Carrier 48/50PG C03-14 Low Voltage Terminal Strip, Low−Voltage Terminal Strip, PM16−28 size units

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 76
Image 76
Low Voltage Terminal Strip

Low Voltage Terminal Strip

The circuit breakers for the low voltage control transformers,

(TB1 on PG03−16 size and TB2 on PG20−28 and

interface connection for the Carrier Comfort Network(CCN)

communication, and interface connection for the Local Equipment

PM16−28 size units)

Network (LEN) communications are also located on the low

This circuit board provides a connection point between the major

voltage terminal strip.

control boards and a majority of the field-installed accessories. (See

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 43 and Table 26.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

14

7

7

J13

J10

J11

RUN TEST

J12

 

SEPARATION OF CIRCUITS TO EACH 24V TRANSFORMER MUST BE MAINTAINED

 

 

 

 

FIRE SHUTDOWN

T55

FAN STATUS

1 2 3 4 5 6 7 8 9 10 R Y1 Y2 W1 W2 G C X 1 2 1 2 3 1 2

8

(+) (COM) (-) SHIELD

CCN

LEN CCN

48HG500382

48/50PG and PM

C07029

Fig. 43 − Low−Voltage Terminal Strip

Table 26 – Field Connection Terminal Strip

TERMINAL LABEL

DISPLAY

POINT DESCRIPTION

NAME

 

 

1

 

24 VDC Sensor Loop power

2

IAQ

Indoor air quality sensor

3

 

Air quality & humidity sensor common

4

OAQ or

Outdoor air quality sensor or

SP.RH

Relative humidity sensor

 

5

RM.OC

Remote occupancy switch

6

 

Switch power (ENTH, RM.OC, IAQ.S)

7

ENTH or

Outdoor enthalpy switch, or

IAQ.S

Indoor air quality switch

 

8*

EC.CP

Economizer commanded position actu­

ator (when in digital control)

 

 

9

 

Economizer signal common

10*

EC.AP

Economizer position feedback (when in

analog control)

 

 

R

 

24 VAC power

Y1

Y1

Thermostat Y1 (1st stage cool)

Y2

Y2

Thermostat Y2 (2nd stage cool)

W1

W1

Thermostat W1 (1st stage heat)

W2

W2

Thermostat W2 (2nd stage heat)

G

G

Thermostat G (Fan)

C

 

24 VAC common

X

ALRM

Alarm output (normally open)

FIRE SHUTDOWN

FDWN

Fire shutdown switch 24 VAC output

or

or

or

HUMIDISTAT 1*

HUM

Humidistat switch input

FIRE SHUTDOWN

FDWN

Fire shutdown switch input

or

or

or

HUMIDISTAT 2*

HUM

Humidistat switch 24 VAC output

T55

SPT

Space temperature (T55/56)

1-2

 

 

T55

SPTO or

Space temperature offset (T56) or

2-3

RAT

Return air temperature

FAN STATUS

 

NOT USED

1-2

 

 

 

LEN

 

Local Equipment Network (LEN)

CCN

 

Carrier Comfort Network (CCN)

* Refer to Third Party Control section for more information

SENSOR

TYPE OF I/O

CONNECTION

LOCATION

PIN NUMBER

 

 

24 VDC output

J10, 17

return/space

4-20 mA input

J10, 16

 

Ground

J10, 15

field installed

4-20 mA input

J10, 14

field installed

24 VAC input

J10, 13

 

24 VAC output

J10, 11-12

economizer, or

24 VAC input

J10, 9-10

return/space

 

 

economizer

2-10 VDC output

J10, 6-8

 

Ground

J10, 3-5

economizer

communication

J10, 1-2

2-10 VDC output

 

 

 

24 VAC output

J11, 11-14

space

24 VAC input

J11,10

space

24 VAC input

J11, 9

space

24 VAC input

J11, 7-8

space

24 VAC input

J11, 6

space

24 VAC input

J11, 5

 

24 VAC output

J11, 2-4

 

24 VAC output

J11, 1

supply/return/

switch input

J12, 7

space

 

 

supply/return/

switch input

J12, 6

space

 

 

space

10k thermistor

J12, 4-5

space or return

10k thermistor

J12, 3-4

 

 

J12, 1-2

 

communication

J13, 6-8, 4-5

 

communication

J13, 1-3, 4-5

76

Page 76
Image 76
Carrier 48/50PG C03-14 manual Low Voltage Terminal Strip, Low−Voltage Terminal Strip, Field Connection Terminal Strip