 | (PG 28) |
RF.OF | Reheat ODF Fan Off | 0 to 100 | °F | 70 | (PG0316) |
| Temp |
|
| 83 | (20, PM16) |
|
|
|
| 88 | (24)(PM 28) |
|
|
|
| 80 | (PG 28) |
RA.LO | Reheat2 OAT Limit A | 20 to 70 | °F | 40 |
|
RA.LP | Reheat2 SSP Lo Limit A | 50 to 100 | psig | 80 |
|
RA.HP | Reheat2 SSP Hi Limit A | 50 to 100 | psig | 90 |
|
RB.LO | Reheat2 OAT Limit B,C | 20 to 70 | °F | 50 |
|
RB.LP | Reheat2 SSP Lo Limit | 50 to 100 | psig | 80 |
|
| B,C |
|
|
|
|
RB.HP | Reheat2 SSP Hi Limit B,C | 50 to 100 | psig | 90 |
|
HEAT | Heating Configuration |
|
|
|
|
HT.TY | Type of Heat Installed | 0=No Heat |
| 0 (50 series with no elec | |
|
| 1=Gas |
| tric heat) | |
|
| 2=Electric |
| 1 (48 series) | |
|
|
|
| 2 (50 series with electric | |
|
|
|
| heat) | |
N.HTR | Number of Heat Stages | 1 to 2 |
| 1 (48 series 1phase, 50 | |
|
|
|
| series <15kW) | |
|
|
|
| 2 (48 series 3phase, 50 | |
|
|
|
| series >=15kW) | |
MRT.H | Heat Minimum On Time | 60 to 999 | sec | 120 | |
MOT.H | Heat Minimum Off Time | 60 to 999 | sec | 120 | |
H.DEC | Heat Stage Decrease | 120 to 999 | sec | 300 | |
| Time |
|
|
|
|
H.INC | Heat Stage Increase | 120 to 999 | sec | 450 | |
| Time |
|
|
|
|
FOD.E | Fanoff Delay, Elect Heat | 10 to 600 | sec | 30 |
|
FOD.G | Fanoff Delay, Gas Heat | 45 to 600 | sec | 45 |
|
HT.LO | Heating Lockout Temp | 40 to 125 | °F | 75 |
|
SAT |
|
|
|
|
|
SAT.H | SAT Heat Mode Sensing | Disable/En |
| Disable | |
|
| able |
|
|
|
SAM.L | Maximum SAT Lower | 85 to 200 | °F | 140 | |
| Level |
|
|
|
|
SAM.U | Maximum SAT Upper | 85 to 200 | °F | 160 | |
| Level |
|
|
|
|
SPT | Space Temperature |
|
|
|
|
HT.PD | SPT Heat Demand (+) | 0.5 to 5 | ^F | 1 |
|
| Level |
|
|
|
|
HT.ND | SPT Heat Demand () | 5 to 0.5 | ^F | 1 |
|
| Level |
|
|
|
|
H.LAG | Heat Thermal Lag Factor | 0 to 5 |
| 1 |
|
CCN TABLE/
COOL_CFG
HMZR_CFG
HEAT_CFG
CCN POINT | PAGE NO. |
LEV3ON
LEV3OFF |
|
| 24 |
REHEAT | 24 |
RSTAGDEC | 28 |
RSTAGINC | 28 |
RHFANCTL | 28 |
RHFANLEV | 28 |
RHFANON | 28 |
RHFANOFF | 28 |
OATLRH_A | 28 |
RHSSPL_A | 28 |
RHSSPH_A | 28 |
OATLRH_B | 28 |
RHSSPL_B | 28 |
RHSSPH_B | 28 |
| 15 |
HEATTYPE | 21 |
NUM_HEAT | 22 |
HMIN_ON | 22 |
HMIN_OFF | 22 |
HSTAGDEC | 21 |
HSTAGINC | 21 |
ELEC_FOD | 17 |
GAS_FOD | 17 |
OATLHEAT | 21 |
| 15 |
SAT_HEAT |
|
SATMAX_L
SATMAX_H
16
HDEM_POS
HDEM_NEG
HEAT_LAG
48/50PG and PM