Carrier 48/50PG C03-14, 48/50PM C16-28 Fan Performance — 48PGE08 Vertical Units, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 120
Image 120
Fan Performance — 48PGE08 Vertical Units

48/50PG and PM

Fan Performance — 48PGE08 Vertical Units

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

0.2

 

 

0.4

 

0.6

0.8

 

1.0

 

 

(Cfm)

 

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

 

2250

463

0.35

541

0.46

611

0.58

677

0.70

738

0.83

 

2400

481

0.41

556

0.52

623

0.64

687

0.77

747

0.90

 

2550

499

0.47

571

0.59

637

0.72

698

0.85

756

0.99

 

2700

518

0.54

587

0.66

650

0.80

710

0.93

766

1.08

 

2850

537

0.62

603

0.75

665

0.88

722

1.03

777

1.18

 

3000

556

0.70

620

0.84

680

0.98

735

1.13

789

1.28

 

3150

575

0.79

637

0.93

695

1.08

749

1.24

801

1.40

 

3300

595

0.89

655

1.04

711

1.19

764

1.35

814

1.52

 

3450

615

1.00

673

1.16

727

1.32

778

1.48

828

1.65

 

3600

635

1.12

691

1.28

744

1.44

794

1.62

842

1.79

 

3750

655

1.24

710

1.41

761

1.58

810

1.76

856

1.94

 

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

1.2

 

 

1.4

 

1.6

1.8

 

2.0

 

 

(Cfm)

 

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

 

2250

797

0.96

852

1.10

904

1.25

 

1.40

1002

1.55

 

2400

803

1.04

857

1.19

909

1.34

 

1.49

1006

1.65

 

2550

811

1.13

864

1.28

914

1.44

 

1.60

1009

1.76

 

2700

820

1.23

871

1.38

921

1.54

 

1.71

1014

1.88

 

2850

829

1.33

879

1.49

928

1.66

 

1.83

1019

2.00

 

3000

840

1.44

888

1.61

936

1.78

 

1.95

1026

2.13

 

3150

851

1.56

898

1.73

944

1.90

 

2.08

1033

2.27

 

3300

862

1.69

909

1.86

954

2.04

 

2.23

1040

2.41

 

3450

875

1.82

920

2.00

964

2.19

1007

2.38

1049

2.57

 

3600

888

1.97

932

2.15

975

2.34

1017

2.54

1058

2.73

 

3750

901

2.12

944

2.31

987

2.51

1028

2.71

1068

2.91

 

LEGEND

 

 

 

 

NOTES:

 

 

 

 

 

Bhp - Brake Horsepower

 

 

 

 

1.

Motor drive range is 568 to 771 rpm for low range motor/drive and 812 to 1015 rpm

 

High Range Motor/Drive Required

 

 

 

for high range motor/drive. All other rpms require a field‐supplied drive.

 

 

2. Maximum continuous bhp is 2.40 for low range motor/drive and 3.10 for high range motor/drive.

3. See General Fan Performance Notes.

Fan Performance — 48PGF08 Vertical Units

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

0.2

 

 

0.4

 

0.6

0.8

 

1.0

 

 

(Cfm)

 

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

 

2250

468

0.36

545

0.46

615

0.58

680

0.71

741

0.83

 

2400

486

0.41

560

0.53

627

0.65

691

0.78

750

0.91

 

2550

505

0.48

576

0.60

641

0.72

702

0.86

760

1.00

 

2700

524

0.55

592

0.68

655

0.81

714

0.95

771

1.09

 

2850

544

0.63

609

0.76

670

0.90

728

1.04

782

1.19

 

3000

564

0.71

627

0.85

686

1.00

741

1.14

794

1.30

 

3150

584

0.81

645

0.95

702

1.10

756

1.26

807

1.42

 

3300

604

0.91

663

1.06

719

1.22

771

1.38

821

1.54

 

3450

625

1.02

682

1.18

736

1.34

787

1.51

835

1.68

 

3600

646

1.15

701

1.31

753

1.48

803

1.65

850

1.82

 

3750

667

1.28

720

1.45

771

1.62

819

1.80

865

1.98

 

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

1.2

 

 

1.4

 

1.6

1.8

 

2.0

 

 

(Cfm)

 

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

 

2250

799

0.97

854

1.11

907

1.26

 

1.40

1005

1.56

 

2400

807

1.05

860

1.20

912

1.35

 

1.50

1008

1.66

 

2550

815

1.14

867

1.29

918

1.45

 

1.61

1013

1.77

 

2700

824

1.24

875

1.40

925

1.56

 

1.72

1018

1.89

 

2850

834

1.35

884

1.51

932

1.67

 

1.84

1024

2.02

 

3000

845

1.46

894

1.63

941

1.80

 

1.97

1030

2.15

 

3150

857

1.58

904

1.75

950

1.93

 

2.11

1038

2.29

 

3300

869

1.71

916

1.89

960

2.07

1004

2.25

1046

2.44

 

3450

882

1.85

928

2.03

971

2.22

1014

2.41

1055

2.60

 

3600

896

2.00

940

2.19

983

2.38

1025

2.57

1065

2.77

 

3750

910

2.16

953

2.35

995

2.55

1036

2.75

1076

2.95

 

LEGEND

 

 

 

 

NOTES:

 

 

 

 

 

Bhp - Brake Horsepower

 

 

 

 

1.

Motor drive range is 568 to 771 rpm for low range motor/drive and 812 to 1015 rpm

 

High Range Motor/Drive Required

 

 

 

for high range motor/drive. All other rpms require a field‐supplied drive.

 

 

2. Maximum continuous bhp is 2.40 for low range motor/drive and 3.10 for high range motor/drive.

3. See General Fan Performance Notes.

120

Page 120
Image 120
Carrier 48/50PG C03-14 Fan Performance — 48PGE08 Vertical Units, Fan Performance — 48PGF08 Vertical Units, 48/50PG and PM