APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — OUTPUTS
|
|
|
| CCN TABLE/ |
| CCN | DISPLAY | |
ITEM | EXPANSION | RANGE | UNITS | CCN POINT | WRITE | WRITE | ||
|
|
|
|
| STATUS | STATUS | ||
|
|
|
|
|
| |||
|
|
|
| STATUS DISPLAY |
|
|
| |
OUTPUTS |
|
|
| UOUTPUT |
|
|
| |
FANS | Fan Outputs |
|
|
|
|
|
| |
IDF | Indoor Fan State | On/Off |
|
| IDFSTATE |
|
| |
F.SPD | Commanded Fan Speed | xxx |
|
| FANSPEED |
|
| |
OFC.1 | Outdoor Fan 1 Relay | On/Off |
|
| OFC_1 |
|
| |
OFC.2 | Outdoor Fan 2 Relay | On/Off |
|
| OFC_2 |
|
| |
OFC.3 | Outdoor Fan 3 Relay | On/Off |
|
| OFC_3 |
|
| |
COOL | Cool Outputs |
|
|
|
|
|
| |
CMP.A | Circuit A Compressor(s) | On/Off |
|
| COMP_A |
|
| |
CMP.B | Compressors B | On/Off |
|
| COMP_B |
|
| |
CMP.C | Compressors C | On/Off |
|
| COMP_C |
|
| |
CCH | Crankcase Heat Relay | On/Off |
|
| CCH |
|
| |
CRC | Cool>Reheat1 Control | On/Off |
|
| CRC |
|
| |
RH2.A | Reheat2 Valve A | On/Off |
|
| RH2_A |
|
| |
RH2.B | Reheat2 Valve BC | On/Off |
|
| RH2_B |
|
| |
HEAT | Heat Outputs |
|
|
|
|
|
| |
HT.1 | Heat Stage 1 Relay | On/Off |
|
| HEAT_1 |
|
| |
HT.2 | Heat Stage 2 Relay | On/Off |
|
| HEAT_2 |
|
| |
ECON | Economizer Outputs |
|
|
|
|
|
| |
EC.CP | Econo Commanded Position | 0 to 100 | % |
| ECONOCMD | forcible | forcible | |
EC.AP | Econo Actual Position | 0 to 100 | % |
| ECONOPOS |
|
| |
PE.1 | Power Exhaust 1 Relay | On/Off |
|
| PE_1 | forcible |
| |
PE.2 | Power Exhaust 2 Relay | On/Off |
|
| PE_2 | forcible |
| |
ALRM | Alarm Relay | On/Off |
|
| ALMOUT | forcible |
|
48/50PG and PM
99