Table 5 – Outdoor Fan Level Transitions

For 48/50PG03−07 units, one outdoor fan is controlled in all modes by the MotormasterR sensing on circuit A.

For 48/50PG08−14 units, 2 outdoor fans are controlled in all modes by the Motormaster sensing on circuit A.

For 48/50PG16 units, 3 outdoor fans are controlled in normal cooling and sub−cooling Reheat1 modes by the Motormaster sensing circuit A. Two of the fans are additionally controlled with OFC.1 output, based on outdoor temperature, during the hot−gas Reheat2 mode (level 1 = 1 fan, level 2 = 3 fans).

For 48/50PG20−28 and 48/50PM16−28 units, contactor OFC1 controls power to the Motormaster which controls OFM1 and OFM4. Contactor OFC2 controls the remaining two fans (16 and 20 size) or remaining 4 fans (24 and 28 sizes).

48/50PG and PM

Table 5 – Outdoor Fan Level Transitions

FAN LEVEL

OUTDOOR TEMPERATURE (F)

Without Humidi-MiZer™ System

With Humidi-MiZer System

 

Level 2 On

55 (sizes 03-20), 45 (sizes 24-28)

61 (PG03-16, sizes 24-28), 68 (size 20, PM16)

Level 2 Off

45 (PG03-16), 50 (size 20, PM16), 40 (sizes 24-28)

57

Level 3 On

65

68 (PG03-16, size 24-28), 88 (size 20, PM16)

Level 3 Off

55

62 (PG03-16, size 24-28), 78 (size 20, PM16)

NOTE: Where not specified, the models are both PG and PM. Levels 0 and 1 are only in play if the OAT is lower than the Level 2 On temperature and the pressure is not above its respected max.

Table 6 – 48/50PG03−16 Fan Level Control of Fans and Contactors

FAN LEVEL

48/50PG03-07

48/50PG08-14

48/50PG16

Standard Unit

Humidi-MiZer Unit

Standard Unit

Humidi-MiZer Unit

Standard Unit

Humidi-Mizer Unit

 

0

OFF

OFF

OFF

OFF

OFF

OFF

 

OFC1 On

Motormaster

OFC1 On,

Motormaster

OFC1 On,

Motormaster, OFC1

1

OFC2 Off

OFC2 Off

Off

Low Speed

Fan 1

Fan 1 and Fan 2

 

Fan 1 On

Fan 1 On

Fan 2

 

 

 

 

 

OFC1 Off

 

OFC1 On,

 

OFC1 On,

Motormaster, OFC1

2

N/A

OFC2 On

N/A

OFC2 On

On

High Speed

 

 

Fan 1 and 2 On

 

Fan 1, 2, 3 On

Fan 1, 2, 3

 

 

 

 

3

N/A

N/A

N/A

N/A

N/A

N/A

Table 7 – 48/50PG20−28 and PM16−28 Fan Level Control of Outdoor Fan contactors (OFC(X))

FAN LEVEL

With Humidi-MiZer System

With Humidi-MiZer System

Circuit A

Circuit B

Circuit A and B

 

0

-

-

-

1

1

3

1

1, 3 (PG28)

 

 

 

2

1,2 (20, PM16)

2, 3 (20, PM16)

1, 2 (20, PM16)

2 (24-28)

2 (24-28)

2 (24-28)

 

3

1,2

2, 3

1, 2

1, 2, 3 (PG28)

 

 

 

20